Burnham 805H Скачать руководство пользователя страница 56

56

N.

  Adjust gas input rate to boiler.

 LP/Propane.

1.  Set thermostat to highest setting.
2.  Adjust tank regulator for gas valve inlet pressure of 

13.5 inches w.c. or less. 

3.  Gas valve has step opening regulator which initially 

opens to 1.4 or 2.5 inch w.c. and steps to full 

pressure after approximately 30 seconds. Check 

manifold pressure after step has occurred. Adjust gas 

valve pressure regulator as necessary for 10.0 inches 

w.c. (turn adjustment screw counterclockwise to 

decrease manifold pressure, or clockwise to increase 

manifold pressure). If 10.0 inches w.c. can not be 

attained, check gas valve inlet pressure. If less than 

11.0 inches w.c., contact gas supplier for assistance.

O.

  Clean Heating System

 

Oil, grease, and other foreign materials which 

accumulate in new hot water boilers and a new or 

reworked system should be boiled out, and then 

thoroughly flushed.  A qualified water treatment 

chemical specialist should be consulted for 

recommendations regarding appropriate chemical 

compounds and concentrations which are compatible 

with local environmental regulations.

P.

  Check Damper Operation

 - If boiler is equipped with 

vent damper, vent damper must be in open position 

when boiler main burners are operating. Start boiler, 

refer to instructions on damper to determine if damper 

is in full open position.

Q. 

Install Front Removable Panel.

1.  Engage top flange (longer of 2 flanges) behind 

Upper Front Panel.

2.  Swing lower portion of door toward boiler.
3.  Lower door to engage bottom flange behind Lower 

Front Tie Bar.

R.

 

Combustion Chamber Burn-Off

1.  The mineral wool combustion chamber panels 

contain a cornstarch based binder that must be 

burned out at installation to prevent odors during 

subsequent boiler operation.

2.  Ventilate the boiler room, set the high limit to its 

maximum setting, set the thermostat to call for heat.

3.  Allow the boiler to fire for at least an hour or until 

the odor from the cornstarch has dissipated.

4.  Return the high limit and thermostat to their desired 

settings.

S.

 

Review User’s Information Manual

 and system 

operation with owner or operator.

Model 805 Only:

IMPORTANT

This boiler is equipped with a feature that saves energy by reducing the boiler water temperature 

as the heating load decreases.  This feature is equipped with an override which is provided 

primarily to permit the use of an external energy management system that serves the same 

function.  THIS OVERRIDE MUST NOT BE USED UNLESS AT LEAST ONE OF THE 

FOLLOWING CONDITIONS IS TRUE:

  •   An external energy management system is installed that reduces the boiler   

       water temperature as the heating load decreases.
  •   This boiler is not used for any space heating.
  •   This boiler is part of a modular or multiple boiler system having a total input 

        of 300,000 BTU/hr or greater.
  •   This boiler is equipped with a tankless coil.

Содержание 805H

Страница 1: ...only be used by a qualified heating installer service technician BEFORE installing read all instructions in this manual and all other information shipped with the boiler Post all instructions and manu...

Страница 2: ...should be made to the following Standards USA BOILERS A Current Edition of American National Standard ANSI NFPA 31 Installation of Oil Burning Equipment for recommended installation practices B Curren...

Страница 3: ...othing and equipment when installing starting up or servicing this boiler to prevent scald injuries Do not rely on the pressure and temperature gauges to determine the temperature and pressure of the...

Страница 4: ...h cast iron section is permanently marked with the MAWP listed on the boiler s ASME Data Label The MAWP for all Series 8HE Boiler is 50 psi Water Only It is common and acceptable practice to install t...

Страница 5: ...sleeved loose fitting clothing 3 Gloves 4 Eye Protection Take steps to assure adequate ventilation Wash all exposed body areas gently with soap and water after contact Wash work clothes separately fr...

Страница 6: ...e Installation 8 II Boiler Assembly 10 III Gas Control System Assembly 17 Knockdown Boilers IV Water Trim and Piping 24 V Gas Piping 28 VI Venting 30 VII Electrical 33 VIII System Start up 49 IX Servi...

Страница 7: ...7 24 13 16 16 1 8 7 dia x 15 ft 11 9 600 610 806H 315 23 3 4 11 7 8 8 27 13 16 18 8 dia x 15 ft 13 9 690 700 807HE 340 27 1 2 13 3 4 8 27 13 16 18 8 dia x 15 ft 15 9 785 870 808HE 410 31 1 4 15 5 8 9...

Страница 8: ...with size of boiler a Front 18 b Top 51 c Draft hood rear sides and flue connector 6 3 Canada 805H 810HE a Top and front 18 45 7 cm b Flue rear and sides 6 15 2 cm D Provide clearance for servicing an...

Страница 9: ...least 1 2 5 cm from the sides and rear and 6 15 2 cm from the front Locate the opening within 12 inches 30 5 cm of top of space Size opening per following i Minimum free area of 1 square inch per 3 00...

Страница 10: ...rear corner of Base End Panel raise boiler and install 1 wood blocks under rear corners Install pipe roller between Base and skid 3 Remove 1 wood blocks Place 3 pipe roller on floor behind skid 4 Rol...

Страница 11: ...less than 50 psi gauge pressure Figure 4 Installation of Special Base for Combustible Flooring 6 Examine boiler for leaks or damage due to shipment or handling 7 Remove plugs from Return Tapping B Ta...

Страница 12: ...ated in Combination Boiler Parts and Control Carton 1 Attach Base Front Panel to Section Assembly using 20 x 1 carriage bolts washers and nuts 2 Seal between top of Base Front Panel and Section Assemb...

Страница 13: ...13 Figure 6 Flame Roll out Switch Installation Figure 7 Burner Burner Access Panel Installation...

Страница 14: ...rews 5 Remove Rating Label from envelope marked RATING LABEL ENCLOSED Remove Combustible Clearance Label from Combination Boiler Parts and Controls Carton Attach to Vestibule Panel in locations shown...

Страница 15: ...15 Figure 8 Jacket Assembly...

Страница 16: ...16 Figure 9 EP Control Installation...

Страница 17: ...4 Mount Transformer continuous circulation or Control Center intermittent circulation to Junction Box See Figure 8 a Canada only loop 4 nylon cable tie between junction box and transformer control ce...

Страница 18: ...18 Figure 10 Schematic Gas Piping 24V Standing Pilot 806H 807HE...

Страница 19: ...19 Figure 11 Main Gas Piping Intermittent Ignition EI...

Страница 20: ...20 Figure 12 Schematic Pilot Piping Honeywell EI USA...

Страница 21: ...21 Figure 13 Schematic Pilot Piping Honeywell EI Canada Natural Gas 805H 810HE LP Gas 806H 807HE...

Страница 22: ...22 Figure 14 Schematic Gas Piping EP Control System Natural Gas Only 806H 810HE...

Страница 23: ...23 Figure 15 Schematic Gas Piping EP CSD 1 Control System 808HE 810HE...

Страница 24: ...at the potential of severe burns is eliminated DO NOT pipe in any area where freezing could occur DO NOT install any shut off valves plugs or caps Consult Local Codes for proper discharge piping arran...

Страница 25: ...ping See Figure 19 a Install 2 NPT x 10 Nipple into Supply Tapping A See Figure 3 Figure 18 Temperature Pressure Gauge Installation Figure 19 Alternate Temperature Pressure Gauge Installation b Instal...

Страница 26: ...ty Burnham Commercial recommends maintaining temperature differential drop across the system at 40 F or less and return water temperature at minimum of 135 F Continued boiler operation for prolonged p...

Страница 27: ...protection from low return water temperature 4 A hot water boiler installed above radiation level must be provided with a low water cutoff device as part of installation 5 A start up strainer is reco...

Страница 28: ...is not shown choose next higher value For materials or conditions other than those listed above refer to the National Fuel Gas Code NFPA 54 ANSI Z223 1 and or CAN CSA B149 1 Installation Codes or size...

