PM 1000162 000 14
Device handbook SINEAX AMx000
12/118
Symbol Meaning
Device may only be disposed of in a professional manner!
Double insulation, device of protection class 2
CE conformity mark. The device fulfills the requirements of the applicable EU
directives.
Products with this mark comply with both the Canadian (CSA) and the American
(UL) requirements.
Caution! General hazard point. Read the operating instructions.
General symbol: Input
General symbol: Output
CAT III Measurement category CAT III
5.2 Terminal assignments of the I/O extensions of AM2000/3000
Function
Option 1
Option 2
Option 3
Option 4
2 relay outputs
1.1
: 51,52,53
1.2
: 55,56,57
2.1
: 61,62,63
2.2
: 65,66,67
4.1
: 31,32,33
4.2
: 35,36,37
2 analog outputs
1.1
: 56(+), 57(-)
1.2
: 55(+), 57(-)
2.1
: 66(+), 67(-)
2.2
: 65(+), 67(-)
3.1
: 46(+), 47(-)
3.2
: 45(+), 47(-)
4.1
: 36(+), 37(-)
4.2
: 35(+), 37(-)
4 analog outputs
1.1
: 56(+), 57(-)
1.2
: 55(+), 57(-)
1.3
: 52(+), 53(-)
1.4
: 51(+), 53(-)
2.1
: 66(+), 67(-)
2.2
: 65(+), 67(-)
2.3
: 62(+), 63(-)
2.4
: 61(+), 63(-)
3.1
: 46(+), 47(-)
3.2
: 45(+), 47(-)
3.3
: 42(+), 43(-)
3.4
: 41(+), 43(-)
4.1
: 36(+), 37(-)
4.2
: 35(+), 37(-)
4.3
: 32(+), 33(-)
4.4
: 31(+), 33(-)
4 digital inputs (active)
1.1
: 51(-), 53(+)
1.2
: 52(-), 53(+)
1.3
: 55(-), 57(+)
1.4
: 56(-), 57(+)
2.1
: 61(-), 63(+)
2.2
: 62(-), 63(+)
2.3
: 65(-), 67(+)
2.4
: 66(-), 67(+)
3.1
: 41(-), 43(+)
3.2
: 42(-), 43(+)
3.3
: 45(-), 47(+)
3.4
: 46(-), 47(+)
4.1
: 31(-), 33(+)
4.2
: 32(-), 33(+)
4.3
: 35(-), 37(+)
4.4
: 36(-), 37(+)
4 digital inputs (passive)
1.1
: 51(+), 53(-)
1.2
: 52(+), 53(-)
1.3
: 55(+), 57(-)
1.4
: 56(+), 57(-)
2.1
: 61(+), 63(-)
2.2
: 62(+), 63(-)
2.3
: 65(+), 67(-)
2.4
: 66(+), 67(-)
3.1
: 41(+), 43(-)
3.2
: 42(+), 43(-)
3.3
: 45(+), 47(-)
3.4
: 46(+), 47(-)
4.1
: 31(+), 33(-)
4.2
: 32(+), 33(-)
4.3
: 35(+), 37(-)
4.4
: 36(+), 37(-)
2 temperature inputs
1.1: 52,53
1.2: 56,57
2.1: 62,63
2.2: 66,67
3.1: 42,43
3.2: 46,47
4.1: 32,33
4.2: 36,37