QT601-2 Quantec Controller
Installation & Programming Manual • Approved Document No. DNU6012001 Rev 5 • Page 21 of 42
2.0 The System Setup Menu
The System Setup Menu allows you to tell the Quantec
Controller specific details about how the system will work.
2.1 Setting 'Time Outs' for Call Divert and Call
Accept Arrangements
This option allows you to tell Quantec the time that should
elapse before a call is diverted from one Group of Displays to
another, or an unanswered 'accepted' call returns to Displays.
On selecting the 'Set Time Outs' prompt, the following
window will appear:
Use the scroll and Accept keys to enter the appropriate Time
Out figure. The range for each function is 1 to 8 minutes in
steps of 1 minute. Any changes will be saved automatically.
2.2 Setting the Access Level 2 Code
This option allows you to change the four digit access code
for Access Level 2 (this can be any combination of the 1, 2 and
3 keys). On selecting the 'Set AL2 Code' prompt, the following
window will appear:
Enter the new code as required. When the fourth key has
been pressed, the Controller automatically registers the code
and returns you to the System Setup Menu.
2.3 Setting the Access Level 3 Code
This option allows you to change the four digit access code
for Access Level 3 (this can be any combination of the 1, 2 and
3 keys). On selecting the 'Set AL3 Code' prompt, the following
window will appear:
Enter the new code as required. When the fourth key has
been pressed, the Controller automatically registers the code
and returns you to the System Setup Menu.
2.4 Setting the Attack Reset Code
For systems utilising Quantec's infrared attack call level, this
option allows the four digit Attack Reset code to be entered
or changed (this can be any combination of the scroll up, scroll
down and Accept keys). On selecting the 'Set Attack Reset'
prompt, the following window will appear:
Enter the new code as required. When the fourth key has
been pressed the Controller automatically registers the new
code and returns you to the System Setup Menu.
2.5 Setting the Call Reset Code
This option allows Quantec's four digit 'Call Reset' code to be
entered or changed (this can be any combination of the scroll
up, scroll down and Accept keys). On selecting the 'Set Call
Reset' prompt, the following window will appear:
Enter the new code as required. When the fourth key has been
pressed the Controller automatically registers the code and
returns you to the System Setup Menu.
2.6 Setting Up the Datalogging Function
This option allows Quantec's Datalogging function to be set
up. Select the 'Setup Logger' prompt and use the scroll and
Accept keys to choose one of the following options:
this disables the logging function so
no events are logged or can be printed.
this enables the logger to print when
manually selected to do so.
this enables the logger to print
automatically after 10, 20, 30, 40, 50,
60, 70, 80, 90 or 100 events.
Note
: If 'Man Only' is selected and the log record is not
printed, the datalogger's memory will fill to capacity. When
this occurs a warning message will appear on the Controller
and any new events will not be logged until the existing
events have been printed.
IMPORTANT
: When 'Surveyor' mode is active (refer to section
2.14) logging settings cannot be altered.
2.7 Setting Up Emergency Call Routes
This option allows you to set the system up so that EMERGENCY
calls are sent to all Display Groups (Globally), regardless of how
the Group Area routing arrangements have been set up.
On selecting the ‘Emergency G/L’ prompt, it is possible to scroll
through the following two options:
When you have selected the required option, press Accept.
2.8 Setting Up Attack Call Routes
This option allows you to set the system up so infrared Attack
calls are sent to all Display Groups (Globally) regardless of how
the Group Area routing arrangements have been set up. On
selecting the ‘Attack G/L’ prompt, it is possible to scroll
through the following two options:
When you have selected the required option, press Accept to
return to the System Setup Menu.
Divert: 1 mins
Accept: 1 mins
Access Level 2
Code:
Access Level 3
Code:
Set Attack Reset
Code:
Set Call Reset
Code:
Logging OFF
Logging Man Only
Logging Man/Auto
Output on: 010
Emergency Calls
Sent: Locally
Emergency Calls
Sent: Globally
Attack Calls
Sent: Locally
Attack Calls
Sent: Globally