1

installation manual 

Be sure to be in conformity with the local, national and 
international laws and regulations. 
 
Read "PRECAUTIONS" carefully before installation. 
 
The following precautions include important safty items. 
Observe them and never forget. 
 
Keep this manual with the owner's manual in a handy place 
for future reference. 

1.    PRECAUTIONS

The safty precautions listed here are divided into two categories. In 
either case, important safty information is listed which must be read 
carefully. 

After completing the installation, make sure that the unit operates 
properly during the start-up operation. Please instruct the customer 
on how to operate the unit and keep it maintained.Also, inform 
customers that they should store this installation manual along with 
the owner's manual for future reference.  

Be sure only trained and qualified service personnel to 
install, repair or service the equipment. 
 

Improper installation, repair, and maintenance may result in 
electric shocks, short-circuit, leaks, fire or other damage to 
the equipment. 

Failure to observe a warning may result in death.

Failure to observe a caution may result in injury or 
damage to the equipment.

Install according to this installation instructions strictly. 

 

If installation is defective, it will cause water leakage, 
electrical shock and fire. 
 

When installing the unit in a small room, take measures 
against to keep refrigerant concentration from exceeding 
allowable safety limits in the event of refrigerant leakage.

 

Contact the place of purchase for more information. 
Excessive refrigerant in a closed ambient can lead to oxygen 
deficiency.

 

 

Use the attached accessories parts and specified parts 
for installation. 

 

otherwise, it will cause the set to fall, water  leakage, 
electrical shock and fire. 
 

Install at a strong and firm location which is able to 
withstand the set' s weight. 

 

If the strength is not enough or installation is not properly 
done, the set will drop to cause injury. 
 

The appliance shall not be installed in the laundry. 
 
Before obtaining access to terminals, all supply circuits 
must be disconnected. 
 
The appliance must be positioned so that the plug is 
accessible. 
 
The enclosure of the appliance shall be marked by word, 
or by symbols, with the direction of the fluid flow. 

 

For electrical work, follow the local national wiring 
standard, regulation and this installation instructions. An 
independent circuit and single outlet must be used. 

 

If electrical circuit capacity is not enough or defect in 
electrical work, it will cause electrical shock fire. 
 

Use the specified cable and connect tightly and clamp 
the cable so that no external force will be acted on the 
terminal.

  

If connection or fixing is not perfect, it will cause heat-up or 
fire at the connection. 

 
Wiring routing must be properly arranged so that control 
board cover is fixed properly. 

 

If control board cover is not fixed perfectly, it will cause 
heat-up at connection point of terminal, fire or electrical 
shock. 
 

If the supply cord is damaged, it must be replaced by the 
manufacturer or its service agent or a similarly qualified 
person in order to avoid a hazard. 
 
An all-pole disconnection swith having a contact 
separation of at least 3mm in all poles should be 
connected in fixed wiring. 
 
When carrying out piping connection, take care not to let 
air substances go into refrigeration cycle.  

Otherwise, it will cause lower capacity, abnormal high 
pressure in the refrigeration cycle, explosion and injury. 
 

Do not modify the length of the power supply cord or use 
of extension cord, and do not share the single outlet with 
other electrical appliances. 

 

Otherwise, it will cause fire or electrical shock. 

 
Carry out the specified installation work after taking into 
account strong winds, typhoons or earthquakes. 

Improper installation work may result in the equipment falling 
and causing accidents. 

CAUTION 

WARNING 

WARNING 

CONTENTS PAGE 

PRECAUTIONS.......................................................................................1
INSTALLATION INFORMATION................................................................2
ATTACHED FITTINGS.............................................................................3
INSPECTING AND HANDLING THE UNIT.................................................4
INDOOR UNIT INSTALLATION.................................................................4
OUTDOOR UNIT INSTALLATION..............................................................6
INSTALL THE CONNECTING PIPE..........................................................8
CONNECT THE DRAIN PIPE...................................................................10
CONNECTIVE DIAGRAM...................................................................11
WIRING.................................................................................................11
TEST OPERATION................................................................................12

Содержание Ceiling series

Страница 1: ...Ceiling And Floor Type INSTALLATION MANUAL Thank you very much for purchasing our air conditioner Before using your air conditioner please read this manual carefully and keep it for future reference...

Страница 2: ...hall not be installed in the laundry Before obtaining access to terminals all supply circuits must be disconnected The appliance must be positioned so that the plug is accessible The enclosure of the...

Страница 3: ...perty damage Install the indoor and outdoor units power supply wiring and connecting wires at least 1 meter away from televisions or radios in order to prevent image interference or noise Depending on...

Страница 4: ...ve poles are right positions when loading batteries This manual is subject to changes due to technological improvement without further notices Cautions on remote controller installation Remote control...

Страница 5: ...e the service agent When handling the unit take into account the following 5 INDOOR UNIT INSTALLATION 5 1 Installation place Refer to Fig 5 1 Fig 5 2 Fig 5 3 and Table 5 1 for specification The indoor...

