Screen
index
Display description
Description/notes
Def.
UOM
Min
Max
Value
description
Type
R/W
Carel
Address
A. On/Off Unit
A01
On-Off Unit
0
-
0
4
0: OFF ¦
1: COMFORT ¦
2: PRECOMFORT¦
3: ECONOMY ¦
4: AUTO
I
R/W
12
Reset time
4
Hour
0,5
16
I
R
-
Override for
-
Hour
0,5
16
I
R
-
Enable auto-resume
No
-
No
Yes
0:No¦ 1:Yes
I
R/W
-
B. Setpoint
B01
Temperature
Current temperature set point
0
°C
-99.9
99.9
A
R
93
Humidity
Current humidity set point
0
% RH
0
100
I
R
13
External compensation
Enable: Gfc08-Gfc09
Config.: Hb03
0
°C
-99.9
99.9
A
R
-
AIN Offset
Enable: Ha19
Configure: Hb23
0
°C
-99.9
99.9
A
R
25
B02
Comfort temp. Summer
Comfort room temp. set point (cooling)
23
°C
Min. temp. set
limit in coo-
ling (Gfc02)
Max. temp.
set limit in co-
oling (Gfc02)
A
R/W
94
Comfort temp. Winter
Comfort room temp. set point (heating)
23
°C
Min. temp. set
limit in hea-
ting (Gfc02)
Max. temp.
set limit in he-
ating (Gfc02)
A
R/W
95
Comfort humid. Summer
Comfort room humidity set point (cooling)
50
%r.H.
Min. humid.
set limit in co-
oling (Gfc03)
Max. humid.
set limit in co-
oling (Gfc03)
I
R/W
14
Comfort humid. Winter
Comfort room humidity set point (heating)
50
%r.H.
0
100
I
R/W
15
B03
Pre-comfort temp. Summer
Precomfort room temp. set point (cooling)
25
°C
Min. temp. set
limit in coo-
ling (Gfc02)
Max. temp.
set limit in co-
oling (Gfc02)
Pre-comfort temp. Winter
Precomfort room temp. set point (heating)
21
°C
Min. temp. set
limit in hea-
ting (Gfc02)
Max. temp.
set limit in he-
ating (Gfc02)
Pre-comfort humid. Summer Precomfort room humidity set point (cooling)
55
%r.H.
0
100
I
R/W
16
Pre-comfort humid. Winter
Precomfort room humidity set point (heating)
45
%r.H.
0
100
I
R/W
17
B04
Economy temp. Summer
Economy room temp. set point (cooling)
27
°C
Min. temp. set
limit in coo-
ling (Gfc02)
Max. temp.
set limit in co-
oling (Gfc02)
A
R/W
98
Economy temp. Winter
Economy room temp. set point (heating)
19
°C
Min. temp. set
limit in hea-
ting (Gfc02)
Max. temp.
set limit in he-
ating (Gfc02)
A
R/W
99
Economy humid. Summer
Economy room humidity set point (cooling)
60
%r.H.
0
100
I
R/W
18
Economy humid. Winter
Economy room humidity set point (heating)
40
%r.H.
0
100
I
R/W
19
B11
Regulation loop 1
(see Ha20…Ha23;
Gfc36…Gfc39)
Setpoint
0
-
-3200
3200
A
R/W
148
Differential
0
-
-3200
3200
A
R/W
149
Integral time
0
s
0
999
I
R/W
129
B12
Regulation loop 2
Setpoint
0
-
-3200
3200
A
R/W
150
Differential
0
-
-3200
3200
A
R/W
151
Integral time
0
s
0
999
I
R/W
130
B13
Regulation loop 3
Setpoint
0
-
-3200
3200
A
R/W
152
Differential
0
-
-3200
3200
A
R/W
153
Integral time
0
s
0
999
I
R/W
131
B14
Regulation loop 4
Setpoint
0
-
-3200
3200
A
R/W
154
Differential
0
-
-3200
3200
A
R/W
155
Integral time
0
s
0
999
I
R/W
132