Page
20
of
35
Restrained Beam Ratings—1, 1-1/2, 2, 3, 4 Hr (See Item 7)
Unrestrained Beam Ratings—1, 1-1/2, 2, 3, 4 Hr (See Item 7)
1.
Steel Beam —
W10x88 min size.
2.
Normal Weight or Lightweight Concrete —
Compressive strength, 3000 psi. For
normal weight concrete either carbonate or siliceous aggregate may be used. Unit weight,
148 pcf. For lightweight concrete, unit weight 110 pcf.
3.
Shear Connector (Optional) —
Studs, 3/4 in. diam headed type or equivalent per AISC
specifications. Welded to the top flange of beam through the steel floor units.
4.
Welded Wire Fabric (Optional) —
6 x 6-10/10 SWG.
5.
Steel Floor and Form Units —
1-1/2, 2, or 3 in. deep fluted, welded to beam.
6.
Glass Fiber Mesh —
3/16 in. by 3/16 in. square pattern glass fiber reinforcing mesh
weighing 5.3 oz per sq. yard shall be placed, following the contour of the beam, in the
following manner:
Thkns of Protection Material (in.)
Depth of Placement of Reinforcing
Mesh (in.)
.12 - .24
Mid point of Protection Material
.24 and greater
.12