background image

The vacuum pump starts, but labours or runs
noisily or rattles

The drive motor draws a too high current (com-
pare with initial value after commissioning)

Connections in the drive motor terminal box are
defective

Not all drive motor coils are properly connected

The drive motor operates on two phases only

Check the proper connection of the wires
against the connection diagram

Tighten or replace loose connections

The vacuum pump runs in the wrong direction

Verification and rectification see “Installation
and Commissioning”, correct if necessary

Standstill over several weeks or months

Let the vacuum pump run warm with inlet
closed

Improper oil quantity, unsuitable oil type

Use the proper quantity of one of the recom-
mended oils

(see “Oil”, oil change see “Maintenance”)

No oil change over extended period of time

Perform oil change incl. flushing (see “Mainte-
nance”)

Foreign objects in the vacuum pump

Stuck bearings

Repair the vacuum pump (Busch service)

The vacuum pump runs very noisily

Defective bearings

Repair the vacuum pump (Busch service)

The vacuum pump runs very hot

(the oil sump temperature shall not exceed
100 °C)

Cooling water flow too low

Check the cooling water circuit and adjust the
flow if necessary

Ambient temperature too high

Observe the permitted ambient temperatures

Temperature of the inlet gas too high

Observe the permitted temperatures for the
inlet gas

Oil level too low

Top up oil

Check the oil filler plugs

Check the mechanical seals (option)

Mains frequency or voltage outside tolerance
range

Provide a more stable power supply

Partial clogging in the suction or discharge line

Remove the clogging

Long suction, discharge or pressure line with
too small diameter

Use larger diameter

Cooling water too low

Quick coupler for cooling water dislocated

Water supply pressure too low

Cooling water piping obstructed

Leakage of cooling water piping

Connect the quick couple

Apply proper pressure

Clean/ replace piping

Replace seals

Pump temperature too high

Failure of discharge line
Back pressure of pump too high
Cooling water flow too low
Vacuum contaminated with product residues
Ambient temperature too high

Check the discharge line
Che the discharge piping
Check the cooling system
Disassemble the vacuum pump
Check the limits of use

Oil level too low

Oil too low
Oil leakage

Check the oil casing sealings
Refill with oil

Cooling liquid temperature too high

Lack of cooling liquid
Escape of cooling liquid

Fill with cooling liquid
Check off the cooling liquid circuit

Troubleshooting

DP 80-2000 C-T

Page 18

0870564647 (En)

Содержание COBRA NS 0070-0160 C

Страница 1: ...allation and Maintenance Instructions Screw Vacuum Pumps COBRA NS 0070 0160 C Ateliers Busch S A Zone industrielle 2906 Chevenez Switzerland 0870570353 181017 Original instructions Modifications reser...

Страница 2: ...d oil 14 Filling in new oil 14 Checking the cooling liquid 14 Checking the level of the cooling liquid 14 Refilling cooling liquid 14 Filling in cooling liquid 14 Draining the cooling liquid 14 Checki...

Страница 3: ...water flow meter OFP Oil filler plug OSG Oil sight glass ODP Oil drain plug GC Nitrogen connection option DGR Nitrogen regulating valve option FIS 02 Nitrogen flow meter option PMR Unblocking screw fo...

Страница 4: ...be combined with a Busch booster pump i e type WY 0500 C Cooling The vacuum pump is cooled by a cooling water circuit in the cylinder 4 indirect cooling A temperature probe mounted in the cylinder of...

Страница 5: ...cognise these instructions by the signal words DANGER WARNING and CAUTION which are defined as follows DANGER Disregard of this safety instruction will always result in death serious injuries or sever...

Страница 6: ...kaging can attack synthetic surfaces and surfaces of other elastomers If in doubt please contact your nearest distributor VCI packaging provides several years of protection against corrosion even unde...

Страница 7: ...or solid particles can lead to the destruction of the vacuum pump If the sucked gas contains dusts or solid foreign bodies u Make sure that a suitable filter or protective screen is installed at the...

Страница 8: ...doubts contact your Busch representative Installation Assembly l Make sure that the necessary installation instructions are followed l Fasten or install the pump at its final installation site Electr...

Страница 9: ...stopping of the vacuum pump when the flow drops below 2 l min The cooling water flow is factory set on 2 5 l min and can be adjusted at the regulating valve CWR This water circuit is used to cool the...

Страница 10: ...s l Stop the vacuum pump and wait a few minutes l Make sure that the oil level still lies between the MIN and MAX markings on the oil sight glasses If the oil level is below the MIN marking u Fill in...

Страница 11: ...een atmospheric and ultimate pressure CAUTION The surface temperature of the vacuum pump can exceed 70 C when the vacuum pump is in operation Risk of burns The vacuum pump may not be touched when it i...

Страница 12: ...off the nitrogen supply l Shut off the cooling water supply Maintenance DANGER In case the vacuum pump has conveyed gases that have been contaminated with foreign materials that are dangerous to heal...

Страница 13: ...t the water outlet CWo and then the water inlet CWi and nitrogen connection GC l Switch on the main power supply l Make sure that the Installation prerequisites are followed l Switch on the vacuum pum...

Страница 14: ...e oil level lies between the MIN and MAX markings on the oil sight glasses l Make sure that the seals of the filler cap are not damaged and that they sit properly Replace them if necessary l Screw on...

Страница 15: ...a danger to the environment Prior to shipping the vacuum pump must imperatively be decontaminated and the degree of contamination must be documented in a declaration of decontamination Declaration of...

Страница 16: ...ion regulations Begin dismantling the vacuum pump CAUTION Wear protective clothing when carrying out dismantling work u Dispose of the vacuum pump as scrap metal Dispose of the individual parts of the...

Страница 17: ...d protection is too small or trip level is too low Compare the trip level of the drive motor starter overload protection with the data on the name plate Correct if necessary In case of high ambient te...

Страница 18: ...uit and adjust the flow if necessary Ambient temperature too high Observe the permitted ambient temperatures Temperature of the inlet gas too high Observe the permitted temperatures for the inlet gas...

Страница 19: ...hemically contaminated or polluted oil can lead to hazardous pump conditions which could cause personal injury Oil quantity The quantity of oil specified in the following table is of informative natur...

Страница 20: ...f informative nature only Respect the procedure of filling the cooling liquid Quantity Zitrec M 25 already mixed ready to use NS 0070 0160 C 4 litres CAUTION The proportion of pure glycol and water fo...

Страница 21: ...V Y 480 V A A A A 17 2 15 8 9 9 9 1 27 21 15 4 12 0 Nominal motor speed 50 Hz 60 Hz min 1 min 1 3000 3600 3000 3600 Noise level EN ISO 2151 50 Hz 60 Hz dB A dB A 62 68 Ambient temperature C F 0 40 32...

Страница 22: ...g the standards Standard Title of the standard EN ISO 12100 2010 Safety of machinery Basic concepts general principles of design EN ISO 13857 2008 Safety of machinery Safety distances to prevent hazar...

Страница 23: ...Note...

Страница 24: ...myun Icheon si Gyunggi do 467 813 Republic of Korea Phone 82 31 645 2700 Fax 82 31 631 2898 e mail busch busch co kr Malaysia Busch Malaysia Sdn Bhd 4 6 Jalan Taboh 33 22 Seksyen 33 Shah Alam Technolo...

Отзывы: