Document type:
Title:
Revision date:
Revision:
User's Manual (MUT)
A3486 3Phase 400Vac to 2x2kW/1x4kW 48Vdc
08/10/2007
10
NPO:
Filename:
Number of pages:
Page:
00120/04:A3486.MUTx/10 A3486_REV10.DOC
35
33
The
VCon
item returns back the VCon value.
A read access to the
VCon#EU
item returns a string with the VCon Engineering Units.
A read access to the
VCon#HighEU
item returns the highest possible VCon value.
A read access to the
VCon#LowEU
item returns the lowest possible VCon value.
The
IMon
item returns back the IMon value.
A read access to the
IMon#EU
item returns a string with the IMon Engineering Units.
A read access to the
IMon#HighEU
item returns the highest possible IMon value.
A read access to the
IMon#LowEU
item returns the lowest possible IMon value.
The
Temp
item returns back the channel temperature.
A read access to the
Temp#EU
item returns a string with the Temp Engineering Units.
A read access to the
Temp#HighEU
item returns the highest possible Temp value.
A read access to the
Temp#LowEU
item returns the lowest possible Temp value.
A read access to the
Status
item returns back a 16 bit pattern indicating channel status,
as follows:
Bit 0: ON/OFF
Bit 1: don’t care
Bit 2: don’t care
Bit 3: OverCurrent
Bit 4: OverVoltage
Bit 5: UnderVoltage
Bit 6: don’t care
Bit 7: Over HVmax
Bit 8: don’t care
Bit 9: Internal Trip
Bit 10: Calibration Error
Bit 11: don’t care
Bit 12: don’t care
Bit 13: OverVoltage Protection
Bit 14: Power Fail
Bit 15: Temperature Error
The
RemIlk
item returns back the Remote Interlock value.
A read access to the
RemIlk#CoOpen
returns back the label “Off” associated to RemIlk
=0.
A read access to the
RemIlk#CoClose
returns back the label “On” associated to RemIlk
=1.
The
IntFail
item returns back the Internal Failure value.
A read access to the
IntFail#CoOpen
returns back the label “Off” associated to IntFail
=0.
A read access to the
IntFail#CoClose
returns back the label “On” associated to IntFail
=1.
The
MaxDrop
item returns back the Maximum Drop status value.
A read access to the
MaxDrop#CoOpen
returns back the label “Off” associated to
MaxDrop =0.
A read access to the
MaxDrop#CoClose
returns back the label “On” associated to
MaxDrop =1.
The
Pw
item allows to switch ON/OFF the channel.
A read access to the
Pw#CoOpen
returns back the label “Off” associated to Pw=0.
A read access to the
Pw#CoClose
returns back the label “On” associated to Pw=1.
The
GlbOnEn
item enables the channel to respond to the A1676A Global On command.