10

installation manual 

Additional Refrigerant Charge 

7.2 

Refrigerant cannot be charged until field wiring has been 
completed.

Refrigerant may only be charged after performing the leak 
test  and the vacuum pumping.

When charging a system, care shall be taken that its 
maximum permissible charge is never exceeded, in view of 
the danger of liquid hammer.

Charging with an unsuitable substance may cause 
explosions and accidents, so always ensure that the 
appropriate refrigerant is charged.

Refrigerant containers shall be opened slowly.

Always use protective gloves and protect your eyes when 
charging refrigerant.

NOTE 

CAUTION 

If a negative result is gotten for R from Table 7-4, no 
refrigerant needs to be added nor removed.

 

The outdoor unit is factory charged with refrigerant. Calculate 
the added refrigerant according  to the diameter  and  the 
length  of  the  liquid side pipe of the outdoor unit/indoor unit 
connection.

Table 7-4

Ø

6.4  

Ø

9.5  

Ø

12.7  

R(g): Additional refrigerant to be charged 
L(m): The length of the refrigerant pipe(one-way) 
D(mm) : Liquid Side Piping Diameter 

30g/m×(L-5) 65g/m×(L-5) 115g/m×(L-5)

Added Refrigerant When  

Over 5m (One-way) 

Less than 5m (One-way)  

R(g) 

L(m) 

D(mm) 

CAUTION 

The drain pipe of indoor unit must be heat insulated, or it will 
condense dew, as well as the connections of the indoor unit. 
 
Hard PVC binder must be used for pipe connection, and make 
sure there is no leakage. 

8.    CONNECT THE DRAIN PIPE

Install the drainpipe of the indoor unit 

The outlet has PTI screw bread, Please use sealing materials 
and pipe sheath(fitting) when connecting PVC pipes.  

Drainage test 

Install the drain joint of the outdoor unit 

Check whether the drainpipe is unhindered. 

New built house should have this test done before 
paving the ceiling. 

With the connection part to the indoor unit, please be noted not 
to impose pressure on the side of indoor unit pipes. 
 
When the declivity of the drain pipe downwards is over 1/100, 
there should not be any winding. 
 
The total length of  the drain pipe when pulled out traversely 
shall not exceed 20m, when the pipe is over long, a prop stand 
must be installed to prevent winding.  
 
Refer to the Fig.8-1 for the installation of the pipes.  

1.5m~2m

Insulating

material

Downward declivity

lower than 1/100 

Bend

S shape 

VP30

Downw ard declivity 

lower t han 1/100

Put as deep as possible

(about 10cm)

Fig. 8-1 

Seal

The base pan hole

of outdoor unit

Drain joint

Seal

The base pan 

of outdoor unit 

Drain 

joint

Fig.8-2 

Fit the seal into the drain joint, then insert the drain joint into 
the base pan hole of outdoor, rotate 90

0

 to securely 

assemble them. Connect the drain joint with an extension 
drain hose (Locally purchased), in case of the condensate 
draining off the outdoor unit during the heating mode.

(Refer 

to Fig.8-2) 

All the pictures in this manual are for explanation purpose 
only. They may be slightly different from the air conditioner 
you purchased.The actual shape shall prevail. 

NOTE 

Содержание Ceiling series

Страница 1: ...Ceiling And Floor Type INSTALLATION MANUAL Thank you very much for purchasing our air conditioner Before using your air conditioner please read this manual carefully and keep it for future reference...

Страница 2: ...hall not be installed in the laundry Before obtaining access to terminals all supply circuits must be disconnected The appliance must be positioned so that the plug is accessible The enclosure of the...

Страница 3: ...perty damage Install the indoor and outdoor units power supply wiring and connecting wires at least 1 meter away from televisions or radios in order to prevent image interference or noise Depending on...

Страница 4: ...ve poles are right positions when loading batteries This manual is subject to changes due to technological improvement without further notices Cautions on remote controller installation Remote control...

Страница 5: ...e the service agent When handling the unit take into account the following 5 INDOOR UNIT INSTALLATION 5 1 Installation place Refer to Fig 5 1 Fig 5 2 Fig 5 3 and Table 5 1 for specification The indoor...

Страница 6: ...size of the ceiling to be handled Do keep the ceiling flat Consolidate the roof beam for possible vibration 1 Installing 10 hanging screw bolts 4 bolts 2 Install the indoor unit After the selection of...

Страница 7: ...e piping length between the outdoor unit and the indoor unit may not exceed the allowable piping length In the case that the installation place is exposed to strong wind such as a seaside make sure th...

Страница 8: ...all prevail Since the gravity center of the unit is not at its physical center so please be careful when lifting it with a sling Never hold the inlet of the outdoor unit to prevent it from deforming D...

Страница 9: ...ensation CAUTION The Procedure of Connecting Pipes 7 1 CAUTION All field piping must be provided by a licensed refrigeration technician and must comply with the relevant local and national codes Do no...

Страница 10: ...22 13 5 16 5 5 7 7 9 9 11 11 13 11 5 13 9 1 2 4 3 5 6 Fig 7 7 Using the vacuum pump Loosen and remove the maintenance nuts of stop valves A and B and connect the charge hose of the manifold valve to t...

Страница 11: ...make sure there is no leakage 8 CONNECT THE DRAIN PIPE Install the drainpipe of the indoor unit The outlet has PTI screw bread Please use sealing materials and pipe sheath fitting when connecting PVC...

Страница 12: ...hecked carefully after wiring The power cord type designation is H07RN F 9 CONNECTIVE DIAGRAM Orifice Fig 9 1 Fig 9 2 For ensuring throttled efficiency Please mount the Orifice as horizontally as poss...

Страница 13: ...ioner is pre heated by turning on the power The indoor unit and outdoor unit are installed properly Tubing and wiring are correctly completed The refrigerant pipe system is leakage checked The drainag...

Страница 14: ...ELECTRIC SIGNAL INDOOR OUTDOOR CONNECTING WIRING mm CIRCUIT BREAKER FUSE A 2 INDOOR UNIT POWER WIRING mm PHASE FREQUENCY AND VOLT WEAK ELECTRIC SIGNAL 3x2 5 20 16 40 25 2 5 2 5 Table 10 1 GROUND WIRIN...

Страница 15: ...n air gap contact separation in all active conductors should be incorporated in the fixed wiring according to the National Wiring Regulation When wiring please choose the corresponding chart or it may...

Страница 16: ...N 3 4 5 core cable 5 2 5mm2 3 core cable 3 2 5mm2 1 core sheild wire 1 0 5mm2 POWER 220 240 50Hz INDOOR UNIT Y G Y G L N 1 2 N T3 E 3 4 WHITE T3 BLACK E Fig 10 5 3 core cable 3 2 5mm2 3 core cable 3...

Страница 17: ...3 XT2 T3 T3 E E Y G Y G POWER 220 240 50Hz 3 core cable 3 2 5mm2 3 core cable 3 2 5mm2 3 core cable 3 2 5mm2 1 core sheild wire 1 0 5mm2 Fig 10 7 Model 24 36 1 PHASE Air Conditioner Link circuit For R...

Страница 18: ...able 3 2 5mm 2 5 core cable 5 2 5mm 2 5 core cable 5 2 5mm 2 POWER 380 415V 3N 50Hz Model 36 60 3 PHASE Air Conditioner Link circuit For R22 Cooling Heating Model 36 1 PHASE OUTDOOR UNIT L 1 N 1 L N 1...

Страница 19: ...XT4 A B C N 3 core cable 3 2 5mm 2 5 core cable 5 2 5mm 2 5 core cable 5 2 5mm 2 POWER 380 415V 3N 50Hz Model 72 3 PHASE Fig 10 10 Air Conditioner Link circuit For R22 Cooling only POWER 5 core cable...

Страница 20: ...r Conditioner Link circuit For R22 Cooling only POWER 5 core cable 5 2 5mm 2 5 core cable 5 2 5mm 380 415V 3N 50Hz 2 INDOOR UNIT OUTDOOR UNIT XT1 A B C N 1 2 3 XT1 XT2 4 1 core cable 1 2 5mm 2 A B C N...

Страница 21: ...onditioner Link circuit For R22 Cooling Heating Model 24 1 PHASE L N 1 2 3 INDOOR UNIT POWER 220 240 50Hz 3 core cable 3 2 5mm2 1 core cable 1 2 5mm2 Y G Y G OUTDOOR UNIT XT3 L N S Fig 10 14 Fig 10 15...

Страница 22: ...T3 T3 E E Y G Y G Y G POWER 220 240 50Hz 3 core cable 3 2 5mm2 3 core cable 3 2 5mm2 1 core sheild wire 1 0 5mm2 Fig 10 16 Model 36 1 PHASE Air Conditioner Link circuit For R22 Cooling only N L 1 2 3...

Страница 23: ...4 A B C N 3 core cable 3 2 5mm 2 5 core cable 5 2 5mm 2 5 core cable 5 2 5mm 2 POWER 380 415V 3N 50Hz Model 36 60 3 PHASE 4 Fig 10 19 Air Conditioner Link circuit For R22 Cooling only POWER 5 core cab...

Страница 24: ...The design and specifications are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer for details 2011 02 23 202000100290...

Отзывы: