SYSTEM 238 Installation Manual

Program Option

CL

Program Function

Comments

Audible/Visual

2E (1 & 2)

Entry/Exit

If Digit Postition (1) is programmed for Entry Pre-Alarm, the

Switches

Pre-Alarm

keypad will beep for the amount of time programmed for the Entry
Delay Time (CL 2D (3)).  If Digit Position (2) is programmed for
Exit Pre-Alarm, the keypad will beep for the time programmed
into CL 2D (4), Exit Delay Time.  The speed at which the keypad
beeps will increase during the last 10 seconds of the Delay time.
Alpha II keypads will display a bar graph in addition to the audible
tone.

Unit Control

2F (3)

Enable 4-minute

Suppresses all trouble and alarm reports for a period of four

Power-Up

minutes after power is initially applied to the panel.  This allows

Delay

the sensors, such as PIR's time to stabilize when initializing or
prevents powered devices, such as smoke detectors, from
sending alarms when first starting panel with a dead battery or no
battery connected.

Loop Switches

30 - 37 (3)

Allow Group

This allows multiple loops to be shunted simultaneously with a

Shunting

single keypad command.  This is typically done on all interior

loops in a system.

Loop Switches

30 - 37 (4)

Delay Before Dial This option programs the loops to have a delay after they are

triggered to allow the User time to shut down the system in the
event of an accidental triggering of the zone.  The amount of time
is determined by the value programmed into CL 0B Digit Position
(1).  The time delay may be between 10 and 150 seconds, in 10
second intervals.

Содержание System 238

Страница 1: ...ort 2 5 8 5 VDC normal 8 6 15 VDC open Install transformer on unswitched power receptacle Only use 12 VDC 6 5 AH sealed lead acid battery POWER SUPPLY INFORMATION Replace battery every 3 5 years with...

Страница 2: ...han 45 seconds 7 No Exit Delay may be greater than 60 seconds 8 The Dynamic Battery Test must be enabled 9 The Unit Status Report must be enabled 10 The 24 hour Check in must be enabled 11 No Delay Be...

Страница 3: ...STEM 238 is capable of addressing up to 8 Alpha keypads LED keypads do not require addressing Each LED keypad uses 35 mA of current Each LCD keypad uses 64 mA of current See Available Power for curren...

Страница 4: ...structed in order to accommodate two switches One tamper for the cover and a second switch for a wall tamper To install the tamper switches Tamper Switches installed in the SYSTEM 238 cabinet LEAD ACI...

Страница 5: ...dows EOL circuit Zone 4 doors or windows EOL circuit Zone 5 interior EOL circuit Zone 6 interior EOL circuit Zone 7 24 hour panic or tamper EOL circuit Zone 8 fire or smoke supervised EOL circuit Emer...

Страница 6: ...owed by the key Then enter the data to be stored and again press the key Warning If you enter a Command Location and then press the key without entering any program data the keypad will beep 5 times i...

Страница 7: ...ess the programming mode when the control panel is disarmed NOTE Programming the Keypad is not the same as Keypad Programming 1 2 3 4 5 6 7 8 9 0 ALPHA II Programming Template ALPHA PLUS Programming T...

Страница 8: ...Arm and Disarm with O C Reports No Shunting 7 Arm Only No Closing Report Shunting Allowed 8 Disarm Only No Opening Report Shunting Allowed 9 Arm and Disarm No O C Reports Shunting Allowed 0 Arm Only...

Страница 9: ...eceiver 1 Message Format 1 3 1 single 2 3 1 extended 3 4 2 2 digit reporting code 4 4 1 5 CFSK III 6 4 9 Ademco DTMF 7 4 2 SumCheck 5 CFSK III 6 DTMF 1400 Hz 3 SumCheck 1400 Hz 4 SumCheck 2300 Hz 1 Fa...

Страница 10: ...rings with long pauses between rings 1 Double ring rings twice quickly followed by a long pause then rings twice again Digit Position 6 Dialing Attempts 5 5 tries 6 6 tries 7 7 tries 8 8 tries 1 1 tr...

Страница 11: ...he zeroes will not be dialed Command Location 0E Receiver 1 Phone Number digits 7 12 0 E 1 2 3 4 5 6 0 0 0 0 0 0 Default Values Command Location 0F Receiver 1 Phone Number digits 13 18 0 F 1 2 3 4 5 6...

