11
9. Remove the heater front securing screws, one either side. Re-
fer figure 12.
10.Remove the heater front by pulling it towards you gently to
partly disengage it from the body of the heater then gently lift
it up vertically to completely disengage it. Refer figure 13.
11.Remove the inner glass. Slacken off screws in top clamp and
remove side clamps. Refer figure 14.
11
12
13
14
14
To check control outlet pressure at burner ‘Full on” and ‘Low
Flame” positions remove the plastic cap from the regulator
adjustment location as indicated in figures 22 (a) & (b).
18 The pressure point is closed with a captive screw. Turn screw
6 revolution anticlockwise to open the pressure point as indi-
cated on figure 23 (a) and place manometer tube over the test
point as per figure 23 (b).
19. Switch the top two control buttons to “Full On” position as
indicated in figure 24(a) and using a ring spanner, as per
figure 24(b), adjust the pressure to 1kPa for Natural gas or
2.65 kPa for LPG. (Turn clockwise to increase pressure and
anticlockwise to decrease pressure).
20. Switch the stop button back to “Low Flame’ position as indi-
cated in figure 25(a),
retain spanner in position
and using a
screwdriver as per figure 25(b) adjust the central screw con-
trol to give a pressure reading of 0.3 kPa for Natural Gas and
1.1 kPa for LPG. (Turn clock-wise to increase pressure and
anticlockwise to decrease pressure).
22
23
24
Gas pressure point
Installation instructions continued