Battery Box Premium HV Combiner Box
17
Installation Manual V1.
1
7. Make sure the switch is well fixed at the end of the sink.
8. Remove the screwdriver from the connector.
6.5.
Connecting the Grounding Cable
Cable requirement
•
Conductor cross-section: 10
-16
mm
2
•
Outer diameter: 5 mm to 12.5 mm
•
With a ring terminal
Procedure:
1. Loose the original nut and washer on the ground post.
2. Put the grounding cable in the ground post.
3. Tighten the nut and washer. (torque: 5.5 Nm).
4. Ensure that the grounding cable is securely fixed.
BYD Smart Device Hungary Kft.