8200-M554-O1 Rev C 2XX-EIP Installation and Setup Manual
13
225 COMMUNICATIONS
Data Sent from the 225 Indicator to the PLC
Byte0 Float point weight. Byte 0
Float point weight. Byte 1
Byte1
Byte2 Float point weight. Byte 2
Float point weight. Byte 3
Byte3
Byte4 Weight status. See bit definitions below Scale Number (Bits 4-7)
Byte5
Byte6 Cmd0. Returned by 225 Indicator when
complete
Cmd1. Returned by 225 Indicator
when complete
Byte7
Data Sent from the PLC to the 225 Indicator:
Byte0 Cmd0. See definition below
Cmd1. See definition below
Byte1
Byte2 N/A
N/A
Byte3
Byte4 Float point value for Cmd. Byte 0
Float point value for Cmd. Byte 1
Byte5
Byte6 Float point value for Cmd. Byte 2
Float point value for Cmd. Byte 3
Byte7
225 COMMANDS
CMD0 and CMD1 are combined to make the command word. Command words are broken into
command bits for PLC ease of programming. To invoke a command, set the bit to one. The
PLC should continue to send a command until the command is returned by the indicator. If the
indicator cannot perform a command, the returned command will include bit 7. The scale
number is encoded as a four-bit binary number, 1 through the number of scales available.
NOTE: ALL COMMAND BITS SHOULD BE RELEASED AFTER THEY ARE
PROCESSED BY THE INDICATOR.
Bit0 Gross/Net
Bit1 Print
Bit2 Zero
Bit3 PB Tare
Bit4 KB Tare, requires float point value be sent in bytes 4, 5, 6, and 7
Bit5-6 not defined
Bit7 This bit is the error bit from the 225 when a command fails.
Bit8-11 not defined
Bit12 Select scale number, bit 0 (least significant)
Bit13 Select scale number, bit 1
Bit14 Select scale number, bit 2
Bit15 Select scale number, bit 3 (most significant)