Страница 6: ...size of the ceiling to be handled Do keep the ceiling flat Consolidate the roof beam for possible vibration 1 Installing 10 hanging screw bolts 4 bolts 2 Install the indoor unit After the selection of...

Страница 7: ...e piping length between the outdoor unit and the indoor unit may not exceed the allowable piping length In the case that the installation place is exposed to strong wind such as a seaside make sure th...

Страница 8: ...all prevail Since the gravity center of the unit is not at its physical center so please be careful when lifting it with a sling Never hold the inlet of the outdoor unit to prevent it from deforming D...

Страница 9: ...ensation CAUTION The Procedure of Connecting Pipes 7 1 CAUTION All field piping must be provided by a licensed refrigeration technician and must comply with the relevant local and national codes Do no...

Страница 10: ...22 13 5 16 5 5 7 7 9 9 11 11 13 11 5 13 9 1 2 4 3 5 6 Fig 7 7 Using the vacuum pump Loosen and remove the maintenance nuts of stop valves A and B and connect the charge hose of the manifold valve to t...

Страница 11: ...make sure there is no leakage 8 CONNECT THE DRAIN PIPE Install the drainpipe of the indoor unit The outlet has PTI screw bread Please use sealing materials and pipe sheath fitting when connecting PVC...

Страница 12: ...hecked carefully after wiring The power cord type designation is H07RN F 9 CONNECTIVE DIAGRAM Orifice Fig 9 1 Fig 9 2 For ensuring throttled efficiency Please mount the Orifice as horizontally as poss...

Страница 13: ...ioner is pre heated by turning on the power The indoor unit and outdoor unit are installed properly Tubing and wiring are correctly completed The refrigerant pipe system is leakage checked The drainag...

Страница 14: ...ELECTRIC SIGNAL INDOOR OUTDOOR CONNECTING WIRING mm CIRCUIT BREAKER FUSE A 2 INDOOR UNIT POWER WIRING mm PHASE FREQUENCY AND VOLT WEAK ELECTRIC SIGNAL 3x2 5 20 16 40 25 2 5 2 5 Table 10 1 GROUND WIRIN...

Страница 15: ...n air gap contact separation in all active conductors should be incorporated in the fixed wiring according to the National Wiring Regulation When wiring please choose the corresponding chart or it may...

Страница 16: ...N 3 4 5 core cable 5 2 5mm2 3 core cable 3 2 5mm2 1 core sheild wire 1 0 5mm2 POWER 220 240 50Hz INDOOR UNIT Y G Y G L N 1 2 N T3 E 3 4 WHITE T3 BLACK E Fig 10 5 3 core cable 3 2 5mm2 3 core cable 3...

Страница 17: ...3 XT2 T3 T3 E E Y G Y G POWER 220 240 50Hz 3 core cable 3 2 5mm2 3 core cable 3 2 5mm2 3 core cable 3 2 5mm2 1 core sheild wire 1 0 5mm2 Fig 10 7 Model 24 36 1 PHASE Air Conditioner Link circuit For R...

Страница 18: ...able 3 2 5mm 2 5 core cable 5 2 5mm 2 5 core cable 5 2 5mm 2 POWER 380 415V 3N 50Hz Model 36 60 3 PHASE Air Conditioner Link circuit For R22 Cooling Heating Model 36 1 PHASE OUTDOOR UNIT L 1 N 1 L N 1...

Страница 19: ...XT4 A B C N 3 core cable 3 2 5mm 2 5 core cable 5 2 5mm 2 5 core cable 5 2 5mm 2 POWER 380 415V 3N 50Hz Model 72 3 PHASE Fig 10 10 Air Conditioner Link circuit For R22 Cooling only POWER 5 core cable...

Страница 20: ...r Conditioner Link circuit For R22 Cooling only POWER 5 core cable 5 2 5mm 2 5 core cable 5 2 5mm 380 415V 3N 50Hz 2 INDOOR UNIT OUTDOOR UNIT XT1 A B C N 1 2 3 XT1 XT2 4 1 core cable 1 2 5mm 2 A B C N...

Страница 21: ...onditioner Link circuit For R22 Cooling Heating Model 24 1 PHASE L N 1 2 3 INDOOR UNIT POWER 220 240 50Hz 3 core cable 3 2 5mm2 1 core cable 1 2 5mm2 Y G Y G OUTDOOR UNIT XT3 L N S Fig 10 14 Fig 10 15...

Страница 22: ...T3 T3 E E Y G Y G Y G POWER 220 240 50Hz 3 core cable 3 2 5mm2 3 core cable 3 2 5mm2 1 core sheild wire 1 0 5mm2 Fig 10 16 Model 36 1 PHASE Air Conditioner Link circuit For R22 Cooling only N L 1 2 3...

Страница 23: ...4 A B C N 3 core cable 3 2 5mm 2 5 core cable 5 2 5mm 2 5 core cable 5 2 5mm 2 POWER 380 415V 3N 50Hz Model 36 60 3 PHASE 4 Fig 10 19 Air Conditioner Link circuit For R22 Cooling only POWER 5 core cab...

Страница 24: ...The design and specifications are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer for details 2011 02 23 202000100290...