Use the Trouble Shooting Guide (pages 19 to 21) to 
assist in locating where a malfunction in the control 
system is occurring.

4

 

PROCEDURE FOR MEASURING FAN 
DIFFERENTIAL PRESSURE (See Figure 13).

a.  With boiler off, remove black silicone tubing from 

low side of pressure switch.

b.  With tee and ¼” aluminum stubs, connect 

manometer as shown with additional tubing.

c.  Start boiler and read differential pressure on 

manometer.  Should be -0.6” wc or greater (example 
-0.7” wc).

d.  Stop boiler, remove manometer and reconnect black 

silicone tubing to duct.

5

 

CHECK GAS INPUT RATE TO BOILER

a.  Input rate and maximum inlet pressure shown on 

rating label must not be exceeded.  Inlet pressure 
must not be lower than minimum inlet pressure 
shown on rating label.

b.  All rate checks and all adjustments are to be made 

while boiler is fi ring - all other appliances connected 
to the same meter as the boiler must be off.

c.  Water manometer or water column gauge should 

be connected to a shutoff valve installed in the 
1/8” pipe tapping in the gas valve - boiler off.  By 
installing gas valve up stream of manometer, gas 
pressure can be introduced gradually - without 
shutoff valve, surge of pressure when boiler is 
turned on, could blow liquid out of manometer.  
Replace plug in gas valve when rate check is 
fi nished.

d.  Approximate input - Adjust pressure regulator on 

combination gas control so that manifold pressure is 
equal to that shown on rating label.  Determine what 

TROUBLE SHOOTING

Figure 13

 

PROCEDURE FOR MEASURING FAN DIFFERENTIAL 

PRESSURE

fl ow (cu. ft.) should be in 3 minutes using formula 
below:

 

 

cu. ft. per   =   Btuh Input (from Rating Label)  

         

     3 min.    =                      20000

 

Clock gas meter for three (3) minutes using second 
hand or stop watch.

 

For minor input changes readjust pressure regulator 
on combination gas control.  Increase or decrease 
manifold pressure to obtain corresponding increase 
or decrease in gas input.

 

Turning regulator adjusting screw clockwise 
increases pressure.  Counterclockwise rotation 
decreases pressure.  If it is necessary to increase 
manifold pressure more than 0.3” of water to obtain 
rated input, remove orifi ces and drill one size larger.  
Reinstall and recheck input rate.

Содержание SM-6

Страница 1: ...l i o B e d i v o r p r e l i o b r e b m u N l e d o M r e l i o B r e b m u N l a i r e S r e l i o B e t a D n o i t a l l a t s n I _ _ _ _ _ _ _ M S _ _ _ _ _ _ _ 6 r o t c a r t n o C g n i t a...

Страница 2: ...of the installing contractor to see that all controls are operating properly when the installation is completed Service on this boiler should be undertaken only by trained and skilled personnel Post...

Страница 3: ...NLY Figure 1 SPACEMASTER WALL MOUNTED GAS BOILER DIMENSIONAL DATA I General Installation Requirements 4 II Installation Instructions 7 III Operating Instructions 13 IV Service 23 V Repair Parts 26 VI...

Страница 4: ...ers Therefore adequate supports must be added between existing studding b A suggested mounting height where practical is five feet six inches from floor to center line of intake air duct opening See F...

Страница 5: ...r area which has adequate air supply shall be provided One opening should be near the floor and the other near the ceiling Each shall have a free area of not less than one 1 square inch for each thous...

Страница 6: ...0 0 1 0 5 3 0 1 5 9 1 5 2 1 4 4 3 9 5 7 1 0 5 1 0 4 4 8 0 6 1 5 7 1 7 3 7 7 5 4 1 r o f I I d n a I s e l b a T h t i w d e s u e b o t s r e i l p i t l u M 0 6 0 n a h T r e h t O y t i v a r G c i...

Страница 7: ...oiler mounting wall bracket on wall using a 24 level across top corners level wall bracket and secure to wall with suitable fasteners h Attach lower R S jacket mounting bracket to right side of boiler...

Страница 8: ...e gasket is in place and flat against back plate Attach duct with four 4 20 brass hex nuts lockwashers and flat washers 3 INSTALLING EXTERIOR TELESCOPING INTAKE AIR DUCT See Figures 4 and 5 a Position...

Страница 9: ...ng stainless steel machine screws provided 5 DO NOT REPLACE ENCLOSURE COVER until boiler piping is completed and system is filled vented and checked for water leaks 6 CONNECT SUPPLY AND RETURN PIPING...

Страница 10: ...y valve will raise the system temperature while opening the by pass valve will lower the system supply temperature If it is required to perform a long term pressure test of the hydronic system the boi...

Страница 11: ...11 Figure 7 RECOMMENDED PIPING FOR COMBINATION HEATING COOLING REFRIGERATION SYSTEMS Figure 9 EXPLODED JACKET ASSEMBLY...

Страница 12: ...be influenced by drafts hot or cold water pipes lighting fixtures television rays of the sun or near a fireplace Keep large furniture away from thermostat so there will be free movement of room air ar...

Страница 13: ...s have been purged but always have one zone open At completion open all zone valves 10 Close drain valve on purge fitting 11 Continue filling the system until the pressure gauge reads 12 psi Close fil...

Страница 14: ...14 NOTE YOUR BOILER IS EQUIPPED WITH A HONEYWELL VR8204 OR VR8304 GAS VALVE PLEASE FOLLOW THESE OPERATING INSTRUCTIONS...

Страница 15: ...15 Figure 11 SCHEMATIC WIRING DIAGRAM...

Страница 16: ...16 Figure 12 LADDER WIRING DIAGRAM...

Страница 17: ...regulator on the gas valve will permit full flow through the main gas valve high fire Should a loss of flame occur the main valve closes and the spark reoccurs within 0 8 second The ignition module h...

Страница 18: ...nstalled in the 1 8 pipe tapping in the gas valve boiler off By installing gas valve up stream of manometer gas pressure can be introduced gradually without shutoff valve surge of pressure when boiler...

Страница 19: ...19...

Страница 20: ...20...

Страница 21: ...21...

Страница 22: ...lead from electrical junction block If burners are not shut down by module determine cause of malfunction Replace module or gas valve if necessary 10 MAIN BURNER FLAMES should have a clearly defined...

Страница 23: ...r and jacket front panel If the flue passageways need cleaning remove burners as described in paragraph 4 below Using long handle wire or bristle flue brush and vacuum brush flueways thoroughly from t...

Страница 24: ...attention to solder joints on bellows and float when this type of control is used Check float for evidence of collapse and check mercury bulb where applicable for mercury separation or discoloration P...

Страница 25: ...thing 3 Gloves 4 Eye Protection Take steps to assure adequate ventilation Wash all exposed body areas gently with soap and water after contact Wash work clothes separately from other laundry and rinse...

Страница 26: ...5 5 0 6 1 1 8 n a F s e d u l c n I y l b m e s s A t n e m e c a l p e R n a F t f a r D d e c u d n I s t e k s a G t e l t u O n a F 2 o w t d n a t e k s a G t e l n I n a F t e k s a G t e l t u...

Страница 27: ...either the supply or return piping The minimum safe water level of a water boiler is at the uppermost top of the boiler that is it must be full of water to operate safely What Kind Typically in resid...

Страница 28: ...HTS AND YOU MAY ALSO HAVE OTHER RIGHTS WHICH VARY FROM STATE TO STATE Limited Warranty FOR RESIDENTIAL CAST IRON WATER BOILERS 03 03 Subject to the terms and conditions set forth below U S Boiler Co I...

Отзывы: