Burnham 805H Скачать руководство пользователя страница 9

9

b.  If result is less than 50 ft

3

 per 1,000 Btuh, space 

is considered a 

confined space

.

4.  Determine building type. A building of 

unusually 

tight construction

 has the following characteristics:

a.  Walls and ceiling exposed to outside atmosphere 

have a continuous water vapor retarder with a 

rating of 1 perm or less with openings gasketed 

and sealed, and

b.  Weather-stripping has been added on openable 

windows and doors, and

c.  Caulking or sealants applied in joints around 

window and door frames, between sole 

plates and floors, between wall-ceiling joints, 

between wall panels, at plumbing and electrical 

penetrations, and at other openings.

5.  For boiler located in an 

unconfined space in a 

building of other than unusually tight construction

adequate combustion and ventilation air is normally 

provided by fresh air infiltration through cracks 

around windows and doors.

6.  For boiler located in an

 unconfined space in a 

building of unusually tight construction

 or in 

confined space

, provide outdoor air through 

permanent opening(s) which communicate directly 

or by duct with the outdoors or spaces (crawl or 

attic) freely communicating with the outdoors.  

Minimum dimension of air opening(s) is 3” (7.6 

cm).
a.  Two permanent openings:  Locate one opening 

within 12 inches (30.5 cm) of top of space. 

Locate remaining opening within 12 inches  

(30.5 cm) of bottom of space.  Size each opening 

per following:

i.

  Direct communication with outdoors. 

Minimum free area of each opening must be 

1 square inch per 4,000 Btu per hour input 

of all equipment in space.

ii.

  Vertical ducts. Minimum free area of each 

opening must be 1 square inch per 4,000 

Btu per hour input of all equipment in space. 

Duct cross-sectional area shall be same as 

opening free area.

iii.

  Horizontal ducts. Minimum free area of each 

opening must be 1 square inch per 2,000 

Btu per hour input of all equipment in space. 

Duct cross-sectional area shall be same as 

opening free area.

b.  One permanent opening shall be permitted where 

the boiler has clearances of at least 1” (2.5 cm) 

from the sides and rear and 6” (15.2 cm) from 

the front.  Locate the opening within 12 inches      

(30.5 cm) of top of space.  Size opening per 

following:

i.

  Minimum free area of 1 square inch per 

3,000 Btu per hour input of all equipment in 

space.

ii.

  Free area shall not be less than the sum 

of the areas of all vent connectors in the 

confined space.

 

Alternate method for boiler located within confined 

space.

 Use indoor air if two permanent openings 

communicate directly with additional space(s) of 

sufficient volume such that combined volume of all 

spaces meet criteria for unconfined space. Size each 

opening for minimum free area of 1 square inch per 

1,000 Btu per hour input of all equipment in spaces, 

but not less than 100 square inches.

7.  Ventilation Duct Louvers and Grilles. Equip outside 

openings with louvers to prevent entrance of rain 

and snow, and screens to prevent entrance of insects 

and rodents. Louvers and grilles must be fixed in 

open position or interlocked with equipment to open 

automatically before burner operation. Screens must 

not be smaller than ¼ inch mesh.

  Consider the blocking effect of louvers, grilles and 

screens when calculating the opening size to provide 

the required free area. If free area of louver or grille 

is not known, assume wood louvers have 20-25 

percent free area and metal louvers and grilles have 

60-75 percent free area.

8.  For Specially Engineered Installations.  The above 

requirements shall be permitted to be waived 

where special engineering, consistent with good 

engineering practice and approved by the authority 

having jurisdiction, provides an adequate supply of 

air for combustion, ventilation, and dilution of flue 

gases.

Do not install boiler where gasoline or other 

flammable  vapors  or  liquids,  or  sources  of 

hydrocarbons (i.e. bleaches, cleaners, chemicals, 

sprays, paint removers, fabric softeners, etc.) are 

used or stored.

Mis-sizing of the boiler with regard to the heating 

system load will result in excessive boiler cycling 

and accelerated component failure. Burnham 

DOES NOT warrant failures caused by mis-sized 

boiler applications.  DO NOT oversize the boiler 

to the system.  Modular/multiple boilers greatly 

reduce the likelihood of boiler oversizing.

