SAT102

heat interface unit

6

Operating Cycles

Domestic water generation

When the domestic hot water is activated by a water outlet (user’s tap)
being opened, detected by the domestic water flow meter, the electronic
controller regulates the modulating valve opening so as to adjust the
temperature detected to the selected set point value.

At the end of the drawing-off procedure, the modulating valve is fully
closed.

The active domestic water cycle is signalled by the yellow DHW LED
which comes on.

The domestic water temperature can be set using trimmer P1 and is
shown on the LCD display.

Optional functions

When activating or de-activating the optional functions the electricity
supply must always be turned off.

Domestic water generation

Domestic water preheating function

The function is enabled by setting dip switch 5 to the ON position.

During periods when the domestic water cycle is not used, if the

DHW  probe  detects  a  temperature  10°C  below  the  SET  value,  the
controller partially opens the domestic water modulating valve for the
time required (max. 5 mins) to bring the temperature detected up to a
value 5˚C below the set point value.

The  domestic  water  preheating function  is  signalled  by  the flashing
yellow DHW LED.

Safety and alarms

Error codes associated with faults signalled by the lighting up of the
FAULT LED are also shown on the display.

Domestic water probe fault

Error code: 6

Removing the fault

Normal operation will be restored once the probe has been replaced.

Incorrect switch setting

Error code: 79

Removing the fault

Restore correct switch setting - see page 5

79

48

P2

P1

5

ON

48

6

Содержание altecnic SATK102

Страница 1: ...SATK102 heat interface unit Installation Operation Maintenance Instructions...

Страница 2: ...e suitable provision for ltering and treating the water before it enters the device in accordance with current legislation Failure to do so may result the HIU becoming damaged or working incorrectly 8...

Страница 3: ...o be removed always disconnect the earth connection after disconnecting the electric supply Check that the earth connection has been made to the highest of standards under current legislation 6 Electr...

Страница 4: ...ntroller 3 Pump SATK1020X SATK1020X HE 4 DHW temperature sensor and strainer 5 Flow temperature pocket probe 6 Energy meter spool piece 7 Plate heat exchanger 8 Flow switch 9 Modulating primary contro...

Страница 5: ...or blocks mobile dividing panels or any masonry walls other than those indicated a preliminary static test must be carried out on the support system Isolation Valves Depending on the speci cation orde...

Страница 6: ...eters and settings depending on the model There are a number of speci c DIP SWITCHES on the controller circuit board the way these are con gured will determine the functions enabled Automatic controll...

Страница 7: ...turned off Domestic water generation Domestic water preheating function The function is enabled by setting dip switch 5 to the ON position During periods when the domestic water cycle is not used if t...

Страница 8: ...ct the probe cable lightly folding the tab C and extracting the connector Unscrew the probe Fit the new probe Re t the connector respecting the only possible way it can be inserted Replacing the valve...

Страница 9: ...if necessary Screw the cartridge back into position Re position the ow sensor When carrying out maintenance on the electrical part for the connections follow the diagram on page 8 After concluding mai...

Страница 10: ...4 5 6 1 2 3 4 5 7 6 L N Electric supply 230 V ac 10 50 Hz 1 DHW temperature probe 2 3 4 5 6 7 DHW flow meter DHW modulating valve actuator Earth Pump Fuse Power Supply 230 V ac X X X X X X X X X X X X...

Страница 11: ...d temperature DHW led on domestic water cycle temperature set point too low increase set point HIU strainer clogged call quali ed personnel to have it serviced exchanger partly clogged call quali ed p...

Страница 12: ...K102 heat interface unit Altecnic Ltd Mustang Drive Stafford Staffordshire ST16 1GW T 44 0 1785 218200 E sales altecnic co uk Registered in England No 2095101 altecnic co uk IOM 069 09 12 16 E O E Not...

Отзывы: