13
5.3 Measuring output
Output variable I
A
:
Load-independent DC current,
proportional to the input angle
Standard ranges:
4…20 mA, 2 wire connection
Setting time:
< 5 ms
External resistance:
R
ext
max. [kΩ] =
H [V] – 12 V
I
A
[mA]
H= Power supply
I
A
= Output signal end value
5.4 Accuracy
Reference value:
Measuring range
Basic accuracy:
Limit of error ≤ 0.5 % with linear characteristic
5.5 Installation data
Housing (main part):
Steel
Finish QPQ (nitro-carbonated)
Rear (cover):
Metal
(aluminium)
Cable glands:
Metal
Mounting position:
Any
Weight:
Approx. 2.9 kg [83.591 oz]
Permissible static
load on the shaft:
Max. 1000 N (radial)
Max. 500 N (axial)
If subjected to vibration the shaft load should
be as low as possible to ensure optimum life
of the bearing
5.6 Regulations
Spurious rodation:
EN 61000-6-3
Immunity:
EN 61000-6-2
Common-mode voltage:
100 V AC, CATII
Test voltage:
750 V DC, 1 min.
all electrical connections against housing
Housing protection:
IP 50 acc. to EN 60529
5.7 Environmental conditions
Climatic rating:
Standard version
Temperature – 25 to + 70 °C [-13...+158 °F]
Annual mean relative humidity
≤ 90%
or
Version with improved climatic
rating
Temperature – 40
to + 70 °C [-40...+158 °F]
Annual mean relative humditiy
≤ 95%
Ex version
Maximum
Power
Temperature class
Pi
T6
T5
T4
1000 mW
40 °C
[104 °F]
55 °C
[131 °F]
75 °C
[167 °F]
900 mW
44 °C
[111.2 °F]
59 °C
[138.2 °F]
75 °C
[167 °F]
800 mW
49 °C
[120.2 °F]
64 °C
[147.2 °F]
75 °C
[167 °F]
700 mW
54 °C
[129.2 °F]
69 °C
[156.2 °F]
75 °C
[167 °F]
660 mW
56 °C
[132.8 °F]
71 °C
[159.8 °F]
75 °C
[167 °F]
The minimum permissible ambient
temperature is -40 degrees.
Transportation and
storage temperature:
– 40 to 80 °C [-40...+176 °F]
Altitude:
2000 m max.
Permissible vibration:
(without addit. gear):
0…200 Hz,
10 g continuous, 15 g for 2 h
200…500 Hz,
5 g continuous, 10 g for 2 h
Shock: 3
×
50 g every 10 impulses
in all 3 axes
5.8 Operation in potentially explosive environments:
Gas explosion
prevention:
Labeling:
Ex ia IIC T6 Gb
Conform to standard:
ATEX:
EN 60079-0:2012
EN 60079-11:2012
Type of protection:
ia
Temperature class:
T6
Group according to
EN 60079-00:2012:
II
• The operation in other explosive atmospheres is not permissible.
• It is not permissible to make any alteration to equipment that is used in
potentially explosive environments.
Devices with explosion prevention must be operated
in accordance with the stipulations of the operating
instructions. The relevant laws, regulations and stan
-
dards for the planned application must be observed.
6. Mounting
The six versions of the transmitter differ in their mechanical design.
Two
of
them are intended for mounting
directly
on the device being measured. The
others are equipped with a
mounting bracket
or a
flange
. The relationship
between the three types of mounting, or more precisely the corresponding
cut-out diagrams and the different versions of the transmitter can be seen
from Table.
Transmitter
versions
Drilling and cut-out diagrams
for mounting transmitters …
…
directly
82
±0.2
62 H8
6.5
120º
[3.228]
[2.441]
[0.256]
…
with a bracket
71
±0.2
90
±0.2
9
[2.795]
[0.354]
[3.543]
…
with a flange
9
130
±0.2
110 H7
[5.118]
[4.330]
[0.354]
Three
M6
screws are needed for the
“directly”
mounted versions and four
M8
nuts and bolts for these
“with a bracket”
or
“with a flange”
. The screws,
respectively nuts and bolts are not supplied, because the required length
varies according to the thickness of the mounting surface.
When deciding where to install the transmitter (measuring loca-
tion), take care that the
“ambient conditions”
given in Section
“5. Technical data” are
not exceeded.
Make the cut-out or drill the holes in the item onto which the transmitter is
to be mounted according to the
corresponding
drilling and cut-out diagram
given in Table 1 and then fit the transmitter.