ENG
“FLSTDMAHUE” +030220961 - rel. 1.1 - 28.08.2019
39
Temperature priority
Temp.
request
Humidity
request
Preheating coil
Cooling
coil
Reheating
coil
Humidi
-
fier
Heating
Dehumidif.
Based on tem-
perature control
probe
Off
If “integration”
Cascade
control
Off
Cooling
Humidific.
Off
Based on
temp. con-
trol probe
Off
Waits for
tempe-
rature
set point
to be
reached
Tab. 9.b
Note:
in the case of request of cooling and dehumidification the control
considers the greater than the two required on the cooling coil.
Humidity priority
Temp.
request
Humidity
request
Preheating coil Cooling coil Reheating
coil
Humidi
-
fier
Heating
Dehumidif.
Waits for humi-
dity set point to
be reached
Based on
humidity
control
probe
If “compen-
sation”
Cooling
Humidifica-
tion
Control on
temperature
probe set down-
stream of coils
if humidifier =
adiabatic
Waits for
humidity set
point to be
reached
Off due to
cooling
Based on
humidity
control
probe
Tab. 9.c
The “no priority” setting should be selected if evaporative cooling (DEC)
is enabled, in which case the simultaneous request for cooling and
humidification use the same actuator and therefore both influence each
other.
No priority
Temperature
request
Humidity
request
Preheating
coil
Cooling coil
Reheating coil
Heating
Dehumidifi-
cation
Off
Control on
humidity
control probe
or probe
downstream
of coils
Controls based
on request,
but only with
reheating
Return/
room
control
Cooling
Humidifica-
tion
Off
The cascade control ramp acts
on the humidity request, which
becomes the higher of the two
values (humidity request for
humidity control and humidity
request for temperature con-
trol) and any limits that com-
pensate for the value
Supply
control
Cooling
Humidifica-
tion
Off
Control on humidity control
probe while the cooling coil
controls the temperature (DEC
provides a free contribution)
Tab. 9.d
Note:
see the paragraph on “Direct evaporative cooling - DEC”.
9.6 Set point compensation
Set point compensation adjusts the set point defined by the user with an
offset that depends on a probe. This function in some cases ensures energy
saving by adapting the set point to the outside temperature, while still
guaranteeing suitable values for comfort. A temperature set point of 23 °C
for example can be adjusted to 21 °C when the climate is extreme. In other
cases, it’s used to:
1.
improve comfort, reducing the difference between the outside
temperature and the inside or room temperature;
2.
integrate another air-conditioning system: for example, if in summer
at 7 in the morning the outside temperature is lower than the room
temperature, the room probe can be used as the compensation probe
and the supply probe as the control probe to lower the set point and
exploit freecooling.
The following are possible:
1.
differentiate between compensation in summer and winter;
2.
select the probe used for compensation, between outside, supply, return
and room probe;
3.
increase or decrease the set point being compensated.
Note
: compensation is disabled if the control probe and the
compensation probe are the same.
Below is an example with the compensation probe set as the outside
temperature probe that compensates the room temperature set point.
Start_comp
B1
End_comp
SetT
SetT+delta
SetT_comp
delta > 0
SUMMER
SetT-delta
delta < 0
Start_comp
B1
End_comp
SetT
SetT+delta
SetT_comp
delta > 0
WINTER
SetT-delta
delta < 0
Fig. 9.d
KKey
SetT
Temperature set point
End_comp
End compensation
Delta
Compensation delta
B1
Compensation probe
Start_comp
Start compensation
SetT_comp
Compensation set point
Screen index Display description
Selection
Hc01
Main regulation probe selection
Temperature
Return ¦ supply ¦ room
Gfc08
Type of summer set point compensation
None ¦ external ¦ room ¦ supply ¦ return
Compensation delta
2 °C
Compensation start
25 °C
Compensation end
32 °C
Gfc09
Type of winter set point compensation
None ¦ external ¦ room ¦ supply ¦ return
Compensation delta
-2 °C
Compensation start
0 °C
Compensation end
-8 °C
Содержание FLSTDMAHUE
Страница 2: ......
Страница 4: ......
Страница 91: ...ENG FLSTDMAHUE 030220961 rel 1 1 28 08 2019 91 ...
Страница 92: ...ENG FLSTDMAHUE 030220961 rel 1 1 28 08 2019 92 ...
Страница 93: ......