Cadis Aquavision Control Скачать руководство пользователя страница 4

 

4/23  www.cadis.be  [email protected]  

 

User’s Manual   
Aquavision Control  

 

Monitoring Module  

Note

: To counter problems with lime scale, the shut-off valve is closed and re-opened weekly; this action is 

performed fully automatically and takes place when there is no consumption detected. During this action a check is 
also performed to ensure that the shut-off valve is fully closed. If the check of the valve has been conducted without 

any problems, this value is OK (green "

"). If the check of the valve has failed, then this value is 'error' (red "

") and 

the shut-off valve should be inspected. 
 
The user can follow all detailed information about the water consumption per pipeline in the right-hand side of the 

table. This information concerns the flow, consumption volume and the index of the water meter in m³. 
 

 

 

2.2

 

Acknowledging and checking alarms  

An alarm is always shown via a pop-up screen on the touch screen or in the web server page. In the special alarm 
page a user with a password can also define the actions that must be linked to an alarm. Possible actions are: 

sending an alarm e-mail, cutting off the water supply or activating a buzzer. 

 

 

Each alarm must be acknowledged by the user, on the touch screen of the module, or remotely on a computer by 

clicking the red 

 

button

. For some alarms with very high consumption, it may be necessary to click 

several times to acknowledge. The alarm confirmation time is saved in the module. 

If you want to acknowledge an 

alarm remotely via your computer, you need access to the network to which the control module has also been 

linked. 
 
Given that the module constantly adjusts its values to the demands of the building, for certain alarms (very high 

values) the user will need to indicate whether it relates to a normal, but high consumption, or whether a leak or 
water wastage has indeed occurred. To do so, the user needs to click on the red "Alarm" button when there is a 
real alarm or leak, or he must click on the green "False alarm" button if normal, yet high consumption is involved. 
The module itself adapts the values for possible alarms after this last action and in the future no alarm will report 

for the same consumption values. 

Содержание Aquavision Control

Страница 1: ...9 3 5 Modifying the password and user language 10 3 6 Alarm when daily or weekly consumption is exceeded 10 3 7 Alarm during a period of no water consumption 11 3 8 Activation of special functions via...

Страница 2: ...e diagram below If additional branch pipelines need to be protected against leaks and water wastage a second Aquavision Control module must be fitted For each additional module three extra branch pipe...

Страница 3: ...is automatically correctly set if the module is linked to a network with access to the Internet Indication of the consumption period and the normal or alarm state of the module Temperature and pressu...

Страница 4: ...define the actions that must be linked to an alarm Possible actions are sending an alarm e mail cutting off the water supply or activating a buzzer Each alarm must be acknowledged by the user on the...

Страница 5: ...y the message System normal 2 3 Consulting the list of alarms and creating alarm reports To be able to analyse several alarms that have occurred the user can view a summary of all alarms on a separate...

Страница 6: ...tected that was calculated by the module Small leak Module detected a small leak Very small leak Leak alarm for a micro leak alarm after 24 hours Average daily consumption exceeded Alarm report if the...

Страница 7: ...r pressure out of range of pre set limits Alarm signal when the pressure exceeds or falls below the pre set minimum or maximum limits Temperature out of range of pre set limits Alarm signal when the t...

Страница 8: ...dule must be linked either directly or via a LAN network of the building on the LAN port After this an Internet browser must be opened and the pre set IP address of the module must be entered in the a...

Страница 9: ...h a CADIS Aquavision Master module At the bottom of the Network settings page you can also enter an IP address for the Aquavision MASTER module N B This should only be done if a CADIS MASTER module ha...

Страница 10: ...the user language and the name the place of the module can be set or modified 2 5 Alarm when daily or weekly consumption is exceeded Go to the Device settings same screen as above On the Device settin...

Страница 11: ...ecial functions can be activated Connect external leak detection system to the AV Control module to cut off water supply or to send alarms Activate unlimited water consumption for a set period via ext...

Страница 12: ...e burglar alarm system is switched on the AV CONTROL module will automatically cut off the water supply by closing the shut off valves When the burglar alarm system is switched off the AV Control modu...

Страница 13: ...rise If this sanitary pipeline also supplies the water for fire hoses then no shut off valve may be fitted 3 Connect the water meter that was installed by the distribution company on the street side f...

Страница 14: ...icking on the pencil on the right If you click on the pencil on the right the next screen opens where you can amend the data per pipe The ID of the water meter and the name of the pipe can be filled i...

Страница 15: ...l on the right and also set limits for the alarms 2 9 Setting alarm e mail cutting off water supply and buzzer per alarm type You can insert the addresses to which alarm e mails must be sent to in the...

Страница 16: ...d here 2 10 The calendar function cut off or allow water supply with volume limit By activating this function the AV Control module will turn on or cut off water at pre set times for predefined pipeli...

Страница 17: ...hich pipeline is involved option button after Input Note The time period can never be longer than 1 week A week starts at the earliest on Monday and finishes at the latest on Sunday The existing calen...

Страница 18: ...rt must be generated Set to 10 as standard 2 12 Creation of consumption reports All consumption data alarms and actions are saved in the module for 1 year and can be consulted at any time Via a separa...

Страница 19: ...en of the AV Control module he must also manually open them afterwards using the same procedure In the Real Time screen select the User action button This brings you to a screen where you see the name...

Страница 20: ...nded for persons who set up and program the GBS systems The following data can be read by a GBS system by means of a ModBus TCP IP communication protocol on the standard IP port 502 Modbus RTU via RS4...

Страница 21: ...open Register 30038 Status External Intrusion alarm input 1 Input closed 0 Input open Register 30039 Time left in hours until Unlimited mode ends Value in hours 0 24 Register 30040 General Status Aqua...

Страница 22: ...er or laptop with a network cable to the AQUAVISION CONTROL module Amend the IP address of the computer via the Network centre Open the computer s network centre via the Configuration screen Click on...

Страница 23: ...ddress and Subnet masker as shown in the example above Click on OK Click on Close Click on Close The computer works now with the fixed IP address 10 100 100 220 Enter the IP address in the web browser...

Отзывы: