Section 4. Sensor Support
45
When a pulse channel is configured for pulse input mode, an internal 100 k
Ω
pull-up resistor to +5 Volt on the P_SW input is automatically employed. This
pull-up resistor accommodates open-collector (open-drain) output devices for
high-frequency input. An external 100 k
Ω
pull-up resistor connecting
to P_LL, C1, or C2 must be added to perform pulse counting on any of those
channels (See
Multiple Switch Closure Measurements
p. 112).
The maximum input voltage on P_SW is 4 volts. For C1 and C2 the maximum
input voltage is 6.5 volts.
4.4.1.2
Low-Level AC (P_LL)
Rotating magnetic pickup sensors commonly generate AC output voltages
ranging from millivolts at low rotational speeds to several volts at high
rotational speeds. Channel P_LL contains internal signal conditioning hardware
for measuring low-level AC output sensors. P_LL measure signals ranging
from 20 mV RMS (±28 mV peak) to 14 V RMS (±20 V peak). Internal AC
coupling is incorporated in the low-level AC hardware to eliminate DC offset
voltages of up to ±0.5 V.
4.4.2
Pulse Input on Digital I/O Channels C1–C2
Read More! Review digital I/O channel specifications in
Specifications
p. 35.
Review pulse counter programming in CRBASIC Help for the PulseCount ()
instruction.
Digital I/O channels C1 – C2 can be configured to measure pulse input signals.
Pulse input signals require external 100 k
Ω
pull-up resistors to be connected
between and the control ports. Maximum input voltage level is 6.5 V.
If pulse inputs greater than +6.5 V need to be measured, external signal
conditioning must employed. Contact Campbell Scientific for further
information.
Low-level AC signals cannot be measured directly on channels C1 – C2.
4.5 Period Averaging Measurements
The CR200(X) can measure the period of a signal on any single-ended analog
input channel (SE 1 - 5). The specified number of cycles are timed with a
resolution of 70 ns, making the resolution of the period measurement 70 ns
divided by the number of cycles chosen.
Cycles are counted as the input voltage transitions from less than 0.9 volts to
more than 2.1 volts. The maximum input voltage must be less than 4 volts. The
maximum frequency that can be detected is 150 kHz.
Содержание CR200
Страница 32: ...Section 2 Quickstart Tutorial 22 ...
Страница 45: ...Section 3 Overview 35 3 3 Specifications ...
Страница 46: ...Section 3 Overview 36 ...
Страница 58: ...Section 4 Sensor Support 48 ...
Страница 62: ...Section 5 Measurement and Control Peripherals 52 ...
Страница 78: ...Section 8 CR200 X Configuration 68 ...
Страница 102: ...Section 9 Programming 92 ...
Страница 138: ...Section 11 Programming Resource Library 128 ...
Страница 156: ...Section 16 Support Software 146 ...
Страница 160: ...Section 17 Care and Maintenance 150 ...
Страница 166: ...Section 18 Troubleshooting 156 18 3 3 Diagnosis and Fix Procedures 18 3 3 1 Battery Voltage Test ...
Страница 167: ...Section 18 Troubleshooting 157 18 3 3 2 Charging Circuit Test Solar Panel ...
Страница 168: ...Section 18 Troubleshooting 158 18 3 3 3 Charging Circuit Test Transformer ...
Страница 169: ...Section 18 Troubleshooting 159 18 3 3 4 Adjusting Charging Circuit Voltage ...
Страница 170: ...Section 18 Troubleshooting 160 ...
Страница 184: ...Appendix A Glossary 14 ...
Страница 190: ...Appendix B Status Table and Settings 20 ...
Страница 192: ...Appendix C Serial Port Pin Outs 22 ...
Страница 211: ......