background image

SAT102

heat interface unit

5

User Interface

The user interface, built into the PCB, consists of the following
devices.

Indicator LED

The various functions and faults are signalled by either 
flashing or permanent illumination of the LEDs.

Energy meter installation

The HIU is designed to include a compact energy meter with
integral return probe, with 1” threaded connections and 130 mm
overall body length.

Before carrying out any maintenance, repair or part replacement
work, proceed as follows:

turn off the electric supply

close the isolation valves

drain the HIU using the drain cocks provided

remove the spool piece (6)

remove the blanking plug

install the flow probe in the ¼    ” pocket provided (5)

install the flow meter on the return pipe.

Please refer to the heat meter technical data sheets for further
information.

Electronic controller

Operating Principle

All functions offered by SATK102 HIUs are controlled by a digital
controller.

The  controller  is  factory  set  with  different  parameters  and
settings depending on the model.

There are a number of specific DIP SWITCHES on the controller
circuit board; the way these are configured will determine the
functions enabled.

Automatic controller function

Reset mixing/modulating valve to zero

Immediately after the power supply has been switched on, the
position of the mixing/modulating valve is reset to zero.

Pump anti-clog

When the pump is not in use, it is powered on for a period of 5
seconds every 24 hours.

Mixing valve/modulating valve anti-clog

The anti-clogging cycle for the mixing/modulating valve is run
every 24 hours.

Trimmers for set point settings

These allow the temperature of the domestic hot water cycle
to be set and their values will be displayed on the LCD display.

LCD display

The set domestic hot water temperature and error codes are
displayed.

Dip switches

Dip switches allow the setup of the various models and
optional functions to be activated.

Default settings:

3

4

5

6

ON

2

1

Light grey: Factory set - do not alter

May be changed to activate optional functions - see page 6

88

Domestic water temperature

ON

Electric supply 230 V (ac)

DHW

Domestic hot water ON

FAULT

Fault detected

6 5 4

2

3

1

Содержание altecnic SATK102

Страница 1: ...SATK102 heat interface unit Installation Operation Maintenance Instructions...

Страница 2: ...e suitable provision for ltering and treating the water before it enters the device in accordance with current legislation Failure to do so may result the HIU becoming damaged or working incorrectly 8...

Страница 3: ...o be removed always disconnect the earth connection after disconnecting the electric supply Check that the earth connection has been made to the highest of standards under current legislation 6 Electr...

Страница 4: ...ntroller 3 Pump SATK1020X SATK1020X HE 4 DHW temperature sensor and strainer 5 Flow temperature pocket probe 6 Energy meter spool piece 7 Plate heat exchanger 8 Flow switch 9 Modulating primary contro...

Страница 5: ...or blocks mobile dividing panels or any masonry walls other than those indicated a preliminary static test must be carried out on the support system Isolation Valves Depending on the speci cation orde...

Страница 6: ...eters and settings depending on the model There are a number of speci c DIP SWITCHES on the controller circuit board the way these are con gured will determine the functions enabled Automatic controll...

Страница 7: ...turned off Domestic water generation Domestic water preheating function The function is enabled by setting dip switch 5 to the ON position During periods when the domestic water cycle is not used if t...

Страница 8: ...ct the probe cable lightly folding the tab C and extracting the connector Unscrew the probe Fit the new probe Re t the connector respecting the only possible way it can be inserted Replacing the valve...

Страница 9: ...if necessary Screw the cartridge back into position Re position the ow sensor When carrying out maintenance on the electrical part for the connections follow the diagram on page 8 After concluding mai...

Страница 10: ...4 5 6 1 2 3 4 5 7 6 L N Electric supply 230 V ac 10 50 Hz 1 DHW temperature probe 2 3 4 5 6 7 DHW flow meter DHW modulating valve actuator Earth Pump Fuse Power Supply 230 V ac X X X X X X X X X X X X...

Страница 11: ...d temperature DHW led on domestic water cycle temperature set point too low increase set point HIU strainer clogged call quali ed personnel to have it serviced exchanger partly clogged call quali ed p...

Страница 12: ...K102 heat interface unit Altecnic Ltd Mustang Drive Stafford Staffordshire ST16 1GW T 44 0 1785 218200 E sales altecnic co uk Registered in England No 2095101 altecnic co uk IOM 069 09 12 16 E O E Not...