Checks before commissioning
ENG
Code Description
Reset
Effect
Buzzer LED Priority
Delay
(s)
No. of
activat.
Evaluation
period (s)
A49
Power supply volt-
age below mini-
mum threshold
Semi-auto
Compressor off. Up to five restart attempts
without considering the timers
9
9
Normal
(serious
when
manual
reset
required)
0
5
3600
A50
PFC error
Semi-auto
Compressor off. Up to five restart attempts
without considering the timers
9
9
Normal
(serious
when
manual
reset
required)
0
5
3600
A52
Inverter module
error
Semi-auto
Compressor off. Up to five restart attempts
without considering the timers
9
9
Normal
(serious
when
manual
reset
required)
0
5
3600
ACM
Compressor error
(E57 or E100 on
400W inverter)
Automatic
Compressor off, stop control
9
9
Serious
-
-
-
blo
Valve blocked
Manual/
disabled
when P14=0
Signal only
9
9
Normal
1500
-
-
dA
Delayed alarm
from external
contact
Automatic
Control in duty setting mode (par. A6), defrost
stopped (if in progress)
9
9
Normal
Par.
A11
-
-
dOr
Alarm 1 door open Automatic
Compressor off
9
9
Normal
Par.
A10
-
-
DSD
BLDC - Start
failure 2
Automatic
Failed compressor start due to too high
deltaP
9
9
Normal
0
-
900
E1
Probe S1 fault
Automatic
Depending on the probe connected to S1
(possible activation of duty setting mode
based on parameter /4 and c4)
9
9
Normal
0
-
-
E2
Probe S2 fault
Automatic
Depending on the probe connected to S2
(possible deactivation of end defrost temper-
ature control)
9
9
Normal
0
-
-
E3
Probe S3 fault
Automatic
Depending on the probe connected to S3
(possible activation of duty setting mode
based on parameter /4 and c4)
9
9
Normal
0
-
-
E4
Probe S4 fault
Automatic
Depending on the probe connected to S4
(possible changeover to superheat calcula-
tion based on parameter P15)
9
9
Normal
0
-
-
E5
Probe S5 fault
Automatic
Depending on the probe connected to S5
9
9
Normal
0
-
-
E6
Probe S6 fault
Automatic
Depending on the probe connected to S6
9
9
Normal
0
-
-
E11
Serial probe S11
not updated
Automatic
Depending on the probe associated with S11
9
9
Normal
0
-
-
E12
Serial probe S12
not updated
Automatic
Depending on the probe associated with S12
9
9
Normal
0
-
-
E13
Serial probe S13
not updated
Automatic
Depending on the probe associated with S13
9
9
Normal
0
-
-
E14
Serial probe S14
not updated
Automatic
Depending on the probe associated with S14
9
9
Normal
0
-
-
E18
Evaporator fan
Automatic
-
-
9
Warning
0
-
-
E19
Condenser fan
Automatic
-
-
9
Warning
0
-
-
EnL
BLDC - Out of
envelope
Semi-auto
Compressor off
9
9
Normal
60
3
3600
Err
No terminal-con-
troller communic.
Automatic
-
-
-
Normal
0
-
-
Etc
Real time clock not
updated
Automatic
Possible faults in programmed functions (e.g.
defrost)
9
9
Normal
0
-
-