ENG
“FLSTDMAHUE” +030220961 - rel. 1.1 - 28.08.2019
68
Screen
Display description
Description/notes
Def.
UOM
Min
Max
Value description
Type
R/W
Carel Addr.
Ha60,
Ha63
Ha66,
Ha69
Ha72,
Ha75
Ha78,
Ha81
Actuator type
None
-
0
9
0-1: None ¦ 2: Air actuator ¦ 3,4: Valve
actuator¦ 5: None ¦ 6: Fire-smoke damper ¦ 7:
None ¦ 8: VAV actuator¦ 9: None
I
R/W
-
Addressing mode
Manual
-
0
1
0: Manual ¦ 1: Auto
D
R/W
-
SN: 00000-00000-000-000
0
-
0
9
I
R/W
-
Address actuator
Enable addressing
No
-
0
1
0:No¦ 1:Yes
D
R/W
Ha61,
Ha64
Ha67,
Ha70
Ha73,
Ha76
Ha79,
Ha82
Enable external input/probe
No
-
No
Yes
0:No¦1:Yes
D
R/W
-
Type
NTC
-
0:NTC ¦ 2:0…1V ¦ 3:0…10V ¦
5: ON/OFF
I
R/W
-
Min value
0
-
-999.9
Max
A
R/W
-
Max value
0
-
Min
999.9
A
R/W
-
Ha62,
Ha65
Ha68,
Ha71
Ha74,
Ha77
Ha80,
Ha83
Position or air flow limits
Minimum
0
%
0
Lim_max
A
R/W
-
Maximum
0
%
Lim_min
100
A
R/W
-
Ha91
…
Ha96
Serial probe n°1…6
Address
128
-
128
159
I
R/W
-
Type
Temperature
-
0
1
0:Temperature ¦ 1: Temphumidity
D
R/W
-
Default installation
No
-
No
Yes
0:No¦ 1:Yes
D
R/W
-
Screen
Display description
Description/notes
Def.
UOM
Min
Max
Value description
Type
R/W
Carel addr.
H. Manufacturer
b. I/O
configuration
Analog inputs
Hb01
Supply temperature
Position
--
-
0
99
I
R/W
-
Type
NTC
-
0
4
0:NTC ¦ 1:Pt1000 ¦ 2:0…1V ¦ 3:0…10V
¦ 4:4…20mA
I
R/W
-
MIN limit
0
°C
-50
MAX limit
A
R/W
-
MAX limit
0
°C
MIN limit
200
A
R/W
-
Hb02
Return temperature
Position
--
-
0
99
I
R/W
-
Type
NTC
-
0
4
0:NTC ¦ 1:Pt1000 ¦ 2:0…1V ¦ 3:0…10V
¦ 4:4…20mA
I
R/W
-
MIN limit
0
°C
-50
MAX limit
A
R/W
-
MAX limit
0
°C
MIN limit
200
A
R/W
-
Hb03
External temperature
Position
--
-
0
99
I
R/W
-
Type
NTC
-
-
-
0:NTC ¦ 1:Pt1000 ¦ 2:0…1V ¦ 3:0…10V
¦ 4:4…20mA
I
R/W
-
MIN limit
0
°C
-50
MAX limit
A
R/W
-
MAX limit
0
°C
MIN limit
200
A
R/W
-
MIN limit
0
°C
-50
MAX limit
A
R/W
-
MAX limit
0
°C
MIN limit
200
A
R/W
-
Type
2:0…1V ¦ 3:0…10V ¦ 4:4…20mA
I
R/W
-
Hb04
Room temperature
Position
--
-
0
99
I
R/W
-
Type
NTC
-
-
-
0:NTC ¦ 1:Pt1000 ¦ 2:0…1V ¦ ¦ 3:0…10V
¦ 4:4…20mA
I
R/W
-
MIN limit
0
°C
-50
MAX limit
A
R/W
-
MAX limit
0
°C
MIN limit
200
A
R/W
-
Hb05
Supply humidity
Position
--
-
0
99
I
R/W
-
Type
2:0…1V ¦ 3:0…10V ¦ 4:4…20mA
I
R/W
-
MIN limit
%RH
0
MAX limit
I
R/W
-
MAX limit
%RH
MIN limit
100
I
R/W
-
Hb06
Return humidity
Position
--
-
0
99
I
R/W
-
Type
2:0…1V ¦ 3:0…10V ¦ 4:4…20mA
I
R/W
-
MIN limit
%RH
0
MAX limit
I
R/W
-
MAX limit
%RH
MIN limit
100
I
R/W
-
Hb07
External humidity
Position
--
-
0
99
I
R/W
-
Type
2:0…1V ¦ 3:0…10V ¦ 4:4…20mA
I
R/W
-
MIN limit
%RH
0
MAX limit
I
R/W
-
MAX limit
%RH
MIN limit
100
I
R/W
-
Hb08
Room humidity
Position
--
-
0
99
I
R/W
-
Type
2:0…1V ¦ 3:0…10V ¦ 4:4…20mA
I
R/W
-
MIN limit
%RH
0
MAX limit
I
R/W
-
MAX limit
%RH
MIN limit
100
I
R/W
-
Hb09
Supply pressure position
Position
--
-
0
99
I
R/W
-
Type
2:0…1V ¦ 3:0…10V ¦ 4:4…20mA
I
R/W
-
MIN limit
Pa
0
MAX limit
I
R/W
-
MAX limit
Pa
MIN limit
5000
I
R/W
-
Hb10
Return pressure position
Position
--
-
0
99
I
R/W
-
Type
2:0…1V ¦ 3:0…10V ¦ 4:4…20mA
I
R/W
-
MIN limit
Pa
0
MAX limit
I
R/W
-
MAX limit
Pa
MIN limit
5000
I
R/W
-
Hb11
Frost protection temp.
Position
--
-
0
99
I
R/W
-
Type
0:NTC ¦ 1:Pt1000 ¦ 2:0…1V ¦ 3:0…10V
¦ 4:4…20mA
I
R/W
-
MIN limit
0
°C
-50
MAX limit
A
R/W
-
MAX limit
0
°C
MIN limit
200
A
R/W
-