SAT102

heat interface unit

10

Fault Finding

Fault

Indications

Possible Cause of Fault

Operations to be Performed

The water is not

heating

 DHW LED on

primary circuit isolating valve closed

open the isolating valve

modulating valve actuator connector disconnected

re-connect actuator connector

modulating valve actuator disconnected from valve body

re-connect actuator

modulating valve actuator faulty

call qualified personnel to have it replaced

clogged strainer and/or heat exchanger

call qualified personnel to have it replaced

presence of air in the system

vent the system

electronic controller not working

call qualified personnel to have it replaced

valve obturator blocked in closed position

call qualified personnel to have it replaced

centralised system not working

contact person in charge of system

FAULT led lit + error

code 6 active

DHW temperature probe disconnected

re-connect probe

DHW temperature probe faulty

call qualified personnel to have it replaced

FAULT led lit + error

code 79 active

incorrect dip switch setting

restore correct switch setting

DHW Led off

DHW priority flow meter disconnected

re-connect flow meter

DHW priority flow meter faulty

call qualified personnel to have it replaced

electronic controller not working

call qualified personnel to have it replaced

all LEDs are off

electricity power supply switched off

switch on electricity supply

protection fuse burnt out

call qualified personnel to have it replaced

electronic controller not working

call qualified personnel to have it replaced

The water is hot but

does not reach the

desired temperature

DHW led on

domestic water cycle temperature set point too low

increase set point

HIU strainer clogged

call qualified personnel to have it serviced

exchanger partly clogged

call qualified personnel to have it serviced

modulating valve actuator faulty

call qualified personnel to have it replaced

valve obturator blocked in intermediate position

call qualified personnel to have it replaced

modulating valve actuator connector disconnected

re-connect actuator connector

excessive demand for DHW

decrease demand

electronic controller not working

call qualified personnel to have it replaced

centralised system temperature insufficient

contact person in charge of system

primary circuit flow rate insufficient

contact person in charge of system

The hot water

temperature is too

high

DHW led on

domestic water cycle temperature set point too high

decrease set point

modulating valve actuator faulty

call qualified personnel to have it replaced

valve obturator blocked in intermediate or open position

call qualified personnel to have it replaced

electronic controller not working

call qualified personnel to have it replaced

Hot water flow rate

is insufficient

DHW led on

HIU strainer clogged

call qualified personnel to have it replaced

domestic water system shut-off valves partly open

open the valves

centralised domestic circuit cold water flow rate insufficient

call qualified personnel to have it serviced

The is no hot water

flow

DHW led off

possible domestic water system shut-off valves closed

open the valves

no cold water in centralised domestic circuit

call qualified personnel to have it serviced

HIU strainer completely clogged

call qualified personnel to have it serviced

heat exchanger completely blocked

call qualified personnel to have it serviced

Содержание altecnic SATK102

Страница 1: ...SATK102 heat interface unit Installation Operation Maintenance Instructions...

Страница 2: ...e suitable provision for ltering and treating the water before it enters the device in accordance with current legislation Failure to do so may result the HIU becoming damaged or working incorrectly 8...

Страница 3: ...o be removed always disconnect the earth connection after disconnecting the electric supply Check that the earth connection has been made to the highest of standards under current legislation 6 Electr...

Страница 4: ...ntroller 3 Pump SATK1020X SATK1020X HE 4 DHW temperature sensor and strainer 5 Flow temperature pocket probe 6 Energy meter spool piece 7 Plate heat exchanger 8 Flow switch 9 Modulating primary contro...

Страница 5: ...or blocks mobile dividing panels or any masonry walls other than those indicated a preliminary static test must be carried out on the support system Isolation Valves Depending on the speci cation orde...

Страница 6: ...eters and settings depending on the model There are a number of speci c DIP SWITCHES on the controller circuit board the way these are con gured will determine the functions enabled Automatic controll...

Страница 7: ...turned off Domestic water generation Domestic water preheating function The function is enabled by setting dip switch 5 to the ON position During periods when the domestic water cycle is not used if t...

Страница 8: ...ct the probe cable lightly folding the tab C and extracting the connector Unscrew the probe Fit the new probe Re t the connector respecting the only possible way it can be inserted Replacing the valve...

Страница 9: ...if necessary Screw the cartridge back into position Re position the ow sensor When carrying out maintenance on the electrical part for the connections follow the diagram on page 8 After concluding mai...

Страница 10: ...4 5 6 1 2 3 4 5 7 6 L N Electric supply 230 V ac 10 50 Hz 1 DHW temperature probe 2 3 4 5 6 7 DHW flow meter DHW modulating valve actuator Earth Pump Fuse Power Supply 230 V ac X X X X X X X X X X X X...

Страница 11: ...d temperature DHW led on domestic water cycle temperature set point too low increase set point HIU strainer clogged call quali ed personnel to have it serviced exchanger partly clogged call quali ed p...

Страница 12: ...K102 heat interface unit Altecnic Ltd Mustang Drive Stafford Staffordshire ST16 1GW T 44 0 1785 218200 E sales altecnic co uk Registered in England No 2095101 altecnic co uk IOM 069 09 12 16 E O E Not...

Отзывы: