PM 1000162 000 14
Device handbook SINEAX AMx000
19/118
Three wire system, balanced load, current measurement via L1
AM2000 / AM3000
AM1000
Direct connection
Maximum permissible rated voltage 300V to ground (520V ph-ph)!
With current transformers
.
With current and voltage transformers
.
In case of current measurement via L2 or L3 connect the device according to the following table:
Terminals
1
3
2
5
8
Current meas. via L2
I2(k) I2(l) L2 L3 L1
Current meas. via L3
I3(k) I3(l) L3
L1
L2
By rotating the voltage connections the measurements U12, U23 and U31 will be assigned interchanged!
L1
L2
L3
N
I1
3
1
I2
4
I3
9
7
IN
PE
6
10
12
16
11
2
5
8
L1
L2
L3
5 A
(UL listed)
L1
L2
L3
N
I1
I2
I3
l
l
l
l
k
k
k
3
1
4
9
7
6
11
2
5
8
L1
L2
L3
5 A
(UL listed)
L1
L2
L3
N
I1
3
1
I2
4
I3
9
7
IN
PE
6
10
12
16
11
2
5
8
L1
L2
L3
K
k
L
l
5 A
(UL listed)
L1
L2
L3
N
I1
I2
I3
l
l
l
l
k
k
k
3
1
4
9
7
6
11
2
5
8
K
k
L
l
L1
L2
L3
5 A
(UL listed)
L1
L2
L3
N
I1
3
1
I2
4
I3
9
7
IN
PE
6
10
12
16
11
2
5
8
L1
L2
L3
K
k
L
l
5 A
(UL listed)
u
U
v
V
u
U
v
V
L1
L2
L3
N
I1
I2
I3
l
l
l
l
k
k
k
3
1
4
9
7
6
11
2
5
8
K
k
L
l
L1
L2
L3
5 A
(UL listed)
U
u
V
v
U
u
V
v