PM 1001937 000 00
Operating manual SIRAX BT7300 / BT7350
17/28
1.8 Disposal
Device may only be disposed in a professional manner!
The disposal of devices and components may only be realised in accordance with good professional practice observing the
country-specifi c regulations. Incorrect disposal can cause environmental risks.
1.9 Return
All devices delivered to Camille Bauer Metrawatt AG shall be free of any hazardous contaminants (acids, lyes, solutions, etc.).
Use original packaging or suitable transport packaging to return the device.
Damage by returning
Damages caused by improper returning, no warranties or guarantees can be given.
2. Introduction
2.1 Purpose of this document
This document describes the current and energy meter SIRAX BT7300 and BT7350. It is intended to be used by Installation personnel, commis-
sioning engineers, Service and maintenance personnel.
Scope
This handbook is valid for all versions of the current and energy meter SIRAX BT7300 and BT7350. Some of the functions described in this
document are available only, if the necessary optional components are included in the device.
Required knowledge
A general knowledge in the field of electrical engineering is required. For assembly and installation of the device knowledge of applicable national
safety regulations and installation standard is required.
2.2 Scope of supply
•
Current and energy meter SIRAX BT7300 or BT7350 with Connection set
•
Safety instructions (ge, en, fr, it, es, nl, cz)
2.3 Further documents
The following documents are provided electronically via www.camillebauer.com:
•
Datasheet (ge, en)
•
Safety instructions (ge, en, fr, it, es, nl, cz)
•
Operating manual (ge, en)
•
Flyer current transformer program
3. Functional description
The SIRAX BT7300 and BT7350 are current transformer with energy meter functionality for monitoring 1-phase AC and DC systems up to a
maximum current of 300 AAC and 400 ADC, and up to a maximum voltage of 800 VAC and 1000 VDC. The current measurement is galvanically
separated from the measured line. With the ability to measure currents with different frequency ranges, the AC / DC current transformers are the
ideal solution for monitoring photovoltaic systems, battery charging systems, UPS systems, variable frequency drives.
4. Assembly and installation
Ensure a safe working environment during assembly, installation and maintenance work. Disconnect the power supply of the
primary conductor and secure it against unintentional reconnection.
Magnetic fields of high intensity can vary the values measured by the transformer. Avoid installation near permanent magnets,
electromagnets or iron masses that induce strong changes in the magnetic field. If there are any irregularities, we recommend
realigning or moving the transformer in the most appropriate area.
• Mounting is via screw grooves for vertical and horizontal panel mounting or via fastening elements for vertical and horizontal DIN rail moun-
ting.
• The installation of the devices is arbitrary.
• Now connect the device according to the wiring diagram.