9
TABLE 2
20
º
F (11
º
C) TEMP
RISE
30
º
F (16.7
º
C) TEMP
RISE
35
º
F (19.4
º
C) TEMP
RISE
Model U.S
G.P.M.
Δ
P
ft. U.S
G.P.M.
Δ
P
ft. U.S
G.P.M.
Δ
P ft.
BF 480
40.0
0.5
26.5
0.3
22.5
0.2
BF 660
55.0
1.1
36.5
0.5
31.0
0.4
BF 840
70.0
2.1
46.5
0.9
40.0
0.7
BF 1020
85.0
3.3
56.5
1.5
48.5
1.2
BF 1200
66.5
2.3
57.0
1.7
BF 1380
76.5
3.3
65.5
2.5
BF 1560
86.0
4.5
74.0
3.4
BF 1740
96.0
5.9
82.0
4.5
BF1950
108.0
6.8
92.5
6.0
Contact Camus for recommendation
Figure 3
If the boiler is installed above radiation level, it must be provided with a low water cutoff device
at the time of boiler installation. (Available from factory)
To eliminate trapped air, install venting devices at high points in the system as well as in the
piping on the suction of the pump and in the piping on the discharge of the boiler.
Use suitable pipe hangers or floor stands to support the weight of all water and gas piping.
Do not allow the boiler to run with inlet water temperature below 110ºF.
The boiler must be installed so that the gas ignition system components are protected from
water (dripping, spraying, rain, etc.) during appliance operation and service (circulator
replacement, control replacement, etc.)