![Carel FLSTDMAHUE Скачать руководство пользователя страница 59](http://html1.mh-extra.com/html/carel/flstdmahue/flstdmahue_user-manual_2557282059.webp)
ENG
“FLSTDMAHUE” +030220961 - rel. 1.1 - 28.08.2019
59
Screen
Display description
Description/notes
Def.
UOM
Min
Max
Value description
Type
R/W Carel Add.
D40
Supply VFD
Status
0
-
0
1
0: not ready ¦ 1: ready
D
R
-
Run
0
-
0
1
0: stop ¦ 1: run
D
R
-
Direction
0
-
0
1
0: --> ¦1: <--
D
R
-
Alarms
0
-
0
1
0: No alarms ¦ 1: active
D
R
-
Speed status
0
-
0
1
0: ramping ¦ 1: refer. reached
D
R
-
D41
Request
0
-
0
100
A
W
53
Feedback
0
-
-99.9
99.9
A
W
-
Dissipator temperature
0
°C
-999
999
I
R
4
DC voltage
0
V
0
9999
I
R
5
D42
Motor data
Speed
0
-
-9999
9999
I
W
-
Voltage
0
V
-9999
9999
A
R
54
Current
0
A
-99.9
99.9
A
R
55
Torque
0
%
-9999
9999
A
R
56
Power
0
%
-999.9
999.9
A
R
57
D50
Return VFD
Status
0
-
0
1
0: not ready ¦ 1: ready
D
R
-
Run
0
-
0
1
0: stop ¦ 1: run
D
R
-
Direction
0
-
0
1
0: --> ¦1: <--
D
R
-
Alarms
0
-
0
1
0: No alarms ¦ 1: active
D
R
-
Speed status
0
-
0
1
0: ramping ¦ 1: reference
reached
D
R
-
D51
Request
0
-
0
100
A
W
59
Feedback
0
-
-99
99
A
W
-
Dissipator temperature
0
°C
-999
999
I
R
7
DC voltage
0
V
0
9999
I
R
8
D52
Motor data
Speed
0
-
-9999
9999
I
R
-
Voltage
0
V
-9999
9999
A
R
60
Current
0
A
-99.9
99.9
A
R
61
Torque
0
%
-999.9
999.9
A
R
62
Power
0
%
-999.9
999.9
A
R
63
D60
D62
D64
D66
D68
D70
D72
D74
Belimo 1…8
Enable: Ha24-Ha27-Ha28-Ha60…83; Config: -
Request
0
-
0
9
0: Closed¦1: Override open¦
2: Open
A
R/W
65;67;
69;71;
73;75;
77;79
Actual position
0
%
0
100
A
R
66;68;
70;72;
74;76;
78;80
Flow-rate
0
m3/h
0
100
A
R
-
External input
%
0
100
I
R
-
0
-
0
1
0: Open¦ 1: Closed
D
R
-
Network alarm
0
-
0
-
0: none¦ 1: offline¦
2: unknown command¦
3: unpermitted command¦
4: device error
I
R
-
D61, D63
D65, D67
D69, D71
D73, D75
Belimo Information 1…8
Version
Serial number
0
-
-
-
I
R
-
0
-
-
-
-
I
R
-
D81, D82
D83, D84
D85, D86
Serial probe n°1…6
Enable: Ha26; Config: Ha31-Ha91
0
-
0
99
I
W
-
Temperature
0
°C
-
-
A
W
-
Humidity
0
%RH
-
-
A
W
-
Dew point
0
°C
-
-
A
W
-
D87
Air flow-rate
Enable: Ha03
Supply
0
m3/h
---
---
I
R
229
Return
0
m3/h
---
---
I
R
230
D88
Heat recovery unit efficiency
DTA/DTT
0
%
0
100
I
R
227
DTA= Aft.Rec.T - Ext. T
---
°C
---
---
I
R
-
DTT= Ret.T - Ext. T
---
°C
---
---
I
R
-
E. Data logger
E01
Alarm No.-hour-date Code –
Description Supply temperature –
Return temperature
Pressing the bell button displays the alarm log. For
the complete list see chap. Alarms
0
-
0
99
I
R/W
-
F. Board switch: see chapter “Description of the Menus”
Screen
Display description
Description/notes
Def.
UOM
Min
Max
Value description
Type
R/W Carel Addr.
G. Service
a. Change
language
Ga01
ENTER to change/ ESC to confirm
0
-
0
9
0:Italian ¦1: English ¦2:Spanish
I
R/W
-
Ga02
Disable language mask at startup
No
-
No
Yes
0:No¦ 1:Yes
D
R/W
-
Display countdown
60
s
0
999
I
R
-
b. Information
Gb01
Software code – Version - date
Manual: Bios: …; Date …;
Boot: …; Date …;
0
-
0
99
I
R
-
Gb02
pCO type
0
-
1
10
0: pCO2¦ 1: pCO1
¦ 2: pCO2¦ 3: pCOC¦ 4: pCOXS¦
¦ 5: pCOOEM¦ ¦ 6: -¦ 7: PCO3¦
¦ 8: Snode¦9: -¦ ¦ 10: pCO5¦
I
R
-
Type of pCO controller
0
-
0
99
10: Large¦ 11: Medium ¦ 12: Small
¦ 13: XL N.O. ¦ 17: XL N.C.
I
R
-
Total flash
0
-
0
9999
I
R/W
-
Ram
0
-
0
9999
I
R/W
-
Built-in type
0
-
0
9
0: No¦ 2: pGD0¦ 3: pGD1
I
R
-
Main cycle
0
-
0
9999
A
W
-
Cycle/s
0
-
0
9999
I
R
-
c. Summer/winter
Gc01
Season selection from
0
-
0
5
0:Keypad ¦1: Digital input ¦
2:B.M.S. ¦ 3:Keypad/B.M.S. ¦4:Auto
¦5: H2O temperature
I
R/W
133