PM 1001937 000 00
Operating manual SIRAX BT7300 / BT7350
24/28
40117
S Min
Min Apparent Power (VA)
Float (LSW first)
R/W
40118
40119
Cosρ Max
Max Cosρ
Float (LSW first)
R/W
40120
40121
Cosρ Min
Min Cosρ
Float (LSW first)
R/W
40122
40123
Frequency Max
Max Frequency (Hz)
Float (LSW first)
R/W
40124
40125
Frequency Min
Min Frequency (Hz)
Float (LSW first)
R/W
40126
40127
THD Max
Max THD
Float (LSW first)
R/W
40128
40129
THD Min
Min THD
Float (LSW first)
R/W
40130
40132
Status SW
Bit 0: flash settings error
Bit 1: flash calibration error
Bit 2: Voltage Over Range
Bit 3: Voltage Under Range
Bit 4/5: don’t care
Bit 6: Zero crossing detecting
Bit 7/8/9: don’t care
Bit 10: Energy storing error
Bit 11: Energy initialization error
Bit 12: don’t care
Bit 13: Current Over Range
Bit 14: Current Under Range
Bit 15: don’t care
Unsigned short
R
40133
V RMS SW
Voltage RMS measurement (V) swapped
Float (MSW first)
R
40134
40135
I RMS SW
Current RMS measurement (mA)
swapped
Float (MSW first)
R
40136
40137
P SW
Power measurement (W) swapped
Float (MSW first)
R
40138
40139
Q SW
Reactive Power measurement Q (VAR)
swapped
Float (MSW first)
R
40140
40141
S SW
Apparent Power measurement S (VA) swapped
Float (MSW first)
R
40142
40143
Cosρ SW
Cosρ measurement swapped
Float (MSW first)
R
40144
40145
Frequency SW
Frequency measurement (Hz) swapped
Float (MSW first)
R
40146
40147
THD SW
THD swapped
Float (MSW first)
R
40148
40149
Energy SW
Total Energy measurement (KWh)swapped
Float (MSW first)
R
40150
40151
Energy positiv SW Only positive Energy Measurement (KWh)
swapped
Float (MSW first)
R
40152
40153
Energy negativ
SW
Only negative Energy Measurement (KWh)
swapped
Float (MSW first)
R
40154
40155
V peak SW
Instantaneous Voltage Peak (V) swapped
Float (MSW first)
R/W
40156
40157
I peak SW
Instantaneous Current Peak (mA)
swapped
Float (MSW first)
R/W
40158
40159
V Max SW
Max RMS Voltage (V) swapped
Float (MSW first)
R/W
40160
40161
V Min SW
Min RMS Voltage (V) swapped
Float (MSW first)
R/W
40162