SYSTEM 238 Installation Manual

4

ALPHA KEYPAD INFORMATION

The Alpha keypad uses a top viewing display. This means the display
reads most clearly when viewed from a top angle rather than straight
on or from below. Mounting the keypad at the light switch level and
adjusting the viewing angle gives the best viewing results.

+

When operated as a Super-
vised Loop, an open will be
reported as a Trouble.
Whether the system is armed
or disarmed. A short on a
Supervised Loop will be re-
ported as an alarm if the sys-
tem is armed, but will have no
effect if the system is dis-
armed.

-

Supervised Loop

N.C.

Trouble

N.O.

Alarm

Loop 8
Terminals C and Z8 are a standard loop that can also power 2-wire
devices. It supplies 10 - 12.5 VDC at 50 mA.  Use Loop 8 to power 2-
wire glass-breaks and smoke detectors.

1.

Position the tamper switch inside the cabinet at the lower right
corner of the cabinet. For the wall tamper, the plunger should go
through the small hole in the back of the cabinet. For the door
tamper, the plunger should face out from the cabinet. Refer to the
drawing below
.

2.

Connect the tamper switches in series and wire the tamper
 terminals to a dedicated zone of the control panel.

3.

Program the dedicated zone as desired: NC, EOL, 24-hour, etc.

Once the tamper switches are installed, opening the cabinet door or
removing the cabinet from the wall will result in a tamper signal at the
panel.

TAMPER SWITCH INSTALLATION

C&K has designed the SYSTEM 238 cabinet to use the  Ademco
Model 19
 tamper switch. The cabinet is constructed in order to
accommodate two switches.  One tamper for the cover and a second
switch for a wall tamper. To install the tamper switches:

Tamper Switches installed in the SYSTEM 238 cabinet

LEAD-ACID
BATTERY

PRINTED CIRCUIT
BOARD

WALL
TAMPER SWITCH

DOOR
TAMPER SWITCH

TELEPHONE INTERFACE

Connect the SYSTEM 238 to the phone line using
the 9.X PCF cord (not included). The cord has an
8-pin telco plug on one end. Plug the telco end
directly into the phone companies RJ31 or RJ38X
jack. Connect the flying leads to the SYSTEM 238
PCB as outlined in the next column:

KEYPAD  SETUP

Voltage Variations
Output voltages at terminals 5, 7, and 8  may vary between 9.0 and
14.4 VDC (worst case), depending on the load, battery condition, and
AC line voltage.

SYSTEM  START-UP

Five minutes after the panel is powered up, it will dynamically test the
standby battery by interrupting AC power for two minutes and monitor-
ing the battery under load.

Standby Battery Time with One LED Keypad

AUX POWER DRAIN*

50 mA

32 hours

STANDBY TIME

* Total power for all keypads, auxiliary, and Loop 8

150 mA
250 mA
500 mA

24 hours
16 hours
10 hours

TB1

If you replace the battery after a SYSTEM TROUBLE - LOW BATTERY
message, you must test the battery under load conditions. Press [*] [6]
[4] [#] to start the Dynamic Battery Test.

NOTE: Some keypads may use [SHIFT] and [ENTER] in

place of the [*] and [#] keys, respectively.

RJ-38X Wiring
Diagram

T
R
T1
R1

Incoming

Telco Line

1

2

3

4

8

7

6

5

T1

R1

T1 = Seized Tip

R1 = Seized Ring

Red

Green

Protector

Ring

Tip

Tamper Jumper

House

Phones

9.X PCF
The 9.X PCF has eight flying leads. Wire them to the PCB terminals
as follows:

GRAY = ring seized

GREEN = tip

RED = ring

BROWN = tip seized

BLUE and ORANGE = tamper

YELLOW and BLACK = not used

Содержание System 238

Страница 1: ...ort 2 5 8 5 VDC normal 8 6 15 VDC open Install transformer on unswitched power receptacle Only use 12 VDC 6 5 AH sealed lead acid battery POWER SUPPLY INFORMATION Replace battery every 3 5 years with...

Страница 2: ...han 45 seconds 7 No Exit Delay may be greater than 60 seconds 8 The Dynamic Battery Test must be enabled 9 The Unit Status Report must be enabled 10 The 24 hour Check in must be enabled 11 No Delay Be...

Страница 3: ...STEM 238 is capable of addressing up to 8 Alpha keypads LED keypads do not require addressing Each LED keypad uses 35 mA of current Each LCD keypad uses 64 mA of current See Available Power for curren...

Страница 4: ...structed in order to accommodate two switches One tamper for the cover and a second switch for a wall tamper To install the tamper switches Tamper Switches installed in the SYSTEM 238 cabinet LEAD ACI...

Страница 5: ...dows EOL circuit Zone 4 doors or windows EOL circuit Zone 5 interior EOL circuit Zone 6 interior EOL circuit Zone 7 24 hour panic or tamper EOL circuit Zone 8 fire or smoke supervised EOL circuit Emer...

Страница 6: ...owed by the key Then enter the data to be stored and again press the key Warning If you enter a Command Location and then press the key without entering any program data the keypad will beep 5 times i...

Страница 7: ...ess the programming mode when the control panel is disarmed NOTE Programming the Keypad is not the same as Keypad Programming 1 2 3 4 5 6 7 8 9 0 ALPHA II Programming Template ALPHA PLUS Programming T...

