Section 14. PakBus Overview
137
14.5.1.1 Automatic Packet Size Adjustment
The BMP5 file receive transaction allows the BMP5 client (LoggerNet) to
specify the size of the next fragment of the file that the CR200(X) sends.
Note
The file receive transaction is used to get table definitions from the
datalogger.
Because LoggerNet must specify a size for the next fragment of the file, it uses
whatever size restrictions that apply to the link.
Hence, the size of the responses to the file receive commands that the CR200(X)
sends is governed by the maxPacketSize setting for the datalogger as well as
that of any of its parents in LoggerNet's network map. Note that this calculation
also takes into account the error rate for devices in the link.
BMP5 data collection transaction does not provide any way for the client to
specify a cap on the size of the response message. This is the main reason why
the "Max Packet Size" setting exists in the CR200(X). The CR200(X) can look
at this setting at the point where it is forming a response message and cut short
the amount of data that it would normally send if the setting limits the message
size.
14.5.2 Ping
Link integrity can be verified with the following procedure by using
PakBusGraph | Ping Node. Nodes can be pinged with packets of 50, 100, 200 or
500 bytes.
Note
Do not use packet sizes greater than 90 when pinging with 100 mW radio
modems and radio enabled dataloggers (
APPENDIX. Telecommunications
Hardware
(Appendix p. 32)).
Pinging with ten repetitions of each packet size will characterize the link. Before
pinging, all other network traffic (scheduled data collections, clock checks, etc.)
should be temporarily disabled. Begin by pinging the first layer of links
(neighbors) from the PC, then proceed to nodes that are more than one hop
away.
TABLE. PakBus Link Performance Gage
(p. 137) provides a link
performance gage.
Table 18.
PakBus Link Performance Gage
500 byte
Ping Sent
Successes
Link Status
10 10 excellent
10 9 good
10 7-8 adequate
10 <7 marginal
Содержание CR200
Страница 32: ...Section 2 Quickstart Tutorial 22 ...
Страница 45: ...Section 3 Overview 35 3 3 Specifications ...
Страница 46: ...Section 3 Overview 36 ...
Страница 58: ...Section 4 Sensor Support 48 ...
Страница 62: ...Section 5 Measurement and Control Peripherals 52 ...
Страница 78: ...Section 8 CR200 X Configuration 68 ...
Страница 102: ...Section 9 Programming 92 ...
Страница 138: ...Section 11 Programming Resource Library 128 ...
Страница 156: ...Section 16 Support Software 146 ...
Страница 160: ...Section 17 Care and Maintenance 150 ...
Страница 166: ...Section 18 Troubleshooting 156 18 3 3 Diagnosis and Fix Procedures 18 3 3 1 Battery Voltage Test ...
Страница 167: ...Section 18 Troubleshooting 157 18 3 3 2 Charging Circuit Test Solar Panel ...
Страница 168: ...Section 18 Troubleshooting 158 18 3 3 3 Charging Circuit Test Transformer ...
Страница 169: ...Section 18 Troubleshooting 159 18 3 3 4 Adjusting Charging Circuit Voltage ...
Страница 170: ...Section 18 Troubleshooting 160 ...
Страница 184: ...Appendix A Glossary 14 ...
Страница 190: ...Appendix B Status Table and Settings 20 ...
Страница 192: ...Appendix C Serial Port Pin Outs 22 ...
Страница 211: ......