background image

8200-M554-O1 Rev C   2XX-EIP Installation and Setup Manual 

RE-INSTALLING THE REAR PANEL 

When the installation is complete: 

1. 

Remove the excess cable from the indicator enclosure.

 

2. 

Make certain no cables or wires are exposed between the main housing and rear panel and 
then place the rear panel onto the main housing.

3. 

Secure the panel to the main housing with the acorn nuts (12 on the 205/210, 14 on the 
225) removed earlier. 

4. 

Tighten the gland connector nut to seal the cable. 

  Do not over-tighten the connector but make certain they are snug. 
 

DO NOT USE TOOLS!

 Finger-tighten only!  

  Make sure any unused gland connectors are plugged.  

5. 

If required, install the lead and wire calibration seal. 

 
 

205/210 INDICATOR SETUP 

With the 2XX-EIP option card installed, a sub-menu 

(Option) has been placed after 

(Key Lock Out Function). The 

sub-menu contains the setup selection to 

change the output weight byte order. 
 

NOTE:

 The prompt will display as 

 when using the CAL switch and 

 when 

using the 

ENTER

 key to advance through the setup prompts.

 

 (Output Weight Byte Order) 

Press the 

ENTER

 key to show the current setting. If the setting displayed is acceptable, 

press the 

ENTER

 key again to save it. Otherwise, using the numeric keys (or the arrow keys 

on the 205) enter the new setting, then press the 

ENTER

 key to save it. Allowable values 

are:  

Default setting. 

 
 

225 INDICATOR SETUP 

With the indicator ON, press the 

SHIFT

 key and then press the Navigation 

ENTER

 key (red 

square key in the center of the Navigation arrows). The display will change to show the 
SETUP/REVIEW MENU. 
 

SETUP/REVIEW MENU

1.ENTER CALIBRATION AND SETUP 
2.VIEW AUDIT TRAIL COUNTERS 
3.CALIBRATE SCALE 1  

 

8.SCALE ID=00 

                              9.DEL CUSTOM TICKET 
                           

 

10.PRINT SETUP 

Enter Selection: 1 

 

EXIT 

Press the 

ENTER

 key, and then press the 

NEXT

 Navigation arrow until SETUP MENU #3 is 

displayed.
 

Содержание 2-EIP Series

Страница 1: ...8200 M554 O1 Rev C 2XX EIP Installation and Setup Manual 1 2XX EIP EtherNet IP Interface Card Installation and Setup Manual For 205 210 and 225 Weight Indicators...

Страница 2: ...8200 M554 O1 Rev C 2XX EIP Installation and Setup Manual 2...

Страница 3: ...le protection against such interference when operated in a commercial environment Operation of this equipment in a residential area may cause interference in which case the user will be responsible to...

Страница 4: ...or 6 Referring to the illustrations on page 3 locate the threaded stand off and the OPTION BOARD connector on the indicator mainboard 205 210 The threaded stand off is below P3 and the OPTION BOARD co...

Страница 5: ...Cont 205 210 Main PCB NOTE 205 Main PCB shown The 210 Main PCB will have connector P2 REMOTE OUTPUTS and J7 REMOTE OUTPUT SRC jumper installed 225 Main PCB P15 OPTION BOARD THREADED STAND OFF ATTACH G...

Страница 6: ...herNet IP Interface Card contains three LEDs to indicate the communication status with the indicator mainboard CS Chip Select LK Link ML Main Line If the CS Chip Select LED is off communications may h...

Страница 7: ...Out Function The sub menu contains the setup selection to change the output weight byte order NOTE The prompt will display as when using the CAL switch and when using the ENTER key to advance through...

Страница 8: ...press the 5 key the ENTER key and then using the numeric keys enter the setting for the byte order Press the ENTER key to save the new setting and return to the 2XX EIP MODBUSTCP SETUP MENU Allowable...

Страница 9: ...ew project or use an existing one set the program in Offline mode Add the module to the configuration in the PLC Start by right click the EtherNet IP module bridge in the I O configuration and select...

Страница 10: ...First enter a name for the module This name will create a tag in RSLogix5000 which can be used to access the memory location in the PLCs memory where the data for the module will be stored With the na...

Страница 11: ...you want to download the configuration 5 Select Download The configuration will now be downloaded to the PLC Now it s possible to access the data exchanged by ControlLogix5000 and the module To do th...

Страница 12: ...NT Input The weight data begins at Data 0 and uses the next four bytes to produce a floating point program tag Float Data 0 Data 1 Data 2 Data 3 Weight Weight Status PWC Status CMD 0 return when compl...

Страница 13: ...value for Cmd Byte 0 Float point value for Cmd Byte 1 Byte5 Byte6 Float point value for Cmd Byte 2 Float point value for Cmd Byte 3 Byte7 205 210 WEIGHT STATUS Data 4 Bit0 MOTION Bit1 BELOW ZERO Bit2...

Страница 14: ...oat point value be sent in Bytes 4 5 6 and 7 Bit05 not defined Bit06 not defined Bit07 This bit is the error bit from the 2XX when a command fails Bit08 PWC1 requires float point value be sent in Byte...

Страница 15: ...225 COMMANDS CMD0 and CMD1 are combined to make the command word Command words are broken into command bits for PLC ease of programming To invoke a command set the bit to one The PLC should continue t...

Страница 16: ...elect scale number bit 1 Bit6 Select scale number bit 2 Bit7 Select scale number bit 3 most significant 225 WEIGHT STATUS Bit0 Motion Bit1 Below Zero Bit2 Center of Zero Bit3 Over Capacity Bit4 Weigh...

Страница 17: ...ED INDICATION STATE DESCRIPTION 1 Network Status Off No power or no IP address Green On line one or more connections established CIP Class 1 or 3 Green Flashing On line no connections established Red...

Страница 18: ...8200 M554 O1 Rev C 2XX EIP Installation and Setup Manual 16...

Страница 19: ...8200 M554 O1 Rev C 2XX EIP Installation and Setup Manual 17...

Страница 20: ...etup Manual 18 Cardinal Scale Mfg Co 102 E Daugherty Webb City MO 64870 USA Ph 417 673 4631 or 1 800 641 2008 Fax 417 673 2153 www cardinalscale com Technical Support 1 866 254 8261 E mail tech cardet...

Отзывы: