SAT102

heat interface unit

1

These instructions must be read and understood
before installing and maintaining the HIU.
CAUTION! FAILURE TO FOLLOW THESE
INSTRUCTIONS COULD RESULT IN A SAFETY
HAZARD!

1

The device must be installed, commissioned and 
maintained by qualified technical personnel in accordance 
with national regulations and/or relevant local 
requirements.

2

If the device is not installed, commissioned and maintained
correctly in accordance with the instructions provided in 
this manual, it may not work correctly and may endanger 
the user.

3

Flush the pipework thoroughly before installing the HIU to 
remove any particles, rust, incrustations, limescale, welding
slag and any other contaminants.        
The water circuits must be clean and free from debris.

4

Make sure that all connection fittings are watertight.

5

When connecting water pipes, make sure that threaded 
connections are not mechanically overstressed. Over time 
this may result in breakage, causing water damage and/or 
personal injury.

6

Water temperatures higher than 50˚C may cause severe 
burns. When installing, commissioning and maintaining the
device, take the necessary precautions so that these 
temperatures will not be hazardous for people.

7

In the case of particularly hard or impure water, there must
be suitable provision for filtering and treating the water 
before it enters the device, in accordance with current 
legislation. Failure to do so may result the HIU becoming 
damaged or working incorrectly.

8

Any use of the HIU other than it’s intended use is 
prohibited

Product Range

SATK10253

40 kW plate heater exchanger.

SATK10203

40 kW plate heater exchanger and primary 
pump.

SATK10203HE

40 kW plate heater exchanger and high 
efficiency primary pump.

SATK10254

70 kW plate heater exchanger.

SATK10204

70 kW plate heater exchanger and primary 
pump.

SATK10204HE

70 kW plate heater exchanger and high 
efficiency primary pump.

SATK10255

80 kW plate heater exchanger.

SATK10205

80 kW plate heater exchanger and primary 
pump.

SATK10205HE

80 kW plate heater exchanger and high 
efficiency primary pump.

Safety Instructions

SATK102

Function

SATK102 Heat Interface Units (HIU) control the domestic hot
water generation in an individual apartment within a centralised
boiler or district heating system.

Wall mounted unit.

NOTE:

Due  to  the  specification  ordered,  or  the  country  of

destination, the actual unit may differ from those shown.

C

ontent

Function and product range

1

Safety instructions

1

Technical specification

2

Dimensions and components

3

Installation

4

Filling the primary heating system

4

System start up

4

Energy meter installation

5

Electronic controller

5

Dip switch settings

5

Safety and alarms

6

Maintenance

7

Electric connections

9

Trouble shooting and solution

10

WARNING

Содержание altecnic SATK102

Страница 1: ...SATK102 heat interface unit Installation Operation Maintenance Instructions...

Страница 2: ...e suitable provision for ltering and treating the water before it enters the device in accordance with current legislation Failure to do so may result the HIU becoming damaged or working incorrectly 8...

Страница 3: ...o be removed always disconnect the earth connection after disconnecting the electric supply Check that the earth connection has been made to the highest of standards under current legislation 6 Electr...

Страница 4: ...ntroller 3 Pump SATK1020X SATK1020X HE 4 DHW temperature sensor and strainer 5 Flow temperature pocket probe 6 Energy meter spool piece 7 Plate heat exchanger 8 Flow switch 9 Modulating primary contro...

Страница 5: ...or blocks mobile dividing panels or any masonry walls other than those indicated a preliminary static test must be carried out on the support system Isolation Valves Depending on the speci cation orde...

Страница 6: ...eters and settings depending on the model There are a number of speci c DIP SWITCHES on the controller circuit board the way these are con gured will determine the functions enabled Automatic controll...

Страница 7: ...turned off Domestic water generation Domestic water preheating function The function is enabled by setting dip switch 5 to the ON position During periods when the domestic water cycle is not used if t...

Страница 8: ...ct the probe cable lightly folding the tab C and extracting the connector Unscrew the probe Fit the new probe Re t the connector respecting the only possible way it can be inserted Replacing the valve...

Страница 9: ...if necessary Screw the cartridge back into position Re position the ow sensor When carrying out maintenance on the electrical part for the connections follow the diagram on page 8 After concluding mai...

Страница 10: ...4 5 6 1 2 3 4 5 7 6 L N Electric supply 230 V ac 10 50 Hz 1 DHW temperature probe 2 3 4 5 6 7 DHW flow meter DHW modulating valve actuator Earth Pump Fuse Power Supply 230 V ac X X X X X X X X X X X X...

Страница 11: ...d temperature DHW led on domestic water cycle temperature set point too low increase set point HIU strainer clogged call quali ed personnel to have it serviced exchanger partly clogged call quali ed p...

Страница 12: ...K102 heat interface unit Altecnic Ltd Mustang Drive Stafford Staffordshire ST16 1GW T 44 0 1785 218200 E sales altecnic co uk Registered in England No 2095101 altecnic co uk IOM 069 09 12 16 E O E Not...

Отзывы: