background image

8

installation manual 

7.    INSTALL THE CONNECTING PIPE

Check whether the height drop between the indoor unit and 
outdoor unit, the length of refrigerant pipe, and the number of 
the bends meet the following requirements:

(The number of the bends less than 15)

Table 7-1

The length ofefrigerant pipe 

The max height drop 

Model 

18/24 

36/60

72

20 

10 

25 

10 

30 

15 

unit: m 

Drill a hole in the wall (suitable just for the size of the wall 
conduit), then set on the fittings such as the wall conduit and 
its cover. 
 
Bind the connecting pipe and the cables together tightly with 
binding tapes. 
Pass the bound connecting pipe through the wall conduct 
from outside. Be careful of the pipe allocation to do on 
damage to the tubing. 
  
Connect the pipes. Refer to "How to Connect the pipes" for 
details. 
 
Expel the air with a vacuum pump. Refer to "How to expel the 
air with a vacuum pump" for details. 
 
Open the stop values of the outdoor unit to make the 
refrigerant pipe connecting the indoor unit with the outdoor 
unit in fluent flow. 
 
Check the leakage. Check all the joints with the leak detector 
or soap water. 
 
Cover the joints of the connecting pipe with the soundproof / 
insulating sheath (fittings), and bind it well with the tapes to 
prevent leakage. 

Be sure to with insulating materials cover all the exposed 
parts of the flare pipe joints and refrigerant pipe on the 
liquid-side and the gas-side. Ensure that there is no gap 
between them. 
Incomplete insulation may cause water condensation. 

CAUTION 

   The Procedure of Connecting Pipes 

7.1 

CAUTION 

All field piping must be provided by a licensed 
refrigeration technician and must comply with the 
relevant local and national codes. 

Do not let air, dust, or other impurities fall in the pipe 
system during the time of installation. 

The connecting pipe should not be installed until the 
indoor and outdoor units have been fixed already. 

Keep the connecting pipe dry, and do not let moisture in 
during installation. 

Execute heat insulation work completely on both sides 
of the gas piping and the liquid piping. Otherwise, this 
can sometimes result in water leakage. 

How to Connect the pipes 

Flaring 

Cut a pipe with a pipe cutter. 

(Refer to Fig.7-1) 

Insert a flare nut into a pipe and flare the pipe. 
 
Refer to Table 7-2 for the dimension of flare nut spaces. 

 Fig.7-1

90 

Lean     crude     burr 

Table 7-2

Ø6.4 

8.3 8.7 

Ø9.5 

12.0 

Ø12.7 

15.4 

Ø15.9 

Ø19.1 

18.6 

22.9 

R0.4~0.8 

45 ° ± 

90 °      

± 4 

65

67N.m 

(663

684 kgf.cm) 

45

47 N.m 

(459

480 kgf.cm) 

35

36 N.m 

(357

367 kgf.cm) 

25

26N.m 

(255

265 kgf.cm) 

15

16 N.m 

(153

163 kgf.cm) 

(mm) 

min max 

Pipe  gauge 

Tightening     torque 

Flare dimensin A 

Flare     shape 

12.4 

15.8 

19.0 

23.3 

Bend the tubing in proper way. Do not harm to them. 

Connect the indoor unit at first, then the outdoor 
unit. 

Bend the pipe with thumb

min-radius 100mm

Fig.7-2

The bending angle should not exceed 90. 

Bending position is preferably in the middle of the 
bendable pipe. The larger the bending radius the better it 
is. 

Do not bend the pipe more than three times. 

When connecting the flare nut, coat the flare both inside 
and outside with either oil or ester oil and initially tighten 
by hand 3 or 4 turns before tighting firmly. 

Fig.7-3

Содержание Ceiling series

Страница 1: ...Ceiling And Floor Type INSTALLATION MANUAL Thank you very much for purchasing our air conditioner Before using your air conditioner please read this manual carefully and keep it for future reference...

Страница 2: ...hall not be installed in the laundry Before obtaining access to terminals all supply circuits must be disconnected The appliance must be positioned so that the plug is accessible The enclosure of the...

Страница 3: ...perty damage Install the indoor and outdoor units power supply wiring and connecting wires at least 1 meter away from televisions or radios in order to prevent image interference or noise Depending on...

Страница 4: ...ve poles are right positions when loading batteries This manual is subject to changes due to technological improvement without further notices Cautions on remote controller installation Remote control...

Страница 5: ...e the service agent When handling the unit take into account the following 5 INDOOR UNIT INSTALLATION 5 1 Installation place Refer to Fig 5 1 Fig 5 2 Fig 5 3 and Table 5 1 for specification The indoor...

Страница 6: ...size of the ceiling to be handled Do keep the ceiling flat Consolidate the roof beam for possible vibration 1 Installing 10 hanging screw bolts 4 bolts 2 Install the indoor unit After the selection of...

