7.7 Data recording
The optional data logger provides long-term recordings of measurement progressions and events.
In addition, file based information can periodically created using the
. Such data can
be stored internally and / or securely sent to a SFTP server.
The recording is performed in endless mode (oldest data will be deleted, as soon as the associated
memory is used for more than 80%).
Group
Data type
Request
•
Mean-values versus time, predefined (5) and
user-specific (12) quantities
•
Periodic meter readings, predefined (4) and
user-specific (12) quantities
Energy
•
Mean value
logger
•
Meter logger
In form of a logbook with time information:
•
Event list: Every state transition of monitoring
functions or limit values, classified as event and
each violation of the pre-warning level of the
(optional) fault current channels
•
Alarm list: Every state transition of monitoring
functions or limit values, classified as alarm and
each violation of the alarm limits of the (optional)
fault current channels
•
Temperature alarm list: Each violation of the
limit values of the (optional) temperature
channels
Events
•
Event and alarm
list
Events will be registered in the disturbance
recorder list. By selecting the entries:
•
the course of the RMS values of all U/I
•
the wave shape of all U/I
during the disturbance will be recorded
Events
•
Disturbance
recorder
•
Security log (SYSLOG)
Service
•
Log of the
security system
7.7.1 Periodic data
Configuration of the periodic data recording
Via the settings menu the user can individually configure:
•
The averaging interval of the standard mean-values P(I+IV), P(II+III), Q(I+II), Q (III+IV), S
•
The averaging interval of up to 12 user-defined mean-values
•
The reading interval of standard meters P(I+IV), P(II+III), Q(I+II), Q (III+IV)
•
The reading interval of up to 12 user-defined meters
The recording of all mean-values and meters is started automatically on device start. The recording of the
mean-values is done when the appropriate averaging interval expires.