Document type:
Title:
Revision date:
Revision:
User's Manual (MUT)
A3486 3Phase 400Vac to 2x2kW/1x4kW 48Vdc
08/10/2007
10
NPO:
Filename:
Number of pages:
Page:
00120/04:A3486.MUTx/10 A3486_REV10.DOC
35
29
HVSync
allows to readout the status of the 625KHz EASY BUS clock
signal provided by the A1676A
If
HVSync = Fail
the 625KHz signal is generated by the
board itself.
StatusIn
allows to readout the back panel STATUS IN signal.
If
StatusIn = Fail
all the channels are turned OFF.
Tracking
allows to readout the module operating mode selected via
front panel switch.
SerNum
allows to readout the module serial number.
RemBdName
allows to readout the module name.
Table 4.2 – CH1..2 Parameters (output channel parameters)
Name Dir
Sign
ValType
Min
Max Res
UM
OnStr
OffStr
Name SET
UNSIGNED
STRING
Temp MON
SIGNED NUMERIC
0 70 1
CELSIUS
Status
MON UNSIGNED
STATUS
0
0
0
---
Pw
SET
UNSIGNED
ON_OFF
On
Off
Trip
SET
UNSIGNED
NUMERIC
0.0
2.0
0.1 SEC
VCon
MON UNSIGNED
NUMERIC
0.0
55.0
0.1 VOLT
SVMax
SET
UNSIGNED
NUMERIC
44.0 52.0
0.1
VOLT
VMon
MON UNSIGNED
NUMERIC
0.0
52.0
0.1
VOLT
GlbOffEn SET
UNSIGNED
ON_OFF
En
Dis
GlbOnEn SET
UNSIGNED
ON_OFF
En
Dis
RemIlk MON
UNSIGNED
ON_OFF
Yes
No
V0Set
SET
UNSIGNED
NUMERIC
44.0 52.0
0.1
VOLT
IMon
MON UNSIGNED
NUMERIC
00.0 40.0
0.1 AMPERE
I0Set
SET
UNSIGNED
NUMERIC
00.0 40.0
0.1 AMPERE
IntFail MON
UNSIGNED
ON_OFF
Yes
No
MaxDrop MON UNSIGNED ON_OFF
Yes No
Name
allows to assign a symbolic name to the channel
Temp
allows to readout the Temperature value.
If
Temp > 70°C
the channel is turned OFF.
Status
allows to readout the channel status value.
the status word significant bits are:
Table 4.3 – Status word significant bits
Status
Name
Meaning
Bit 0
ON/OFF
Bit 3
OVC
Over Current : IMon > I0set