Test Instructions

The 7507 series meter is equipped with a fast output test 
device located inside the plastic container.
In order to access this, remove the seal and take out the 
fixing screws.

On the right-hand side of the back of the card (fig. 1) there is 
a key offering access to the technical manual.

An input pulse can be simulated by connecting pins 11 - 12 (fig. 3).
The maximum input pulse frequency is 1 Hz. 

After pressing the key on the back of the card, pressing 
the key on the front allows you to scroll through the various 
screens.

The energy increases according to the following equation: 

D

E

 = 

κ⋅

D

T

D

V

0,2777698

10

-3 

[Wh]

The probes, which absolutely cannot be separated from the electronics circuit, 
may be inserted in a thermostatic bath, observing the temperature range of 
10–90 °C and taking account of a 

D

T between 3–80 K

(fig. 1)

(fig. 2)

(fig. 3)

ELECTRONICS BOX REAR PART

CABLE ROUTE

TEAR-PROOF CABLE CLIP

A

A

A

A

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

24 V (ac)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

RS48

5

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Cooling unit

s

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

digital inpu

t

A

B

Heating units

4

th

 pulse inpu

t

3

rd

 pulse inpu

t

pulse input

blue wire

white wire

 Wh

8

κ

 = thermal coefficient [kJ/m

3

K]

D

T

 = temperature change [K]

 

D

V

 = volume change [ l ]

D

V = N

where  N  = number of pulses
 

P  = single pulse value per litre

Operating specifications

1)   In order to protect against spurious measurements or undesired metering, the metering control software makes the processing of consumption 

subordinate to a specific flow temperature value (FT).

The 

heating metering cycle is activated for FT > 22 °C

 (factory setting).

The 

cooling units cycle is activated for FT < 15 °C

 (factory setting, with optional accessory code 755810).

On request, the setpoint values can be changed by technical personnel.

2)  The software governing metering moreover has consumption processing subordinate to 

  minimum temperature difference

 in order to provide further protection against spurious measurements or minimum metering due to 

temperature tolerances. At the time of factory setting, 

a dead band of 0,4 K

 (factory setting) is therefore defined.

3) The software governing metering also requires 

installation of the flow rate meter on the return pipe

.

   On request and further to the action of technical personnel, the configuration setpoint can be adapted in order to install the meter on the flow 

pipe.

Содержание CONTECA EASY ULTRA

Страница 1: ...culator unit an ultrasonic flow meter and two temperature probes The CONTECA EASY ULTRA meter is extremely simple to install and requires no special maintenance The flow is measured using the two way...

Страница 2: ...h l h l h C kWh PN Qp Qi Qs m m C K C 90 preferably horizontal class OA OC in accordance with EN1434 2 see table 1 and 2 see table 1 and 2 see table 1 and 2 lithium battery life 12 years p Code The CO...

Страница 3: ...e while the return probe blue label should be on the return pipe At the end of the installation process the main heat meter components electronics unit temperature probes and volume meter should under...

Страница 4: ...protect the volume meter By observing the instant flow rate and flow return temperature difference values significantly lower flow rate compared to the nominal value and significantly higher temperat...

Страница 5: ...duration 120 ms Vmax 24 V dc 50 mA 755882 2 3 OUT 1 Open collector pulse output for HEATING units GND 2 duration 120 ms Vmax 24 V dc 50 mA 755881 755882 4 NOT used 5 6 IN 4 fourth pulse input generic...

Страница 6: ...input blue wire white wire Enery pulse outputs codes 755881 755882 2 3 Remote heating units totaliser output kWh OC type 1 2 Remote cooling units totaliser output kWh OC type These outputs can be conn...

Страница 7: ...ption with optional code 755826 2nd DCW pulse consumption 3rd pulse consumption with optional code 755825 Flow rate Power Flow temperature Return temperature Temperature difference DHW flow rate with...

Страница 8: ...change K V volume change l V N P where N number of pulses P single pulse value per litre Operating specifications 1 In order to protect against spurious measurements or undesired metering the meterin...

Страница 9: ...ass the thread through the hole on the probe and the pocket and twist it E Wind the thread as illustrated in the figure so that once lead sealing is complete the cap cannot be unscrewed without breaki...

Страница 10: ...bob D Pass the thread through the hole on the probe and the pocket and twist it E Wind the thread as illustrated in the figure so that once lead sealing is complete the cap cannot be unscrewed without...

Страница 11: ...SY RS485 EASY CONTECA EASY RS485 EASY CONTECA EASY RS485 EASY CONTECA EASY RS485 EASY CONTECA EASY RS485 EASY CONTECA EASY 11 M Bus M Bus Master 230 V ac 755058 M Bus RS 485 slave converter Used to ad...

Страница 12: ...ied out by the user removed Maximum number of users 250 Datalogger specifications Electric supply 24 V dc 10 24 V ac 3 W 2 Ethernet outputs ETH1 PoE ETH2 Working temperature range 0 50 C Mounting 35 m...

Страница 13: ...755881 Acquisition board Terminals 2 3 Heating units 7507 Terminals 2 3 Heating units Terminals 1 2 Cooling units CALEFFI ENERGY kWh 2 6 0 V HEATING UNITS output COOLING UNITS output GND 1 2 3 4 5 6...

Страница 14: ...20030 PULSE MONITOR Pulse logger Electric supply lithium battery 6 digit display with user key Daily data saving Tamper proof seal and sensor Enables acquisition of a pulse output from the heat meter...

Страница 15: ...ues with the aim of providing the exact domestic hot water consumption figure Code 755890 Electronic 8 digit LCD totaliser equipped with cover plate for three slot recessed electric box Lithium batter...

Страница 16: ...ULTRA 7507 series CONTECA EASY ULTRA heat meters in the 7507 series conform to the requirements of directive 2014 32 EU better known as MID acronym for Measuring Instrument Directive Production proce...

Отзывы: