Page 5
Ventilation Requirements
1. For this model additional ventilation is not normally required in the room that the fire is
fitted. However, if spillage is detected during spillage test additional ventilation may be
required. In GB reference should be made to BS 5871:Part 2, and in IE, reference should
be made to the current edition of I.S.813 which makes clear the conditions that must be
met to demonstrate that sufficient ventilation is available.
2. Any purpose provided ventilation must be checked periodically to ensure it is free from
obstructions.
3. When fitting the fire in Northern Ireland (NI), purpose provided ventilation must be
provided in accordance with the rules in force.
4. In other EC countries equivalent rules in force must be used.
Gas Supply
1. This gas fire is suitable for use with Natural Gas (12H) at 20mbar +/- 1 mb supply
pressure.
2. Connection to the gas supply must be made using rigid or semi-rigid tubing.
3. A separate means of isolating the gas supply should be provided near to the appliance to
facilitate servicing. An isolating valve has been supplied for this purpose.
Electrical Supply
1. If necessary install a mains socket near the appliance.
2. Plug the power supply / transformer unit into an adjacent socket and route the cable to the
appliance and insert the DC plug into the socket behind the fret on the left hand side of the
appliance. The cable should be installed through a conduit sufficiently large to
accommodate the DC plug so that replacement of the power supply / transformer unit is
possible. The fan is switched automatically as the fire warms and cools.
Note; the power supply unit is supplied with a selection of DC plugs. Choose the one that
fits the socket on the fire and connect it to the socket on the lead from the PSU with side
showing centre positive next to the arrow.
2.1.
Important Note About ODS Pilot
This fire is fitted with an ODS pilot which causes the appliance to shut down in the event of a
reduction of oxygen (e.g. caused by poor ventilation) in the room. Should this happen, follow
the lighting instructions to re-light the fire. In the event that the fire should shut down again,
do NOT attempt to re-light it but contact your gas installer for remedial action to be taken.
Under no circumstances should it be adjusted or put out of action by the installer
or the user. If the pilot needs replacing, only the approved part (available from
your supplier or Burley Magiglo.) should be fitted. Note: if any part of the pilot
assembly becomes faulty the complete assembly will need replacing.