![C-TEC QT601-2 Скачать руководство пользователя страница 8](http://html1.mh-extra.com/html/c-tec/qt601-2/qt601-2_installation-and-programming-manual_3100300008.webp)
Radio transmitter
connection for alphanumeric
pagers, or DECT telephones
RS232 connection
(for a PC running Quantec’s QT707S
Surveyor Data Management Software,
or a QT600P printer for outputting
the Quantec Controller’s datalog)
230 Va.c.
3 A switch
fused spur
BC286/2
24 V 7 Ah standby
battery pack
(2 x 12 V batteries)
QT603 Network Splitter
QT603 Network Splitter
QT603 Network Splitter
QT603 Network Splitter
QT601-2 Quantec
Controller
GENERAL WIRING RULES
• Quantec utilises a unique data protocol that works down just two wires.
• All system wiring is made in a ‘Spine’ and ‘Limb’ configuration, using network splitters, allowing the use of ordinary
unscreened cable which simplifies installation, fault-finding and commissioning.
• A maximum of 255 addressable devices can be connected to a Quantec Controller (dependent on network topology).
• Distribute Splitters evenly throughout the site and locate at an accessible height.
• As addressable devices are soft addressed, no consideration needs to be given to how they will interact until system
programming.
• Slave devices such as slave ceiling pulls, slave overdoor lights and slave infrared ceiling receivers connect to Quantec
via a master call point, master ceiling receiver, monitoring point or universal programming device using 2, 3 or 4 cores
of strand security cable - refer to the shaded areas on Page 9 for guidance.
• A QT423 Configurator is needed to program the special functions available on devices marked *
QT603 Network Splitter
2
2
5 open collector
outputs (active
for individual call
levels) typically
used to switch
24 V relays
RS232 PC connection for
system programming
SPINE WIRING
• Wire Spines in 1.5 mm
2
or 2.5 mm
2
T & E
For a typically loaded system, the following spine lengths apply:
• Max. length for a single spine using 1.5 mm
2
cable = 150 m
• Max. length for a single spine using 2.5 mm
2
cable = 250 m
• Max. length of all limbs = 750 m.
The above are general rules of thumb, if required refer to
Pages 10 & 11 for more specific wiring details/calculator chart.
1 mm
2
T&E
QT601-2 Quantec Controller
Installation & Programming Manual • Approved Document No. DNU6012001 Rev 5 • Page 8 of 42
SYSTEM WIRING OVERVIEW