![Carel FLSTDMAHUE Скачать руководство пользователя страница 62](http://html1.mh-extra.com/html/carel/flstdmahue/flstdmahue_user-manual_2557282062.webp)
ENG
“FLSTDMAHUE” +030220961 - rel. 1.1 - 28.08.2019
62
Screen
Display description
Description/notes
Def.
UOM
Min
Max
Value description
Type
R/W Carel Addr.
Gfb15
pCOe number:
1
---
0
999
I
W
Ch 1:
Ofs.:
0.0
---
-99.9
99.9
A
R/W
Prb.: 0.0
---
0.0
10.0
I
R/W
Ch 2:
Ofs.:
0.0
---
-99.9
99.9
A
R/W
Prb.: 0.0
---
0.0
10.0
I
R/W
Gfb16
pCOe number:
1
---
0
999
I
W
Ch 3:
Ofs.: 0.0
---
-10.0
10.0
A
R/W
Prb.: 0.0
---
0.0
10.0
I
R/W
Ch 4:
Ofs.: 0.0
---
99.9
999.9
A
R/W
Prb.: 0.0
---
0.0
10.0
I
R/W
Gfb17
pCOe number:
1
---
0
999
I
W
Ch 1:
Ofs.: 0.0
---
-10.0
10.0
A
R/W
Prb.: 0.0
---
0.0
10.0
I
R/W
Ch 2:
Ofs.: 0.0
---
99.9
999.9
A
R/W
Prb.: 0.0
---
0.0
10.0
I
R/W
Gfb18
pCOe number:
1
---
0
999
I
W
Ch 3:
Ofs.: 0.0
---
-10.0
10.0
A
R/W
Prb.: 0.0
---
0.0
10.0
I
R/W
Ch 4:
Ofs.: 0.0
---
99.9
999.9
A
R/W
Prb.: 0.0
---
0.0
10.0
I
R/W
Gfb19
Belimo 0
---
1
8
I
W
Ofs.: 0.0
---
-9.9
9.9
A
R/W
Prb.: 0.0
---
-99.9
99.9
A
R
Belimo 0
---
1
8
I
W
Ofs.: 0.0
---
-9.9
9.9
A
R/W
Prb.: 0.0
---
-99.9
99.9
A
R
Gfb20
Belimo 0
---
1
8
I
W
Ofs.: 0.0
---
-9.9
9.9
A
R/W
Prb.: 0.0
---
-99.9
99.9
A
R
Belimo 0
---
1
8
I
W
Ofs.: 0.0
---
-9.9
9.9
A
R/W
Prb.: 0.0
---
-99.9
99.9
A
R
Gfb21
Belimo 0
---
1
8
I
W
Ofs.: 0.0
---
-9.9
9.9
A
R/W
Prb.: 0.0
---
-99.9
99.9
A
R
Belimo 0
---
1
8
I
W
Ofs.: 0.0
---
-9.9
9.9
A
R/W
Prb.: 0.0
---
-99.9
99.9
A
R
Gfb22
Belimo 0
---
1
8
I
W
Ofs.: 0.0
---
-9.9
9.9
A
R/W
Prb.: 0.0
---
-99.9
99.9
A
R
Belimo 0
---
1
8
I
W
Ofs.: 0.0
---
-9.9
9.9
A
R/W
Prb.: 0.0
---
-99.9
99.9
A
R
Gfb23
Probe calibration
Humidity probe offset downstream of coils Enable: Hb23a
0
%RH
-99.9
99.9
A
R/W
Temperature probe offset after heat reco-
very unit
Enable: Hb23b
0
°C
-9.9
9.9
A
R/W
Gfb24
IEC humidity probe offset
0
%RH
-99.9
99.9
A
R/W
c.
Thermoregulation
Gfc01
Main mask information
1st row
Return
tempera-
ture
-
0
14
0:None 1:Supply temp.¦
2:Returm temp.¦
3:Room temp.¦
4:External temp¦
5:Temp setpoint¦
6: Supply humid.¦ 7: Return
humid.¦8:Room humid.¦
9:Ext. humid.¦
10: Humid. setpoint¦
11:Supply pressure.¦
12:Return pressure¦
13: CO2 quality¦
14: VOC quality
I
R/W
-
2nd row
Return
hum.
-
0
14
See 1st row
I
R/W
Gfc02
Temperature set limits
Summer low
15
°C
-99.9
99.9
A
R/W
106
Summer high
35
°C
Summer
low
99.9
A
R/W
107
Winter low
15
°C
-99.9
99.9
A
R/W
108
Winter high
35
°C
Winter
low
99.9
A
R/W
109
Gfc03
Humidity set limits
Summer low
30
% RH
0
100
I
R/W
71
Summer high
90
% RH
Summer
low
100
I
R/W
72
Winter low
30
% RH
0
100
I
R/W
73
Winter high
90
% RH
Winter
low
100
I
R/W
74
Gfc04
Temperature regulation
Regulation type
Prop+
integr
0:Proportional¦
1:Prop.+Integr.¦2:PID
I
R/W
75
Auto cool/heat
No
-
No
Yes
0:No¦1:Yes
D
R/W
168
Supply limits
None
-
1
4
1:None ¦2:High ¦3:Low ¦
4:High/Low
I
R/W
76