Содержание 805H

Страница 1: ...only be used by a qualified heating installer service technician BEFORE installing read all instructions in this manual and all other information shipped with the boiler Post all instructions and manu...

Страница 2: ...should be made to the following Standards USA BOILERS A Current Edition of American National Standard ANSI NFPA 31 Installation of Oil Burning Equipment for recommended installation practices B Curren...

Страница 3: ...othing and equipment when installing starting up or servicing this boiler to prevent scald injuries Do not rely on the pressure and temperature gauges to determine the temperature and pressure of the...

Страница 4: ...h cast iron section is permanently marked with the MAWP listed on the boiler s ASME Data Label The MAWP for all Series 8HE Boiler is 50 psi Water Only It is common and acceptable practice to install t...

Страница 5: ...sleeved loose fitting clothing 3 Gloves 4 Eye Protection Take steps to assure adequate ventilation Wash all exposed body areas gently with soap and water after contact Wash work clothes separately fr...

Страница 6: ...e Installation 8 II Boiler Assembly 10 III Gas Control System Assembly 17 Knockdown Boilers IV Water Trim and Piping 24 V Gas Piping 28 VI Venting 30 VII Electrical 33 VIII System Start up 49 IX Servi...

Страница 7: ...7 24 13 16 16 1 8 7 dia x 15 ft 11 9 600 610 806H 315 23 3 4 11 7 8 8 27 13 16 18 8 dia x 15 ft 13 9 690 700 807HE 340 27 1 2 13 3 4 8 27 13 16 18 8 dia x 15 ft 15 9 785 870 808HE 410 31 1 4 15 5 8 9...

Страница 8: ...with size of boiler a Front 18 b Top 51 c Draft hood rear sides and flue connector 6 3 Canada 805H 810HE a Top and front 18 45 7 cm b Flue rear and sides 6 15 2 cm D Provide clearance for servicing an...

Страница 9: ...least 1 2 5 cm from the sides and rear and 6 15 2 cm from the front Locate the opening within 12 inches 30 5 cm of top of space Size opening per following i Minimum free area of 1 square inch per 3 00...

Страница 10: ...rear corner of Base End Panel raise boiler and install 1 wood blocks under rear corners Install pipe roller between Base and skid 3 Remove 1 wood blocks Place 3 pipe roller on floor behind skid 4 Rol...

Страница 11: ...less than 50 psi gauge pressure Figure 4 Installation of Special Base for Combustible Flooring 6 Examine boiler for leaks or damage due to shipment or handling 7 Remove plugs from Return Tapping B Ta...

Страница 12: ...ated in Combination Boiler Parts and Control Carton 1 Attach Base Front Panel to Section Assembly using 20 x 1 carriage bolts washers and nuts 2 Seal between top of Base Front Panel and Section Assemb...

Страница 13: ...13 Figure 6 Flame Roll out Switch Installation Figure 7 Burner Burner Access Panel Installation...

Страница 14: ...rews 5 Remove Rating Label from envelope marked RATING LABEL ENCLOSED Remove Combustible Clearance Label from Combination Boiler Parts and Controls Carton Attach to Vestibule Panel in locations shown...

Страница 15: ...15 Figure 8 Jacket Assembly...

Страница 16: ...16 Figure 9 EP Control Installation...

Страница 17: ...4 Mount Transformer continuous circulation or Control Center intermittent circulation to Junction Box See Figure 8 a Canada only loop 4 nylon cable tie between junction box and transformer control ce...

Страница 18: ...18 Figure 10 Schematic Gas Piping 24V Standing Pilot 806H 807HE...

Страница 19: ...19 Figure 11 Main Gas Piping Intermittent Ignition EI...

Страница 20: ...20 Figure 12 Schematic Pilot Piping Honeywell EI USA...

Страница 21: ...21 Figure 13 Schematic Pilot Piping Honeywell EI Canada Natural Gas 805H 810HE LP Gas 806H 807HE...

Страница 22: ...22 Figure 14 Schematic Gas Piping EP Control System Natural Gas Only 806H 810HE...

Страница 23: ...23 Figure 15 Schematic Gas Piping EP CSD 1 Control System 808HE 810HE...

Страница 24: ...at the potential of severe burns is eliminated DO NOT pipe in any area where freezing could occur DO NOT install any shut off valves plugs or caps Consult Local Codes for proper discharge piping arran...

Страница 25: ...ping See Figure 19 a Install 2 NPT x 10 Nipple into Supply Tapping A See Figure 3 Figure 18 Temperature Pressure Gauge Installation Figure 19 Alternate Temperature Pressure Gauge Installation b Instal...

Страница 26: ...ty Burnham Commercial recommends maintaining temperature differential drop across the system at 40 F or less and return water temperature at minimum of 135 F Continued boiler operation for prolonged p...

Страница 27: ...protection from low return water temperature 4 A hot water boiler installed above radiation level must be provided with a low water cutoff device as part of installation 5 A start up strainer is reco...

Страница 28: ...is not shown choose next higher value For materials or conditions other than those listed above refer to the National Fuel Gas Code NFPA 54 ANSI Z223 1 and or CAN CSA B149 1 Installation Codes or size...

Страница 29: ...6 0 78 1 0 3 1 0 824 0 44 23 1 11 5 5 3 2 1 0 97 1 4 4 1 1 1 049 0 56 29 4 14 7 6 8 2 6 1 23 1 8 5 3 1 1 380 0 74 38 6 19 3 8 9 3 5 1 6 2 3 6 9 Specific Gravity Correction Factor Specific Gravity Cor...

Страница 30: ...rated pipe or tile lining will cause severe injury or death C Install Draft Hood on canopy outlet Maintain height from Jacket Top Panel to Draft Hood skirt as shown in Figure 1 DO NOT ALTER CUT OR MOD...

Страница 31: ...on 2 Where two or more appliances vent into a common vent the area of the common vent should at least equal the area of the largest vent plus 50 of the area of the additional vents Do not connect the...

Страница 32: ...d to the common venting system are located and other spaces of the building Turn on clothes dryers and any appliance not connected to the common venting system Turn on any exhaust fans such as range h...

Страница 33: ...enced by drafts or restricted air flow hot or cold pipes lighting fixtures television or sunlight Allow free air movement by avoiding placement of furniture near thermostat Set heat anticipator to mat...

Страница 34: ...is causes the damper to close When the damper blade reaches the fully closed position the damper motor is de energized POWER FAILURE The damper blade will stop in the position it was in when power fai...

Страница 35: ...y interrupts main burner operation when flames or excessive heat are present in vestibule Circulator continues to operate and Vent Damper if used remains open with call for heat Control is single use...

Страница 36: ...36 Figure 27 Wiring Diagram Standing Pilot 24V Continuous Circulation 806H 807HE...

Страница 37: ...37 Figure 28 Wiring Diagram Standing Pilot 24V Intermittent Circulation 806H 807HE...

Страница 38: ...ain burner operation when excessive flue gas spillage occurs Circulator continues to operate and Vent Damper if used remains open with call for heat If blocked vent switch is activated do not attempt...

Страница 39: ...39 Figure 29 Wiring Diagram Honeywell EI USA Canada 805 Only with Hydrostat 3200 Control...

Страница 40: ...40 Figure 30 Wiring Diagram Honeywell EI USA Continuous Circulation 806 810...

Страница 41: ...41 Figure 31 Wiring Diagram Honeywell EI USA Intermittent Circulation 806 810...

Страница 42: ...42 Figure 32 Wiring Diagram Honeywell EI Canada Continuous Circulation Natural 806H 810HE LP 806H 807HE...

Страница 43: ...43 Figure 33 Wiring Diagram Honeywell EI Canada Intermittent Circulation Natural 806H 810HE LP 806H 807HE...

Страница 44: ...culator continues to operate with call for heat Normal operation resumes when water temperature falls below set point ii Blocked Vent Switch Automatically interrupts main burner operation when excessi...

Страница 45: ...45 Figure 34 Wiring Diagram EP Ignition System Natural Gas Only Continuous Circulation EP CSD 1 Natural Gas USA Only 808HE 810HE...

Страница 46: ...46 Figure 35 Wiring Diagram EP Ignition System Natural Gas Only Intermittent Circulation EP CSD 1 Natural Gas USA Only 808HE 810HE...

Страница 47: ...ure 36 McDonnell Miller 751P MT 120V L W C O Wiring for Boilers with 24V Limit Circuits 806H 810HE Figure 37 McDonnell Miller 751P MT 120V L W C O Wiring for Boilers with 120V Limit Circuits EP 808HE...

Страница 48: ...38 Hydrolevel OEM 170 550 650 750 120V L W C O Wiring for Boilers with 24V Limit Circuits 806H 810HE Figure 39 Hydrolevel OEM 170 550 650 750 120V L W C O Wiring for Boilers with 120V Limit Circuits 8...

Страница 49: ...low from bucket until discharge from hose is bubble free for 30 seconds 8 Close the open zone valve or shut off valve for the zone being purged of air then open the zone valve or shut off valve for th...

Страница 50: ...50 Figure 40 Lighting Instructions 24V Standing Pilot...

Страница 51: ...51 Figure 41 Operating Instructions EI...

Страница 52: ...52 Figure 42 Operating Instructions EP...

Страница 53: ...controls to lowest setting 3 Remove burner access panel s 4 Open manual pilot valve s 5 Turn on main electric switch 6 Reset safety switch on flame safeguard relay 7 Intermittent electric ignition rec...

Страница 54: ...air injection Adjust primary air as follows Figure 45 Honeywell Q3481B Pilot Flame 24V Electronic Ignition Figure 44 Honeywell Q314 Pilot Flame 24V Standing Pilot Figure 46 Honeywell Q179C Pilot Flam...

Страница 55: ...inimum gas supply pressure listed on rating label contact gas supplier for assistance 3 Clock gas meter for at least 30 seconds Use Table 12 to determine gas flow rate in Cubic Feet per Hour 4 Determi...

Страница 56: ...sition Q Install Front Removable Panel 1 Engage top flange longer of 2 flanges behind Upper Front Panel 2 Swing lower portion of door toward boiler 3 Lower door to engage bottom flange behind Lower Fr...

Страница 57: ...foreign matter or restrictions Clean burners with a soft bristle brush blow any dirt out with compressed air or use a vacuum cleaner See Figure 48 E Clean Boiler Flueways See Figure 48 1 Shut down gas...

Страница 58: ...es and secured with hitch pin clips Verify Main Burner with Pilot Bracket is in proper location See Table 13 H Lubrication Manufacturers Instruction should be followed on all parts installed on boiler...

Страница 59: ...may not operate reliably over time Service call recommended Note This indication may flash temporarily during or shortly after lightoff on some applications Check gas supply pilot burner flame sense w...

Страница 60: ...rol remains in wait mode When the fault corrects control resumes normal operation after one minute delay Check transformer and AC line for proper input voltage to the control Check with full system lo...

Страница 61: ...61 Honeywell EI Trouble Shooting Guide...

Страница 62: ...717 293 5803 X Repair Parts r e l i o b n o n o i t a m r o f n i g n i k e e s n e h W r o t c a r t n o c g n i t a e h r u o y l l a c r e l i o b o t s r i a p e r r o e c i v r e s r o F l e b a...

Страница 63: ...1 6171609 1 6171610 1 1A Left End Section 7171601 1 1 1 1 1 1 1B Intermediate Section 7171603 3 4 5 6 7 8 1C Right End Section 7171602 1 1 1 1 1 1 1D Tie Rod 80861032 1 80861033 1 80861013 1 80861034...

Страница 64: ...ntity 805H 806H 807HE 808HE 809HE 810HE 2 Canopy 2A Canopy 6111605 1 6111606 1 61116071 1 6111608 1 61116091 1 61116110 1 2B Bolt Carriage 20 x 1 80860115 2 2 2 2 2 2 2C Washer Flat 80860603 2 2 2 2 2...

Страница 65: ...1816103 1 3E Burner Access Panel Assembly 61816054 1 61816064 1 61816074 1 61816084 2 61816094 2 61816104 2 3F Jacket Attachment Bracket 7041601 4 4 4 4 4 4 3G Bolt Carriage 20 x 1 80860106 4 4 4 4 4...

Страница 66: ...r with Pilot Bracket EP 8231603 1 1 1 1 1 4C Manifold 82216051 1 82216061 1 82216071 1 82216081 1 82216091 1 82216101 1 4D Pipe Plug 1 8 NPT Included with 4C 1 1 1 1 1 1 4E Main Burner Orifice 39 Natu...

Страница 67: ...B Solenoid Gas Valve Honeywell V8295A1024 NPT 81660235 806H 807HE 1 Solenoid Gas Valve Honeywell V8295A1032 1 NPT 81660236 808HE 810HE 1 C Manual Shut Off Valve Conbraco 50GB501A 1 NPT 822615 808HE 8...

Страница 68: ...LP Gas A Gas Valve Robertshaw 7000DERHC Natural Gas 1 NPT 81660151 805H 810HE 1 Gas Valve Robertshaw 7000DERHC LP LP Gas 1 NPT 81660158 USA 805H 810HE Canada 805H 807HE B Manual Shut Off Valve Conbrac...

Страница 69: ...lve Honeywell V8295A1024 NPT 81660235 806H 807HE 1 Solenoid Gas Valve Honeywell V8295A1032 1 NPT 81660236 808HE 810HE C Manual Shut Off Valve Conbraco 50GB501A 1 NPT 822615 806H 810HE 1 D Hex Bushing...

Страница 70: ...81660236 1 C Manual Shut Off Valve Conbraco 50 403 02 1 NPT 822615 1 D Leak Test Shut Off Valve Conbraco 50GB501A 1 8 x 1 8 822679 2 E Pipe Plug 1 8 806603594 2 F Hex Bushing 1 4 x 1 8 806600520 1 G...

Страница 71: ...Natural Gas 8236033 807HE 1 Pilot Burner Honeywell Q314A3828 LP Gas 8236034 B Thermocouple Honeywell Q309A1996 w 36 Lg Lead 8236004 C Brass Compression Union 1 4 OD Tube 8236008 806H 807HE 1 D Regula...

Страница 72: ...embly and Piping Intermittent Ignition Honeywell EI USA 5 10 Section Natural and LP Gas A Pilot Burner Honeywell Q3481B1206 Natural Gas 103704 01 805H 810HE 1 Pilot Burner Honeywell Q3481B1420 LP Gas...

Страница 73: ...1 C Shut Off Valve Essex P2L 822645 808HE 810HE 1 D Pipe Tee 1 8 NPT Malleable 806601005 E Pipe Plug 1 8 NPT Sq Head 806603508 F Brass Compression Adapter 1 4 OD Tube x 1 8 NPT 822630 807HE Natural Ga...

Страница 74: ...ling 1 4 OD Tube 8236008 806H 807HE USA Canada 808HE 810HE USA Only 1 G Shut Off Valve Essex P2L 822645 808HE 810HE Canada Only 1 H Pipe Tee 1 8 NPT Malleable 806601005 J Pipe Plug 1 8 NPT Sq Head 806...

Страница 75: ...gnition Lead Honeywell R1061012 3 Ft Lg 7136247 1 E Ground Wire Assembly 6136259 1 F Brass Compression Coupling 1 4 OD Tube 8236008 1 G Conbraco Leak Test Shut Off Cock 1 8 x 1 8 822679 1 H Brass Comp...

Страница 76: ...76...

Страница 77: ...11 1 7201613 1 7201615 1 7201617 1 6C Jacket Upper Rear Panel 70416056 1 70416066 1 70416076 1 70416086 1 70416096 1 70416106 1 6D Jacket Upper Rear Panel Insulation 72016059 1 72016069 1 72016079 1 7...

Страница 78: ...78...

Страница 79: ...ket Right Side Panel Lower Corner Insulation Piece 72016012 1 1 1 1 1 1 6Q Jacket Vestibule Panel 70416055 1 70416065 1 70416075 1 70416085 1 70416095 1 70416105 1 6R Jacket Vestibule Panel Upper Insu...

Страница 80: ...60302 1 1 1 1 1 1 D1 Nipple NPT x 3 806600038 1 1 1 1 1 1 E Drain Valve NPT Conbraco 35 302 03 806603061 1 1 1 1 1 1 E1 Nipple NPT x 3 806600038 1 1 1 1 1 1 E2 Coupling NPT 806602561 1 1 1 1 1 1 F Blo...

Страница 81: ...nd Automatic Vent Damper 8A Draft Hood 8111605 1 8111604 1 1 8111602 1 8111601 1 1 8B Automatic Vent Damper 7 Effikal RVGP 7 8116324 1 Automatic Vent Damper 8 Effikal RVGP 8 8116325 1 1 Automatic Vent...

Страница 82: ...82...

Страница 83: ...83...

Страница 84: ...84...

Отзывы: