Installation
ENG
Horizontal short side
50002730_011_R01
16 (0.6)
186 (7.3)
=
=
32 (1.3)
Fig. 3.k
3.4 Cooling
Sufficient air flow (at least 2m/s) and air change must be provided inside the compartment where the system is placed (made
up of fan, compressor and control). The air flow must hit the control from the opposite side to the electrical connection
terminals, to cool the heatsink and compressor. A support has been inserted for housing a 40 mm side fan near the heatsink.
The maximum ambient temperature is 45 ° C.
50002730_012_R01
Fig. 3.l
Caution
:
•
ensure the minimum required air flow of 2 m/s across the heat sink, as specified in the table of technical specifications;
•
avoid shielding the air flow due to the installation of other components.
•
the maximum ambient temperature is 45 ° C.