Charging process: Automatic
Automatic
switching mains:
Main charging
process:
Post charging phase:
Holding charge:
OFF when battery voltage reached
14.4 V
Ten hours constant 14.4 V in the
case of gel batteries.
Four hours constant 14.4 V in the
case of liquid batteries.
Holding charge, constant at 13.8 V
Temperature
dependent control:
(optional)
Mains
Solar
Booster
The values of the automatic switching refer to a battery
temperature of 20° C. When using a temperature sensor at
the battery II, these values vary as a function of the
battery temperature.
High temperature > Lowering of the threshold values.
Low temperature > higher threshold values.
Charging current
solar:
max. 12 A, 2 solar panels each of 85 W
Voltage solar:
14.4 V / 13.8 V
Charging current
booster:
10 A
Voltage booster:
14.2 V
Low-voltage
monitoring:
OFF at 10.8 V
ON at 12.5 V
Application:
Parallel operation, buffer operation, general charging
operation
Temperature:
Ambient temperature of –25 °C to +35 °C. During
operation, the housing may heat up to approx. 75 °C.
Cooling:
By convection
Implementation:
According to Association of German Electrotechnical
Engineers regulations and the provisions of the Instrument
Safety Act.
Test labelling: