Technical specifications

- Electric supply:

24 V (+10 % / -5 %) (ac) - 50 Hz - 1 W 

- Data transmission:

M-Bus protocol on BUS RS-485 (default)

MODBUS protocol on BUS RS-485 (on request) 

- Tamper-proof protection
- Advanced control software
- Conformity:

Directive 2014/32/EU EN 1434 (MI004)

Standard installation

Product range

7507 series 

Heat meter with threaded connection 

 size 1/2”–1 1/2”

7507 series 

Heat meter with flanged connection 

 size DN 50–DN 200

Code 755010 

TOUCH-screen controller 

Code 750450 

EASY datalogger

Code 750350 

EASY TELE datalogger

7558 series 

Additional options

Function

CONTECA

® 

EASY ULTRA  is an 

ultrasonic heat meter

, especially 

suited to measuring thermal energy consumption in residential 

buildings; thanks to a double memory register, it can also meter 

energy in both 

heating

 and 

cooling

 modes (option code 755810).

The device comprises an electronic calculator unit, an ultrasonic 

flow meter and two temperature probes. The CONTECA

® 

EASY 

ULTRA meter is extremely simple to install and requires no special 

maintenance. 

The flow is measured using the two-way ultrasound technique, based 

on the transit time method. As it has no moving parts, the device 

is therefore not very susceptible to build-up issues and offers an 

extremely low pressure drop.

The CONTECA

® 

EASY ULTRA meter is equipped with an 

8-digit LCD 

display

 that can be switched on with a key. This display enables easy 

reading of both energy consumption values and technical data, for 

appliance operating status evaluation and data logging.

The CONTECA

® 

EASY ULTRA meter is able to acquire up to 4 

additional pulse inputs and two additional alarm-status digital inputs, 
and is equipped for centralised teletransmission (max. 250 users) in 
M-Bus protocol, on the RS-485 network. The device also supports
MODBUS RTU protocol.

CALEFFI

RS485

EASY

CO

N

TECA

EASY

        M07 1259

07185865

1

CONTECA

®

 EASY ULTRA direct heat meter 

MID Directive - Bus RS-485 transmission

7507 series

Содержание CONTECA EASY ULTRA

Страница 1: ...culator unit an ultrasonic flow meter and two temperature probes The CONTECA EASY ULTRA meter is extremely simple to install and requires no special maintenance The flow is measured using the two way...

Страница 2: ...h l h l h C kWh PN Qp Qi Qs m m C K C 90 preferably horizontal class OA OC in accordance with EN1434 2 see table 1 and 2 see table 1 and 2 see table 1 and 2 lithium battery life 12 years p Code The CO...

Страница 3: ...e while the return probe blue label should be on the return pipe At the end of the installation process the main heat meter components electronics unit temperature probes and volume meter should under...

Страница 4: ...protect the volume meter By observing the instant flow rate and flow return temperature difference values significantly lower flow rate compared to the nominal value and significantly higher temperat...

Страница 5: ...duration 120 ms Vmax 24 V dc 50 mA 755882 2 3 OUT 1 Open collector pulse output for HEATING units GND 2 duration 120 ms Vmax 24 V dc 50 mA 755881 755882 4 NOT used 5 6 IN 4 fourth pulse input generic...

Страница 6: ...input blue wire white wire Enery pulse outputs codes 755881 755882 2 3 Remote heating units totaliser output kWh OC type 1 2 Remote cooling units totaliser output kWh OC type These outputs can be conn...

Страница 7: ...ption with optional code 755826 2nd DCW pulse consumption 3rd pulse consumption with optional code 755825 Flow rate Power Flow temperature Return temperature Temperature difference DHW flow rate with...

Страница 8: ...change K V volume change l V N P where N number of pulses P single pulse value per litre Operating specifications 1 In order to protect against spurious measurements or undesired metering the meterin...

Страница 9: ...ass the thread through the hole on the probe and the pocket and twist it E Wind the thread as illustrated in the figure so that once lead sealing is complete the cap cannot be unscrewed without breaki...

Страница 10: ...bob D Pass the thread through the hole on the probe and the pocket and twist it E Wind the thread as illustrated in the figure so that once lead sealing is complete the cap cannot be unscrewed without...

Страница 11: ...SY RS485 EASY CONTECA EASY RS485 EASY CONTECA EASY RS485 EASY CONTECA EASY RS485 EASY CONTECA EASY RS485 EASY CONTECA EASY 11 M Bus M Bus Master 230 V ac 755058 M Bus RS 485 slave converter Used to ad...

Страница 12: ...ied out by the user removed Maximum number of users 250 Datalogger specifications Electric supply 24 V dc 10 24 V ac 3 W 2 Ethernet outputs ETH1 PoE ETH2 Working temperature range 0 50 C Mounting 35 m...

Страница 13: ...755881 Acquisition board Terminals 2 3 Heating units 7507 Terminals 2 3 Heating units Terminals 1 2 Cooling units CALEFFI ENERGY kWh 2 6 0 V HEATING UNITS output COOLING UNITS output GND 1 2 3 4 5 6...

Страница 14: ...20030 PULSE MONITOR Pulse logger Electric supply lithium battery 6 digit display with user key Daily data saving Tamper proof seal and sensor Enables acquisition of a pulse output from the heat meter...

Страница 15: ...ues with the aim of providing the exact domestic hot water consumption figure Code 755890 Electronic 8 digit LCD totaliser equipped with cover plate for three slot recessed electric box Lithium batter...

Страница 16: ...ULTRA 7507 series CONTECA EASY ULTRA heat meters in the 7507 series conform to the requirements of directive 2014 32 EU better known as MID acronym for Measuring Instrument Directive Production proce...