Checks before commissioning
ENG
Table of initial configuration parameters
Cat.
Description
Def
Min
Ma
x
UOM
CM
Compressor model (0 = FC-E40, 1 = FC-E57, 2 = FC-E100)
0
2
-
H0
BMS serial address
199
1
247
-
H3
BMS serial protocol (0 = CAREL, 1 = MODBUS)
1
0
1
-
/P1
Type of probe, group 1 (S1, S2, S3)
0 = PT1000 Standard Range
3 = Reserved
1 = NTC Standard Range
4 =Reserved
2 = Reserved
5 = NTC-HT
1
0
5
-
P1
Electronic valve: 0 = not present, 1 = OnBoard driver
1
0
1
-
/P2
Type of probe, group 2 (S4, S5)
1 = NTC Standard Range
4 = Reserved
2 = 0-5 V
5 = NTC-HT
3 = 4-20 mA
6 = 0.5-4.5V
6
1
6
-
/P3
Type of probe, group 3 (S6)
0 = PT1000 Standard Range
4 = 0-10V
1 = NTC Standard Range
5 = NTC-HT
2 = 0-5 V
6 = 0.5-4.5V
3 = 4-20 mA
1
0
6
-
/Fd
Assign superheated gas temperature probe position (tGS)
0 = Function disabled
6 = S6
1 = S1
-1 = S11: serial probe
2 = S2
-2 = S12: serial probe
3 = S3
-3 = S13: serial probe
4 = S4
-4 = S14: serial probe
5 = S5
3
-4
6
-
/FE
Assign saturated evaporation pressure/temperature probe position (PEu/tEu)
0 = Function disabled
6 = S6
1 = S1
-1 = S11: serial probe
2 = S2
-2 = S12: serial probe
3 = S3
-3 = S13: serial probe
4 = S4
-4 = S14: serial probe
5 = S5
4
-4
6
-
/UE
Maximum value for saturated evap. pressure/temp. probe (PEu/tEu)
9.3
/LE
200
barg (psig)
/LE
Minimum value for saturated evap. pressure/temp. probe (PEu/tEu)
-1
-1
/UE
barg (psig)
End
End commissioning wizard
-
-
-
-
Tab. 4.c
Table of initial configuration parameters
Code
Description
Def
Min
Ma
x
UOM
St
Control set point
50
r1
r2
°C (°F)
P3
Superheat control set point
10
0
25
K
P4
Proportional gain for superheat control
15
0
100
P5
Integral time for superheat control
0 = function disabled
150
0
900
s
P6
Derivative time for superheat control
0 = function disabled
5
0
100
s
cPr
PID control: proportional gain
2
0
100
%/°C
ctl
PID control: integral time
100
0
900
s
cdt
PID control: derivative time
0
0
100
s
d0
Type of defrost
0 = heater by temperature
1 = hot gas by temperature
2 = heater by time
3 = hot gas by time
4 = heater by time with temperature control
0
0
4
-
dt1
End defrost temperature (read by Sd)
8
-50
50
°C (°F)
dP1
Maximum defrost duration
45
1
240
min
dd
Dripping time after defrost (fans off )
0 = no dripping
2
0
15
min