Страница 7: ...e piping length between the outdoor unit and the indoor unit may not exceed the allowable piping length In the case that the installation place is exposed to strong wind such as a seaside make sure th...

Страница 8: ...all prevail Since the gravity center of the unit is not at its physical center so please be careful when lifting it with a sling Never hold the inlet of the outdoor unit to prevent it from deforming D...

Страница 9: ...ensation CAUTION The Procedure of Connecting Pipes 7 1 CAUTION All field piping must be provided by a licensed refrigeration technician and must comply with the relevant local and national codes Do no...

Страница 10: ...22 13 5 16 5 5 7 7 9 9 11 11 13 11 5 13 9 1 2 4 3 5 6 Fig 7 7 Using the vacuum pump Loosen and remove the maintenance nuts of stop valves A and B and connect the charge hose of the manifold valve to t...

Страница 11: ...make sure there is no leakage 8 CONNECT THE DRAIN PIPE Install the drainpipe of the indoor unit The outlet has PTI screw bread Please use sealing materials and pipe sheath fitting when connecting PVC...

Страница 12: ...hecked carefully after wiring The power cord type designation is H07RN F 9 CONNECTIVE DIAGRAM Orifice Fig 9 1 Fig 9 2 For ensuring throttled efficiency Please mount the Orifice as horizontally as poss...

Страница 13: ...ioner is pre heated by turning on the power The indoor unit and outdoor unit are installed properly Tubing and wiring are correctly completed The refrigerant pipe system is leakage checked The drainag...

Страница 14: ...ELECTRIC SIGNAL INDOOR OUTDOOR CONNECTING WIRING mm CIRCUIT BREAKER FUSE A 2 INDOOR UNIT POWER WIRING mm PHASE FREQUENCY AND VOLT WEAK ELECTRIC SIGNAL 3x2 5 20 16 40 25 2 5 2 5 Table 10 1 GROUND WIRIN...

Страница 15: ...n air gap contact separation in all active conductors should be incorporated in the fixed wiring according to the National Wiring Regulation When wiring please choose the corresponding chart or it may...

Страница 16: ...N 3 4 5 core cable 5 2 5mm2 3 core cable 3 2 5mm2 1 core sheild wire 1 0 5mm2 POWER 220 240 50Hz INDOOR UNIT Y G Y G L N 1 2 N T3 E 3 4 WHITE T3 BLACK E Fig 10 5 3 core cable 3 2 5mm2 3 core cable 3...

Страница 17: ...3 XT2 T3 T3 E E Y G Y G POWER 220 240 50Hz 3 core cable 3 2 5mm2 3 core cable 3 2 5mm2 3 core cable 3 2 5mm2 1 core sheild wire 1 0 5mm2 Fig 10 7 Model 24 36 1 PHASE Air Conditioner Link circuit For R...

Страница 18: ...able 3 2 5mm 2 5 core cable 5 2 5mm 2 5 core cable 5 2 5mm 2 POWER 380 415V 3N 50Hz Model 36 60 3 PHASE Air Conditioner Link circuit For R22 Cooling Heating Model 36 1 PHASE OUTDOOR UNIT L 1 N 1 L N 1...

Страница 19: ...XT4 A B C N 3 core cable 3 2 5mm 2 5 core cable 5 2 5mm 2 5 core cable 5 2 5mm 2 POWER 380 415V 3N 50Hz Model 72 3 PHASE Fig 10 10 Air Conditioner Link circuit For R22 Cooling only POWER 5 core cable...

Страница 20: ...r Conditioner Link circuit For R22 Cooling only POWER 5 core cable 5 2 5mm 2 5 core cable 5 2 5mm 380 415V 3N 50Hz 2 INDOOR UNIT OUTDOOR UNIT XT1 A B C N 1 2 3 XT1 XT2 4 1 core cable 1 2 5mm 2 A B C N...

Страница 21: ...onditioner Link circuit For R22 Cooling Heating Model 24 1 PHASE L N 1 2 3 INDOOR UNIT POWER 220 240 50Hz 3 core cable 3 2 5mm2 1 core cable 1 2 5mm2 Y G Y G OUTDOOR UNIT XT3 L N S Fig 10 14 Fig 10 15...

Страница 22: ...T3 T3 E E Y G Y G Y G POWER 220 240 50Hz 3 core cable 3 2 5mm2 3 core cable 3 2 5mm2 1 core sheild wire 1 0 5mm2 Fig 10 16 Model 36 1 PHASE Air Conditioner Link circuit For R22 Cooling only N L 1 2 3...

Страница 23: ...4 A B C N 3 core cable 3 2 5mm 2 5 core cable 5 2 5mm 2 5 core cable 5 2 5mm 2 POWER 380 415V 3N 50Hz Model 36 60 3 PHASE 4 Fig 10 19 Air Conditioner Link circuit For R22 Cooling only POWER 5 core cab...

Страница 24: ...The design and specifications are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer for details 2011 02 23 202000100290...

Отзывы: