installation manual 

Too large torque will harm the bellmouthing and too small 
will cause leakage. Please determine the torque 
according to Table 7-2. 
 
After the connecting work is finished, be sure to check 
that there is no gas leak. 

Be sure to use both a spanner and torque wrench 
together when connecting or disconnecting pipes to /from 
the unit. 

Fig.7-4

How to expel the air with a vacuum pump 

Stop valve operation introduction 

1.          Opening stop valve 

2.          Closing stop valve 

1. 

2. 

1. 

2. 

3. 

Remove the cap and turn the valve 
counterclock-wise with the hexagon wrench. 

Turn it until the shaft stops.Do not apply excessive force 
to the stop valve. Doing so may breakthe valve body, as 
the valve is not a backseat type. Always use the special 
tool. 

Make sure to tighten the cap securely. 

Remove the cap and turn the valve clockwise with the 
hexagon wrench. 

Securely tighten the valve until the shaft contacts the 
main bodyseal. 

CAUTION 

Make sure to tighten the cap securely. 
For the tightening torque, refer to the table below. 

Table 7-3

Tightening torque N  M (Turn clockwise to close) 

Stop  

Valve size 

Shaft (valve body) 

Cap  

(Valve lid) 

Ø6.4 

Hexagonal  

wrench 4 mm 

Ø9.5 

Ø12.7 

Ø15.9 

Hexagonal  

wrench 6 mm 

Hexagonal  

wrench 6 mm 

Ø19.1 

Maintenance nut

35

40 

23

27 

18

22 

13.5

16.5 

5

7

9

11 

11

13 

11.5

13.9 

Fig.7-7

Using the vacuum pump 

Loosen and remove the maintenance nuts of stop valves A 
and B, and connect the charge hose of the manifold valve to 
the service port of stop valve A. (Be sure that stop valves A 
and B are both closed) 
 
Connect the joint of the charge hose with the vacuum pump. 
 
Open the Lo-lever of the manifold value completely. 
 
Turn on the vacuum pump. At the beginning of pumping, 
loosen the maintenance nut of stop valve B a little to check 
whether the air comes in (the sound of the pump changes, 
and the indicator of compound meter turns below zero). Then 
fasten the maintenace nut. 
 
When the pumping has finished, close the Lo-lever of the 
manifold valve completely and turn off the vacuum 
pump.Make pumping for 15 minutes or more and check that 
the compound meter indicates -76cmHg(-1X10 Pa) 
 
Loosen and remove the cap of stop valves A and B to open 
stop valve A and B completely, then fasten the cap. 
 
Disassemble the charge hose from the service port of stop 
valve A, and fasten the nut. 

Fig.7-6

Fig.7-5

Always use a charge hose for service port connection
After tightening the cap, check that no refrigerant leaks 
arepresent.

service port

cap

maintenance nut

Stop valve

Gas side

Liquid side

hexagon hole

shaft

seal

Outdoor

unit

Indoor

unit

CAUTION 

Pressure meter

Multi-meter

-76 cmHg

Lo-lever

Lo-lever

Charge hose

Charge hose

Vacuum pump

Hi-lever

Manifold valve

Содержание Ceiling series

Страница 1: ...Ceiling And Floor Type INSTALLATION MANUAL Thank you very much for purchasing our air conditioner Before using your air conditioner please read this manual carefully and keep it for future reference...

Страница 2: ...hall not be installed in the laundry Before obtaining access to terminals all supply circuits must be disconnected The appliance must be positioned so that the plug is accessible The enclosure of the...

Страница 3: ...perty damage Install the indoor and outdoor units power supply wiring and connecting wires at least 1 meter away from televisions or radios in order to prevent image interference or noise Depending on...

Страница 4: ...ve poles are right positions when loading batteries This manual is subject to changes due to technological improvement without further notices Cautions on remote controller installation Remote control...

Страница 5: ...e the service agent When handling the unit take into account the following 5 INDOOR UNIT INSTALLATION 5 1 Installation place Refer to Fig 5 1 Fig 5 2 Fig 5 3 and Table 5 1 for specification The indoor...

Страница 6: ...size of the ceiling to be handled Do keep the ceiling flat Consolidate the roof beam for possible vibration 1 Installing 10 hanging screw bolts 4 bolts 2 Install the indoor unit After the selection of...

Страница 7: ...e piping length between the outdoor unit and the indoor unit may not exceed the allowable piping length In the case that the installation place is exposed to strong wind such as a seaside make sure th...

Страница 8: ...all prevail Since the gravity center of the unit is not at its physical center so please be careful when lifting it with a sling Never hold the inlet of the outdoor unit to prevent it from deforming D...

Страница 9: ...ensation CAUTION The Procedure of Connecting Pipes 7 1 CAUTION All field piping must be provided by a licensed refrigeration technician and must comply with the relevant local and national codes Do no...

Страница 10: ...22 13 5 16 5 5 7 7 9 9 11 11 13 11 5 13 9 1 2 4 3 5 6 Fig 7 7 Using the vacuum pump Loosen and remove the maintenance nuts of stop valves A and B and connect the charge hose of the manifold valve to t...

Страница 11: ...make sure there is no leakage 8 CONNECT THE DRAIN PIPE Install the drainpipe of the indoor unit The outlet has PTI screw bread Please use sealing materials and pipe sheath fitting when connecting PVC...

Страница 12: ...hecked carefully after wiring The power cord type designation is H07RN F 9 CONNECTIVE DIAGRAM Orifice Fig 9 1 Fig 9 2 For ensuring throttled efficiency Please mount the Orifice as horizontally as poss...

Страница 13: ...ioner is pre heated by turning on the power The indoor unit and outdoor unit are installed properly Tubing and wiring are correctly completed The refrigerant pipe system is leakage checked The drainag...

Страница 14: ...ELECTRIC SIGNAL INDOOR OUTDOOR CONNECTING WIRING mm CIRCUIT BREAKER FUSE A 2 INDOOR UNIT POWER WIRING mm PHASE FREQUENCY AND VOLT WEAK ELECTRIC SIGNAL 3x2 5 20 16 40 25 2 5 2 5 Table 10 1 GROUND WIRIN...

Страница 15: ...n air gap contact separation in all active conductors should be incorporated in the fixed wiring according to the National Wiring Regulation When wiring please choose the corresponding chart or it may...

Страница 16: ...N 3 4 5 core cable 5 2 5mm2 3 core cable 3 2 5mm2 1 core sheild wire 1 0 5mm2 POWER 220 240 50Hz INDOOR UNIT Y G Y G L N 1 2 N T3 E 3 4 WHITE T3 BLACK E Fig 10 5 3 core cable 3 2 5mm2 3 core cable 3...

Страница 17: ...3 XT2 T3 T3 E E Y G Y G POWER 220 240 50Hz 3 core cable 3 2 5mm2 3 core cable 3 2 5mm2 3 core cable 3 2 5mm2 1 core sheild wire 1 0 5mm2 Fig 10 7 Model 24 36 1 PHASE Air Conditioner Link circuit For R...

Страница 18: ...able 3 2 5mm 2 5 core cable 5 2 5mm 2 5 core cable 5 2 5mm 2 POWER 380 415V 3N 50Hz Model 36 60 3 PHASE Air Conditioner Link circuit For R22 Cooling Heating Model 36 1 PHASE OUTDOOR UNIT L 1 N 1 L N 1...

Страница 19: ...XT4 A B C N 3 core cable 3 2 5mm 2 5 core cable 5 2 5mm 2 5 core cable 5 2 5mm 2 POWER 380 415V 3N 50Hz Model 72 3 PHASE Fig 10 10 Air Conditioner Link circuit For R22 Cooling only POWER 5 core cable...

Страница 20: ...r Conditioner Link circuit For R22 Cooling only POWER 5 core cable 5 2 5mm 2 5 core cable 5 2 5mm 380 415V 3N 50Hz 2 INDOOR UNIT OUTDOOR UNIT XT1 A B C N 1 2 3 XT1 XT2 4 1 core cable 1 2 5mm 2 A B C N...

Страница 21: ...onditioner Link circuit For R22 Cooling Heating Model 24 1 PHASE L N 1 2 3 INDOOR UNIT POWER 220 240 50Hz 3 core cable 3 2 5mm2 1 core cable 1 2 5mm2 Y G Y G OUTDOOR UNIT XT3 L N S Fig 10 14 Fig 10 15...

Страница 22: ...T3 T3 E E Y G Y G Y G POWER 220 240 50Hz 3 core cable 3 2 5mm2 3 core cable 3 2 5mm2 1 core sheild wire 1 0 5mm2 Fig 10 16 Model 36 1 PHASE Air Conditioner Link circuit For R22 Cooling only N L 1 2 3...

Страница 23: ...4 A B C N 3 core cable 3 2 5mm 2 5 core cable 5 2 5mm 2 5 core cable 5 2 5mm 2 POWER 380 415V 3N 50Hz Model 36 60 3 PHASE 4 Fig 10 19 Air Conditioner Link circuit For R22 Cooling only POWER 5 core cab...

Страница 24: ...The design and specifications are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer for details 2011 02 23 202000100290...

Отзывы: