5. Cut the cable to length.
6.4.
Connecting the DC Cables
BYD recommends using bootlace ferrules for connecting the DC cables to the blocks.
Cable requirements:
The diameter of the DC cables: 5 mm
to 12.5 mm.
Cross section: 6 mm
2
to
16
mm
2
Procedure:
1.
Attach the cables to an external cable support rail.
2. Cut the cables to length and strip 25 mm off the
insulation.
3. If you are using bootlace ferrules, mount the
bootlace ferrules and crimp gas-tight.
4. Lead the cables to the blocks.
5. Insert a flat-head screwdriver into the switch of the
connector.( recommended screwdriver type, S3.5×100)
6. Hold the cables, and push up the screwdriver to make the switch go to
the end.
Damage to the Combiner Box due to moisture penetration
• Moisture can penetrate the Combiner Box through unsealed cable glands.