11
Figure 4
•
Adjustment
procedure.
a) Fully open bypass and outlet valves.
b) With boiler running, read the inlet temperature after 15 minutes.
c) If the inlet temperature is less than 110 ºF slowly close outlet valve until the inlet
temperature climbs to 110 ºF
d) If the inlet temperature is greater than 110ºF but not greater than 140 ºF no
further adjustment is required.
e) Check the inlet temperature after 5 minutes and make final adjustments.