Страница 29: ...6 0 78 1 0 3 1 0 824 0 44 23 1 11 5 5 3 2 1 0 97 1 4 4 1 1 1 049 0 56 29 4 14 7 6 8 2 6 1 23 1 8 5 3 1 1 380 0 74 38 6 19 3 8 9 3 5 1 6 2 3 6 9 Specific Gravity Correction Factor Specific Gravity Cor...

Страница 30: ...rated pipe or tile lining will cause severe injury or death C Install Draft Hood on canopy outlet Maintain height from Jacket Top Panel to Draft Hood skirt as shown in Figure 1 DO NOT ALTER CUT OR MOD...

Страница 31: ...on 2 Where two or more appliances vent into a common vent the area of the common vent should at least equal the area of the largest vent plus 50 of the area of the additional vents Do not connect the...

Страница 32: ...d to the common venting system are located and other spaces of the building Turn on clothes dryers and any appliance not connected to the common venting system Turn on any exhaust fans such as range h...

Страница 33: ...enced by drafts or restricted air flow hot or cold pipes lighting fixtures television or sunlight Allow free air movement by avoiding placement of furniture near thermostat Set heat anticipator to mat...

Страница 34: ...is causes the damper to close When the damper blade reaches the fully closed position the damper motor is de energized POWER FAILURE The damper blade will stop in the position it was in when power fai...

Страница 35: ...y interrupts main burner operation when flames or excessive heat are present in vestibule Circulator continues to operate and Vent Damper if used remains open with call for heat Control is single use...

Страница 36: ...36 Figure 27 Wiring Diagram Standing Pilot 24V Continuous Circulation 806H 807HE...

Страница 37: ...37 Figure 28 Wiring Diagram Standing Pilot 24V Intermittent Circulation 806H 807HE...

Страница 38: ...ain burner operation when excessive flue gas spillage occurs Circulator continues to operate and Vent Damper if used remains open with call for heat If blocked vent switch is activated do not attempt...

Страница 39: ...39 Figure 29 Wiring Diagram Honeywell EI USA Canada 805 Only with Hydrostat 3200 Control...

Страница 40: ...40 Figure 30 Wiring Diagram Honeywell EI USA Continuous Circulation 806 810...

Страница 41: ...41 Figure 31 Wiring Diagram Honeywell EI USA Intermittent Circulation 806 810...

Страница 42: ...42 Figure 32 Wiring Diagram Honeywell EI Canada Continuous Circulation Natural 806H 810HE LP 806H 807HE...

Страница 43: ...43 Figure 33 Wiring Diagram Honeywell EI Canada Intermittent Circulation Natural 806H 810HE LP 806H 807HE...

Страница 44: ...culator continues to operate with call for heat Normal operation resumes when water temperature falls below set point ii Blocked Vent Switch Automatically interrupts main burner operation when excessi...

Страница 45: ...45 Figure 34 Wiring Diagram EP Ignition System Natural Gas Only Continuous Circulation EP CSD 1 Natural Gas USA Only 808HE 810HE...

Страница 46: ...46 Figure 35 Wiring Diagram EP Ignition System Natural Gas Only Intermittent Circulation EP CSD 1 Natural Gas USA Only 808HE 810HE...

Страница 47: ...ure 36 McDonnell Miller 751P MT 120V L W C O Wiring for Boilers with 24V Limit Circuits 806H 810HE Figure 37 McDonnell Miller 751P MT 120V L W C O Wiring for Boilers with 120V Limit Circuits EP 808HE...

Страница 48: ...38 Hydrolevel OEM 170 550 650 750 120V L W C O Wiring for Boilers with 24V Limit Circuits 806H 810HE Figure 39 Hydrolevel OEM 170 550 650 750 120V L W C O Wiring for Boilers with 120V Limit Circuits 8...

Страница 49: ...low from bucket until discharge from hose is bubble free for 30 seconds 8 Close the open zone valve or shut off valve for the zone being purged of air then open the zone valve or shut off valve for th...

Страница 50: ...50 Figure 40 Lighting Instructions 24V Standing Pilot...

Страница 51: ...51 Figure 41 Operating Instructions EI...

Страница 52: ...52 Figure 42 Operating Instructions EP...

Страница 53: ...controls to lowest setting 3 Remove burner access panel s 4 Open manual pilot valve s 5 Turn on main electric switch 6 Reset safety switch on flame safeguard relay 7 Intermittent electric ignition rec...

Страница 54: ...air injection Adjust primary air as follows Figure 45 Honeywell Q3481B Pilot Flame 24V Electronic Ignition Figure 44 Honeywell Q314 Pilot Flame 24V Standing Pilot Figure 46 Honeywell Q179C Pilot Flam...

Страница 55: ...inimum gas supply pressure listed on rating label contact gas supplier for assistance 3 Clock gas meter for at least 30 seconds Use Table 12 to determine gas flow rate in Cubic Feet per Hour 4 Determi...

Страница 56: ...sition Q Install Front Removable Panel 1 Engage top flange longer of 2 flanges behind Upper Front Panel 2 Swing lower portion of door toward boiler 3 Lower door to engage bottom flange behind Lower Fr...

Страница 57: ...foreign matter or restrictions Clean burners with a soft bristle brush blow any dirt out with compressed air or use a vacuum cleaner See Figure 48 E Clean Boiler Flueways See Figure 48 1 Shut down gas...

Страница 58: ...es and secured with hitch pin clips Verify Main Burner with Pilot Bracket is in proper location See Table 13 H Lubrication Manufacturers Instruction should be followed on all parts installed on boiler...

Страница 59: ...may not operate reliably over time Service call recommended Note This indication may flash temporarily during or shortly after lightoff on some applications Check gas supply pilot burner flame sense w...

Страница 60: ...rol remains in wait mode When the fault corrects control resumes normal operation after one minute delay Check transformer and AC line for proper input voltage to the control Check with full system lo...

Страница 61: ...61 Honeywell EI Trouble Shooting Guide...

Страница 62: ...717 293 5803 X Repair Parts r e l i o b n o n o i t a m r o f n i g n i k e e s n e h W r o t c a r t n o c g n i t a e h r u o y l l a c r e l i o b o t s r i a p e r r o e c i v r e s r o F l e b a...

Страница 63: ...1 6171609 1 6171610 1 1A Left End Section 7171601 1 1 1 1 1 1 1B Intermediate Section 7171603 3 4 5 6 7 8 1C Right End Section 7171602 1 1 1 1 1 1 1D Tie Rod 80861032 1 80861033 1 80861013 1 80861034...

Страница 64: ...ntity 805H 806H 807HE 808HE 809HE 810HE 2 Canopy 2A Canopy 6111605 1 6111606 1 61116071 1 6111608 1 61116091 1 61116110 1 2B Bolt Carriage 20 x 1 80860115 2 2 2 2 2 2 2C Washer Flat 80860603 2 2 2 2 2...

Страница 65: ...1816103 1 3E Burner Access Panel Assembly 61816054 1 61816064 1 61816074 1 61816084 2 61816094 2 61816104 2 3F Jacket Attachment Bracket 7041601 4 4 4 4 4 4 3G Bolt Carriage 20 x 1 80860106 4 4 4 4 4...

Страница 66: ...r with Pilot Bracket EP 8231603 1 1 1 1 1 4C Manifold 82216051 1 82216061 1 82216071 1 82216081 1 82216091 1 82216101 1 4D Pipe Plug 1 8 NPT Included with 4C 1 1 1 1 1 1 4E Main Burner Orifice 39 Natu...

Страница 67: ...B Solenoid Gas Valve Honeywell V8295A1024 NPT 81660235 806H 807HE 1 Solenoid Gas Valve Honeywell V8295A1032 1 NPT 81660236 808HE 810HE 1 C Manual Shut Off Valve Conbraco 50GB501A 1 NPT 822615 808HE 8...

Страница 68: ...LP Gas A Gas Valve Robertshaw 7000DERHC Natural Gas 1 NPT 81660151 805H 810HE 1 Gas Valve Robertshaw 7000DERHC LP LP Gas 1 NPT 81660158 USA 805H 810HE Canada 805H 807HE B Manual Shut Off Valve Conbrac...

Страница 69: ...lve Honeywell V8295A1024 NPT 81660235 806H 807HE 1 Solenoid Gas Valve Honeywell V8295A1032 1 NPT 81660236 808HE 810HE C Manual Shut Off Valve Conbraco 50GB501A 1 NPT 822615 806H 810HE 1 D Hex Bushing...

Страница 70: ...81660236 1 C Manual Shut Off Valve Conbraco 50 403 02 1 NPT 822615 1 D Leak Test Shut Off Valve Conbraco 50GB501A 1 8 x 1 8 822679 2 E Pipe Plug 1 8 806603594 2 F Hex Bushing 1 4 x 1 8 806600520 1 G...

Страница 71: ...Natural Gas 8236033 807HE 1 Pilot Burner Honeywell Q314A3828 LP Gas 8236034 B Thermocouple Honeywell Q309A1996 w 36 Lg Lead 8236004 C Brass Compression Union 1 4 OD Tube 8236008 806H 807HE 1 D Regula...

Страница 72: ...embly and Piping Intermittent Ignition Honeywell EI USA 5 10 Section Natural and LP Gas A Pilot Burner Honeywell Q3481B1206 Natural Gas 103704 01 805H 810HE 1 Pilot Burner Honeywell Q3481B1420 LP Gas...

Страница 73: ...1 C Shut Off Valve Essex P2L 822645 808HE 810HE 1 D Pipe Tee 1 8 NPT Malleable 806601005 E Pipe Plug 1 8 NPT Sq Head 806603508 F Brass Compression Adapter 1 4 OD Tube x 1 8 NPT 822630 807HE Natural Ga...

Страница 74: ...ling 1 4 OD Tube 8236008 806H 807HE USA Canada 808HE 810HE USA Only 1 G Shut Off Valve Essex P2L 822645 808HE 810HE Canada Only 1 H Pipe Tee 1 8 NPT Malleable 806601005 J Pipe Plug 1 8 NPT Sq Head 806...

Страница 75: ...gnition Lead Honeywell R1061012 3 Ft Lg 7136247 1 E Ground Wire Assembly 6136259 1 F Brass Compression Coupling 1 4 OD Tube 8236008 1 G Conbraco Leak Test Shut Off Cock 1 8 x 1 8 822679 1 H Brass Comp...

Страница 76: ...76...

Страница 77: ...11 1 7201613 1 7201615 1 7201617 1 6C Jacket Upper Rear Panel 70416056 1 70416066 1 70416076 1 70416086 1 70416096 1 70416106 1 6D Jacket Upper Rear Panel Insulation 72016059 1 72016069 1 72016079 1 7...

Страница 78: ...78...

Страница 79: ...ket Right Side Panel Lower Corner Insulation Piece 72016012 1 1 1 1 1 1 6Q Jacket Vestibule Panel 70416055 1 70416065 1 70416075 1 70416085 1 70416095 1 70416105 1 6R Jacket Vestibule Panel Upper Insu...

Страница 80: ...60302 1 1 1 1 1 1 D1 Nipple NPT x 3 806600038 1 1 1 1 1 1 E Drain Valve NPT Conbraco 35 302 03 806603061 1 1 1 1 1 1 E1 Nipple NPT x 3 806600038 1 1 1 1 1 1 E2 Coupling NPT 806602561 1 1 1 1 1 1 F Blo...

Страница 81: ...nd Automatic Vent Damper 8A Draft Hood 8111605 1 8111604 1 1 8111602 1 8111601 1 1 8B Automatic Vent Damper 7 Effikal RVGP 7 8116324 1 Automatic Vent Damper 8 Effikal RVGP 8 8116325 1 1 Automatic Vent...

Страница 82: ...82...

Страница 83: ...83...

Страница 84: ...84...

Отзывы: