ENG
“FLSTDMAHUE” +030220961 - rel. 1.1 - 28.08.2019
60
Screen
Display description
Description/notes
Def.
UOM
Min
Max
Value description
Type
R/W Carel Addr.
Gc02
Set season
0
-
0
1
0:Auto¦1:Fix days
D
R/W
174
Summer start
15/05
dd/mm
01/01
31/12
I
R/W
134-5
Winter start
30/09
dd/mm
01/01
31/12
I
R/W
136-7
Threshold summer
25
°C
-99.9
99.9
A
R/W
156
Threshold winter
10
°C
-99.9
99.9
A
R/W
157
Delay change
1
Hour
0
999
I
R/W
138
Gc03
Season threshold
Enable: Gc01=temp.H2O, Hc14, Hb16
Summer
25
°C
-99.9
99.9
A
R/W
Winter
30
°C
-99.9
99.9
A
R/W
d. Working
hours
Working hours
Gd01
Supply fan
0
Hour
0
999
I
R
146-7 *
Return fan
0
Hour
0
999
I
R
150-1 *
Humidifier
0
Hour
0
999
I
R
154-5 *
Rotary recovery
0
Hour
0
999
I
R
156-7 *
Gd02
Cool pump 1
0
Hour
0
999
I
R
158-9 *
Cool pump 2
0
Hour
0
999
I
R
160-1 *
Preheat pump 1
0
Hour
0
999
I
R
162-3 *
Preheat pump 2
0
Hour
0
999
I
R
164-5 *
Reheat pump 1
0
Hour
0
999
I
R
166-7 *
Reheat pump 2
0
Hour
0
999
I
R
168-9 *
Gd03
Preheating heaters
Heater 1
0
Hour
0
999
I
R
170-1 *
Heater 2
0
Hour
0
999
I
R
172-3 *
Heater 3
0
Hour
0
999
I
R
174-5 *
Heater 4
0
Hour
0
999
I
R
176-7 *
Gd04
Reheating heaters
Heater 1
0
Hour
0
999
I
R
178-9 *
Heater 2
0
Hour
0
999
I
R
180-1 *
Heater 3
0
Hour
0
999
I
R
182-3 *
Heater 4
0
Hour
0
999
I
R
184-5 *
* = working hours x 1000
e. Config.
BMS
Ge01
BMS protocol
0
-
0
2
0:CAREL¦ 1:MODBUS¦
2:LON¦
I
R/W
-
Baud rate
0
bps
0
4
0:1200 ¦1:2400 ¦ 2:4800 ¦3:9600 ¦
4:19200 ¦ 5:38400
I
R/W
-
Address
1
-
0
207
I
R/W
-
Ge01a
BMS2 configuration
BMS2 protocol
Modbus
-
-
-
0:CAREL¦ 1:MODBUS¦ 2: LON
I
R/W
-
Baud rate
19200
bit/s
-
-
0:1200 ¦1:2400 ¦ 2:4800 ¦3:9600 ¦
4:19200 ¦ 5:38400
I
R/W
-
Address
1
-
1
207
I
R/W
Ge02
BMS offline alarm enable
0
-
0
1
0:No¦1:Yes
I
R/W
-
Timeout
0
s
0
900
-
I
R
-
Ge03
Press ENTER to ENABLE commissioning servi-
ce /Connect the BMS port
0
-
0
1
0:No¦1:Yes
D
R
-
f. Service
settings
a.
Working hour set
Gfa01
Supply fan
Threshold
0
h
0
99000
I
R/W
-
Reset (acts on counter Gd01)
0
-
0
1
0:N=No ¦ 1:Y=Yes
D
R/W
-
Return fan
Threshold
0
h
0
99000
I
R/W
-
Reset (acts on counter Gd01)
0
-
0
1
0:N=No ¦ 1:Y=Yes
D
R/W
-
Gfa02
Humidifier
Threshold
0
h
0
99000
I
R/W
-
Reset (acts on counter Gd01)
0
-
0
1
0:N=No ¦ 1:Y=Yes
D
R/W
-
Rotary recovery
Threshold
0
h
0
99000
I
R/W
-
Reset (acts on counter Gd01)
0
-
0
1
0:N=No ¦ 1:Y=Yes
D
R/W
-
Gfa03/4
Pump 1/2
-
Cooling
Threshold
0
h
0
99000
I
R/W
-
Reset (acts on counter Gd02)
0
-
0
1
0:N=No ¦ 1:Y=Yes
D
R/W
-
Preheating
Threshold
0
h
0
99000
I
R/W
-
Reset (acts on counter Gd02)
0
-
0
1
0:N=No ¦ 1:Y=Yes
D
R/W
-
Reheating
Threshold
0
h
0
99000
I
R/W
-
Gfa05
Preheating heaters
Threshold heater 1
0
h
0
99000
I
R/W
-
Reset (acts on counter Gd03)
0
-
0
1
0:N=No ¦ 1:Y=Yes
D
R/W
-
Threshold heater 2
0
h
0
99000
I
R/W
-
Reset (acts on counter Gd03)
0
-
0
1
0:N=No ¦ 1:Y=Yes
D
R/W
-
Threshold heater 3
0
h
0
99000
I
R/W
-
Reset (acts on counter Gd03)
0
-
0
1
0:N=No ¦ 1:Y=Yes
D
R/W
-
Reset (acts on counter Gd03)
0
h
0
99000
I
R/W
-
Reset (acts on counter Gd03)
0
-
0
1
0:N=No ¦ 1:Y=Yes
D
R/W
-
Gfa06
Reheating heaters
Threshold heater 1
0
h
0
99000
I
R/W
-
Reset (acts on counter Gd01)
0
-
0
1
0:N=No ¦ 1:Y=Yes
D
R/W
-
Threshold heater 2
0
h
0
99000
I
R/W
-
Reset (acts on counter Gd01)
0
-
0
1
0:N=No ¦ 1:Y=Yes
D
R/W
-
Threshold heater 3
0
h
0
99000
I
R/W
-
Reset (acts on counter Gd01)
0
-
0
1
0:N=No ¦ 1:Y=Yes
D
R/W
-
Threshold heater 4
0
h
0
99000
I
R/W
-
Reset (acts on counter Gd01)
0
-
0
1
0:N=No ¦ 1:Y=Yes
D
R/W
-
b.
Probe adjustment
Gfb01
Supply temperature
Offset
0
°C
-9.9
9.9
A
R/W
-
Probe
-
°C
-99.9
99.9
A
R
10
Return temperature
Offset
0
°C
-9.9
9.9
A
R/W
-
Probe
-
°C
-99.9
99.9
A
R
11
Return temperature
Offset
0
°C
-9.9
9.9
A
R/W
-
Probe
-
°C
-99.9
99.9
A
R
16