Страница 12: ...Fill in remaining positions with 0 The zeroes will not be dialed 6 Order in which the numbers will be dialed 0 9 dialing digits 0 dial tone detect 2 DTMF dialing only not used in pulse dialing 3 DTMF...

Страница 13: ...be dialed Fill in remaining positions with 0 The zeroes will not be dialed 0 9 dialing digits 0 dial tone detect 2 DTMF dialing only not used in pulse dialing 3 DTMF dialing only not used in pulse dia...

Страница 14: ...conds 1 250 milliseconds 2 500 milliseconds 3 750 milliseconds Digit Position 3 Loop Restore Type 0 No Restoral Report sent 1 Restoral sent when loop normal 2 Restoral sent when loop normal and bell s...

Страница 15: ...ne Report Code Command Location 29 Soft Zone C Police Digit Positions 1 and 2 Police Report Code 1 2 3 4 0 0 1 2 Default Values 2 9 Digit Position 3 Police Zone Receiver Select Digit Position 4 Police...

Страница 16: ...ng options 1 Low battery 2 AC fail 3 Bell fuse fail 4 Loop trouble 5 Failed to communicate 6 Battery restore UNIT STATUS FIXED EXTENSION CODES 7 AC restore 8 Bell fuse restore 9 Loop trouble restore A...

Страница 17: ...s Report Code Valid entries are 0 F The User ID will be reported as the second digit when reporting in the 3 1 Extended 4 2 or CFSK formats Program 0 to disable Duress Reports Default Values 1 2 3 4 5...

Страница 18: ...efault Values 1 2 3 4 5 1 0 0 0 1 2 E Command Location 2F Unit Control Digit Position 1 Local System Only Default Values 1 2 3 4 0 0 1 1 2 F Digit Position 2 Enable Daily Dynamic Battery Test Digit Po...

Страница 19: ...g on alarm for time programmed in 0B 1 Command Location A0 Set Test Report Countdown Timer Digit Position 1 Set Countdown Timer A 0 1 0 1 4 hour 1 1 2 hour 2 1 hour 3 2 hours 4 3 hours 5 4 hours 6 6 h...

Страница 20: ...quipment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruc tions may cause harmful interference to radio communications...

Страница 21: ...roup Bypass and Instant Same as Group Bypass above except system Combination 4 7 or Arm is Instant Armed Exit Delay operates normally Combination 7 4 upon expiration of Exit Delay all delayed zones ar...

Страница 22: ...exadecimal values are entered through the use of the key and one of the digits 0 5 For additional help with entering hexadecimal numbers refer to page 7 The hexadecimal conversion chart is also found...

Страница 23: ...two keypads are trying to communicate at the same time The only way to correct the problem is to disconnect both keypads and then re address one of them making sure that the address is not used by an...

Страница 24: ...It acts Time as a buffer on the loop to minimize the possibility of fast acting sensors such as swingers on window foil producing false alarms Loop Control 1F 26 3 Loop Restore This option is used in...

Страница 25: ...riod of four Power Up minutes after power is initially applied to the panel This allows Delay the sensors such as PIR s time to stabilize when initializing or prevents powered devices such as smoke de...

Страница 26: ...unction with the alarm system may not sense fires that start where smoke cannot reach the detectors such as chimneys walls or roofs or on the other side of closed doors Smoke detectors also may not se...

Страница 27: ...ate Control Location Installer Address VOLTS AC volts term 1 and 2 AUX POWER VOLTS term 5 and 6 CURRENT Keypads term 6 and 8 SWITCHED AUX term 5 and 6 UNSWITCHED AUX term 6 and 7 LOOP 8 POWERED DEVICE...

Страница 28: ...witches 3 1 0 1 0 0 Loop 2 Switches 3 3 0 1 0 0 Loop 4 Switches 3 5 0 1 0 0 Loop 6 Switches 3 7 0 0 0 0 Loop 8 Switches 1 1 A 1 D 2 A 1 Event Reports 2 C B 1 C 1 1 1 0 0 0 2 E Opening Closing Reports...

Отзывы: