36
H050002740 rel. 1.1 - 17.05.2021
Technical specifications
ENG
5.1 Connector table
Ref.
W
iring terminals
W
ire cross- sec-
tion (mm
2
)
Lma
x
(m)
J1
Spade: 6.3 mm female
1.5
-
Spade: 6.3 mm female
1.5
-
Spade: 6.3 mm female
1.5
-
J2
Lumberg 3575 03 …, MOLEX 91627-1502, TE 1-1740533-3
0.75
3
J3
JST XHP-7
0.3
3
J4
JST XHP-7
0.3
3
J5
Not used
-
-
J6
Lumberg 3575 02 k10 Stocko 7262-002-004-960-000-00-g
J7
Lumberg 3612 03…, Sauro CUF03001, Weco 130-P-020/3
0.13
10
J8
JST XHP-4 connector (user terminal side: JST ZHR-4 pin) +SXH-002T-P0.6 (terminal)
0.13
10
J9
Degson 15EDGK-3.81-03P-14-00A(H), Phoenix Contact MC 1.5/3-ST-3.81
0.081 to 1.31
500
J10
MOLEX Micro- FIT 43025- 0800, FCI Minitek 0430300004, FCI10127718-002PLF
(terminal) 10127716-08LF (connector) + Molex
0.05 to 0.52
10
J11
MOLEX Micro- FIT 43025- 1000, FCI Minitek 0430300004, FCI10127718-002PLF
(terminal) 10127716-10LF (connector) + Molex
0.05 to 0.52
10
J12
DEGSON 2EDGK-5.08-03P-14-13A(H)M3, PHOENIX CONTACT MSTB 2.5/3-ST-5.08, SAURO CIF03005
0.21 to 2.5
10
J13
DEGSON 2EDGK-5.08-02P-14-13A(H)M3, PHOENIX CONTACT MSTB 2.5/2-ST-5,08, SAURO CIF02005
0.21 to 2.5
10
J14
CAREL EXV unipolar valve connector
Pre-wired
Tab.
5
.c
5.2 Rated current values
The following table shows the rated input current and output current values, as well as the specifications for sizing the cables
(cross-section, maximum length) and the fuses.
Model
Rated input
current
Protection
fuses (*)
Protection
fuses for USA -
CAN (**)
Rated output
current
Power cable
size
Minimum
compressor
cable size
Ma
x
imum
compressor
cable length
(A)
(A)
(A)
(A)
(mm
2
)
(mm
2
)
(m)
all versions
115 Vac / Small
3.8
16
15
1.3
1.5
0.75
3
all versions
230 Vac / Small
2
16
15
1.3
1.5
0.75
3
all versions
230 Vac / Medium
3.8
16
15
2.6
1.5
0.75
3
Tab.
5
.d
(*) type gG;