Страница 8: ...Arm and Disarm with O C Reports No Shunting 7 Arm Only No Closing Report Shunting Allowed 8 Disarm Only No Opening Report Shunting Allowed 9 Arm and Disarm No O C Reports Shunting Allowed 0 Arm Only...

Страница 9: ...eceiver 1 Message Format 1 3 1 single 2 3 1 extended 3 4 2 2 digit reporting code 4 4 1 5 CFSK III 6 4 9 Ademco DTMF 7 4 2 SumCheck 5 CFSK III 6 DTMF 1400 Hz 3 SumCheck 1400 Hz 4 SumCheck 2300 Hz 1 Fa...

Страница 10: ...rings with long pauses between rings 1 Double ring rings twice quickly followed by a long pause then rings twice again Digit Position 6 Dialing Attempts 5 5 tries 6 6 tries 7 7 tries 8 8 tries 1 1 tr...

Страница 11: ...he zeroes will not be dialed Command Location 0E Receiver 1 Phone Number digits 7 12 0 E 1 2 3 4 5 6 0 0 0 0 0 0 Default Values Command Location 0F Receiver 1 Phone Number digits 13 18 0 F 1 2 3 4 5 6...

Страница 12: ...Fill in remaining positions with 0 The zeroes will not be dialed 6 Order in which the numbers will be dialed 0 9 dialing digits 0 dial tone detect 2 DTMF dialing only not used in pulse dialing 3 DTMF...

Страница 13: ...be dialed Fill in remaining positions with 0 The zeroes will not be dialed 0 9 dialing digits 0 dial tone detect 2 DTMF dialing only not used in pulse dialing 3 DTMF dialing only not used in pulse dia...

Страница 14: ...conds 1 250 milliseconds 2 500 milliseconds 3 750 milliseconds Digit Position 3 Loop Restore Type 0 No Restoral Report sent 1 Restoral sent when loop normal 2 Restoral sent when loop normal and bell s...

Страница 15: ...ne Report Code Command Location 29 Soft Zone C Police Digit Positions 1 and 2 Police Report Code 1 2 3 4 0 0 1 2 Default Values 2 9 Digit Position 3 Police Zone Receiver Select Digit Position 4 Police...

Страница 16: ...ng options 1 Low battery 2 AC fail 3 Bell fuse fail 4 Loop trouble 5 Failed to communicate 6 Battery restore UNIT STATUS FIXED EXTENSION CODES 7 AC restore 8 Bell fuse restore 9 Loop trouble restore A...

Страница 17: ...s Report Code Valid entries are 0 F The User ID will be reported as the second digit when reporting in the 3 1 Extended 4 2 or CFSK formats Program 0 to disable Duress Reports Default Values 1 2 3 4 5...

Страница 18: ...efault Values 1 2 3 4 5 1 0 0 0 1 2 E Command Location 2F Unit Control Digit Position 1 Local System Only Default Values 1 2 3 4 0 0 1 1 2 F Digit Position 2 Enable Daily Dynamic Battery Test Digit Po...

Страница 19: ...g on alarm for time programmed in 0B 1 Command Location A0 Set Test Report Countdown Timer Digit Position 1 Set Countdown Timer A 0 1 0 1 4 hour 1 1 2 hour 2 1 hour 3 2 hours 4 3 hours 5 4 hours 6 6 h...

Страница 20: ...quipment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruc tions may cause harmful interference to radio communications...

Страница 21: ...roup Bypass and Instant Same as Group Bypass above except system Combination 4 7 or Arm is Instant Armed Exit Delay operates normally Combination 7 4 upon expiration of Exit Delay all delayed zones ar...

Страница 22: ...exadecimal values are entered through the use of the key and one of the digits 0 5 For additional help with entering hexadecimal numbers refer to page 7 The hexadecimal conversion chart is also found...

Страница 23: ...two keypads are trying to communicate at the same time The only way to correct the problem is to disconnect both keypads and then re address one of them making sure that the address is not used by an...

Страница 24: ...It acts Time as a buffer on the loop to minimize the possibility of fast acting sensors such as swingers on window foil producing false alarms Loop Control 1F 26 3 Loop Restore This option is used in...

Страница 25: ...riod of four Power Up minutes after power is initially applied to the panel This allows Delay the sensors such as PIR s time to stabilize when initializing or prevents powered devices such as smoke de...

Страница 26: ...unction with the alarm system may not sense fires that start where smoke cannot reach the detectors such as chimneys walls or roofs or on the other side of closed doors Smoke detectors also may not se...

Страница 27: ...ate Control Location Installer Address VOLTS AC volts term 1 and 2 AUX POWER VOLTS term 5 and 6 CURRENT Keypads term 6 and 8 SWITCHED AUX term 5 and 6 UNSWITCHED AUX term 6 and 7 LOOP 8 POWERED DEVICE...

Страница 28: ...witches 3 1 0 1 0 0 Loop 2 Switches 3 3 0 1 0 0 Loop 4 Switches 3 5 0 1 0 0 Loop 6 Switches 3 7 0 0 0 0 Loop 8 Switches 1 1 A 1 D 2 A 1 Event Reports 2 C B 1 C 1 1 1 0 0 0 2 E Opening Closing Reports...

Отзывы: