The Calix E7-20 ground system can be connected to a Common Bonding Network (CBN) or
Isolated Bonding Network (IBN).
Note:
For environments that employ an IBN scheme, the low voltage and frame grounds on
the E7-20 shelf are isolated from the input power DC-return.
The installation kit includes a 12-foot ground cable, plus hardware to attach it to the E7-20
frame ground. The grounding terminal for anti-static wrist strap connection is located on the
left side of the chassis.
!
ESD!ALERT!
!!Beware!of!electrostatic!discharge.!Follow!standard!ESD!
precautions.!Always!wear!a!grounded!ESD!wristband!to!avoid!damaging!the!
electronic!equipment.!
To!ground!the!E7=20!chassis!
1.!
Get the ground cable and supplied hardware (pair of 10-32 Keps nuts and washers) from
the installation kit.
2.!
Connect the ground cable to the E7-20 chassis as follows:
a.
!
Install (2) star washers and then the ground cable's 2-hole lug onto the dual-post
Frame Ground terminal (located on the rear of the chassis).
b.
!
Install (2) 10-32 Keps nuts onto the Frame Ground posts to secure the lug in place.
Tighten to 27 in-lbs of torque.